Air -Conditioner s For Building Application OUTDOOR UNIT PUHY-P-TGMU-A GB F INST ALLA TION MANU AL F or saf e and correct use, please read this installation man ual thoroughly bef ore installing the air-conditioner unit.
2 (Unit : mm [in]) L 1 L 2 450 [17-23/32] 100 [3-15/16] 5 [Fig. 5.0.1] [Fig. 6.0.1] 1 P72 ~ P144 6 <B> (2) C 45 ° = > 300 [11-13/16] = > 1000 [39-3/8] = > <A> A L 2 = > L 1 = .
3 8 8.2 [Fig. 8.2.1] B A A B C D e a No.1 No.2 No.3 No.4 No.5 b c d C C CC C B A a b c d e C D C C C C A No.1 No.2 No.3 No.4 No.5 A : Outdoor unit B : First branch C : Indoor unit D : Cap 7 [Fig. 7.1.1] B A A : M10 anchor bolt procured at the site. B : Cor ner is not seated.
4 D C C B B E F G H I J A LO HI LO HI B A K J L H M C D E N O F G I [Fig. 9.3.1] [Fig. 9.3.3] [Fig. 9.3.2] 9.3 A A : Nitrogen gas B : T o indoor unit C : System analyzer D : Lo knob E : Hi knob F : Ba.
5 10.4 10 9.4 [Fig. 9.4.4] [Fig. 9.4.3] [Fig. 9.4.2] C A B D E [Fig. 9.4.1] [Fig. 10.4.1] BA C ~208 – 230V BA ~208 – 230V E E D E E [Fig. 10.2.1] [Fig.
6 GB D F E I NL P GR RU TR CZ SV SL HG PO Contents 1. Safety precautions 1.1. Bef ore installation and electric work s Before installing the unit, make sure you read all the “Saf ety precautions”. s The “Safety precautions” pr ovide very impor tant points re- garding saf ety .
7 GB D F E I NL P GR RU TR CZ SV SL HG PO • Install the power cable so that tension is not applied to the cable. - T ension ma y cause the cable to break and generate heat and cause a fire . • Install a leak circuit breaker , as required. - If a leak circuit breaker is not installed, electric shock ma y result.
8 GB D F E I NL P GR RU TR CZ SV SL HG PO 3. Specifications Model Noise le vel (50/60 Hz) External static pressure Cooling mode: – 5 ° CDB ~ 43 ° CDB [23 ° FDB ~ 109 ° FDB] (0 ° CDB ~ 43 ° CDB [32 ° FDB ~ 109 ° FDB] with outdoor unit at lower position) Heating mode: – 20 ° CWB ~ 15.
9 GB D F E I NL P GR RU TR CZ SV SL HG PO 7. Installation of unit 7.1. Installation [Fig. 7.1.1] (P .3) A M10 anchor bolt procured at the site. B Corner is not seated. • Fix unit tightly with bolts so that unit will not fall do wn due to ear thquake or gust of wind.
10 GB D F E I NL P GR RU TR CZ SV SL HG PO 9. Additional refrigerant charge At the time of shipping, the outdoor unit is charged with the refrigerant. As this charge does not include the amount needed for e xtended piping, additional charg- ing for each refrigerant line will be required on site .
11 GB D F E I NL P GR RU TR CZ SV SL HG PO Appropriate tightening torque by torque wrench: Copper pipe e xternal dia. (mm [in]) Tightening torque (N·m/kg·cm) ø6.35 [1/4] 14 to 18 / 140 to 180 ø9.52 [3/8] 35 to 42 / 350 to 420 ø12.7 [1/2] 50 to 57.
12 GB D F E I NL P GR RU TR CZ SV SL HG PO Note: • When using polyeth ylene cover as co vering material, asphalt roofing shall not be required. • No heat insulation must be pr ovided f or electric wires. [Fig. 9.4.2] (P .5) A Liquid pipe B Gas pipe C Electric wire D Finishing tape E Insulator [Fig.
13 GB D F E I NL P GR RU TR CZ SV SL HG PO h. The group setting operations among the multiple indoor units is done b y the remote controller (RC) after the electr ical power has been turned on.
14 GB D F E I NL P GR RU TR CZ SV SL HG PO 11. T est run W arning: • Be sure to use specified wires to connect so that no external f orce is imparted to terminal connections. If connections are not fixed firmly , it ma y cause heating or fire. • Be sure to use the appropriate type of o vercurrent pr otection switch.
15 GB D F E I NL P GR RU TR CZ SV SL HG PO 12. Inf ormation on rating plate P72 7.0 [15 LBS 7oz] 222 [490] Model Refrigerant (R410A) kg Allowable pressure (Ps) Net weight kg [LBS] P96 9.5 [20 LBS 16oz] 237 [524] P108 9.5 [20 LBS 16oz] 237 [524] P126 13.
WT04551X01 Printed in Japan HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MAR UNOUCHI, CHIY ODA-KU , T OKY O 100-8310, JAP AN Please be sure to put the contact address/telephone number on this manual before handing it to the customer. This product is designed and intended for use in the residential, commer- cial and light-industrial environment.
Een belangrijk punt na aankoop van elk apparaat Mitsumi electronic PUHY-P-TGMU-A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Mitsumi electronic PUHY-P-TGMU-A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Mitsumi electronic PUHY-P-TGMU-A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Mitsumi electronic PUHY-P-TGMU-A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Mitsumi electronic PUHY-P-TGMU-A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Mitsumi electronic PUHY-P-TGMU-A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Mitsumi electronic PUHY-P-TGMU-A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Mitsumi electronic PUHY-P-TGMU-A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.