3M ™ C old Shrink QT - II I Si licone R ub b e r Sk ir ted T ermination K it With Hi gh-K Stress R el i ef Fo r T ap e Shield ed, W ire S hielde d a nd U niS hield ® Ca ble 7 68 4-S -8 Ins tr uc tions IEEE Std. No. 48 Class 1 T ermination 35 kV Class 200 kV BIL F CAUTION Working around energized systems may cause serious injury or death.
2 78-81 17-0985-2 Rev C 1.0 Kit Contents 3 High-K, T racking Resistant, Silicone Rubber T erminations 3 Preformed Ground Braids 3 Constant Force Springs 3 3M™ EMI Copper Foil Shielding T ape 1 181 S.
78-81 17-0985-2 Rev C 3 Instruc tions For T a pe Shielded Ca ble 2.0 Pr epare Cable 2.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 2.2 Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug.
4 78-81 17-0985-2 Rev C 3.0 Install Ground Br aid 3.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 2). Cut off excess.
78-81 17-0985-2 Rev C 5 3.3 W rap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 4). Cinch (tighten) the spring after wrapping the final winding.
6 78-81 17-0985-2 Rev C 4.0 Install Lug or Connector 4.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 6) will not fit through the termination core, clean the insulation (per Step 5.
78-81 17-0985-2 Rev C 7 6.0 Install T er mination 6.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7).
8 78-81 17-0985-2 Rev C In structions fo r Wire Sh iel ded Ca ble 7.0 Prepare Cable 7.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 7.2 Prepare cable using dimensions shown in Figure 8 and 9. Refer to T able 3 for semi-con cutback dimension.
78-81 17-0985-2 Rev C 9 8.0 Install Ground Braid 8.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess.
10 78-81 17-0985-2 Rev C 8.3 W rap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring after wrapping the final winding.
78-81 17-0985-2 Rev C 11 9.0 Install Lug or Connector 9.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 14) will not fit through the termination core, clean the insulation (per Step 10.
12 78-81 17-0985-2 Rev C 11.0 Install T er mination 1 1.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 15).
78-81 17-0985-2 Rev C 13 Ins t ru c t ion s for U niS hield ® Shielde d Cable 12.0 Prepare Cable 12.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 12.2 Prepare cable using dimensions shown in Figure 16, 17 and 18.
14 78-81 17-0985-2 Rev C 12.4 Remove constant force spring. Carefully bend shield wires back upon cable jacket 1 1/2" (38 mm). Cut excess shield wire and discard (Figure 17). 1 1/2 (38 mm) Semi-Conductive Ja ck et F old Back Shield Wires Depth of T er minal Lug + Growth All ow ance [A] + 3” (76 mm) Figure 17 12.
78-81 17-0985-2 Rev C 15 13.0 Install Ground Braid 13.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires ( Figur e 19 ).
16 78-81 17-0985-2 Rev C 13.3 W rap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 21). Cinch (tighten) the spring after wrapping the final winding.
78-81 17-0985-2 Rev C 17 14.0 Install Lug or Connector 14.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.
18 78-81 17-0985-2 Rev C 16.0 Install T er mination 16.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 24).
78-81 17-0985-2 Rev C 19 T ooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper Lugs 30014 thru 30045 One hole 31036 thru 31068 One hole-long barrel Cable Size AWG/ kcmil Stud Size (in.
20 78-81 17-0985-2 Rev C T ooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 T wo hole Cable Size AWG/ kcmil Stud Size (in.) 3M™ Scotchlok ™ Lug Number Crimping T ool-Die Sets (Minimum Number Of Crimps) Burndy Corporation Thomas & Betts Corporation Square D Co.
78-81 17-0985-2 Rev C 21 T ooling Index Crimping Information for 3M™ Stem Connectors Copper/Aluminum Conductor Size AWG & kcmil 3M™ Connec - tor Number Crimping T able For 3M™ Stem T ype Connector Recommended Crimping T ools Stranded Solid Manufacturer Mech.
3M, Scotch and Scotchlok are trademarks of 3M Company . UniShield is a registered trademark of General Cable T echnologies Corporation. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed.
Een belangrijk punt na aankoop van elk apparaat 3M 7684-S-8 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen 3M 7684-S-8 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens 3M 7684-S-8 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding 3M 7684-S-8 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over 3M 7684-S-8 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van 3M 7684-S-8 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de 3M 7684-S-8 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met 3M 7684-S-8 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.