RTU-DNET DeviceNet Remote I/O Communication Module Application Manual.
.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 1 Warning 3 Please r ead this instruction car efully before use and follow th is instruction to operate the device in or der to pr event damages on the device or injuries to staff.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 2 4.3 DeviceNet I/O Mapping Data .................................................................................................... 1 4 4.4 Example .....................
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 3 1 Introduction 1. T o ensure correct installatio n and operation of RTU- DNET , please read this chapter carefully before u sing your RTU-DNET . 2. This chapter only provides introdu ctory informat ion on RTU-DNET .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 4 Baud rates 125 kbps; 250 kb p s; 500 kbps Electrical specification V oltage 1 1 ~ 25 VDC, supplied by internal bus.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 5 Default I/O mapping data (DeviceNet → RTU-DNE T) I/O mapping data (RTU- DNET → DeviceNet) S pecial module (model n.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 6 2.3 DeviceNet Connection Port The connector is used on t he co nnection to DeviceNet.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 7 OFF When DeviceNet is off, the I/O dat a in the buffer area will be cl eared. IN0 ON When DeviceNet is off, the I/O dat a in the buffer area will be held. IN1 Reserved Note: z Please set up the function switch when the power i s switched of f.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 8 3.3 Connecting to DeviceNet Connection Port z The colors on the PINs on the DeviceNet connection port match the colo rs of the connection cables. Make sure you connect the cable to the right PIN.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 9 No. Item Unit Explanation 5 Length of input data of special module Wor d The length of input data of the sp eci al mod.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 10 Byte position Data written into special module Data read from spe cial module 1 R/R[0]+Service Code[0x10] R/R[0]+Serv.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 11 Attribute ID Access rule Name Range Default Explanation 8 Get S tatus word 0~255 N/A Displaying the statu s of R TU-DNET . See 4.3 for more det ails. 9 Get/Set Control word N/A N/A For setting up the mode of RTU-DNET , e.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 12 Attribute ID Access rule Name Range Default Explanation 1 S pecial module and configuration inconsistent 0 Configurat.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 13 Attribute ID Access rule Name Range Default Explanation 30 Get/Set S tart CR for module 6 input data N/A N/A S tart C.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 14 Attribute ID Access rule Name Range Default Explanation 61 Get/Set Output data length for module 6 N/A N/A Length of .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 15 bit S tatus value Explanation 2 0/1 Reserved 3 0/1 Reserved 4 0/1 Reserved 5 0/1 Reserved 6 0/1 Reserved 7 0/1 Reserv.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 16 bit S tatus value Explanation 14 0/1 Reserved 15 0/1 Reserved 2. I/O dat a map ping If the I/O data do not inclu .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 17 Master (byte) RTU -DNET … … z RTU -DNET → DeviceNet mas ter Master (byte) RTU -DNET 0 Low byte of status word o.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 18 Item Content Software screen DIDO Input Points (X) 16 bit s DIDO Output Points (Y) 8 bits AIAO Module Number 4 Input .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 19 (2) Double click on R TU-DNET ico n, and the “Node Configuration…” dialo g box will appear . (3) Click on “IO Configure …” button in “Nod e Cnfiguration…” dialog box, and you will then see “R TU Configuration” pag e.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 20 (5) Click on “OK”. DeviceNetBuilder will then display the spe cial module conne cted and the number of digit al I/O points on the “R TU Configuration” p age.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 21 (8) Click on “OK” in “AIAO Module Configuration” page and return to “R TU Configuration” pag e. (9) Click on “Dowload” to download the configu ration to RTU-DNET .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 22 5 How to Construct a DeviceN et Netw ork Using RTU-DNET In this section, we will explain ho w to co nfigure RTU-DNET a nd the I/O mapping relation between R T U-DNET and DVPDNET -SL by an application example.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 23 (2) Select “Setup” => “Communication S etting” => “System Channel”, and the “Serial Port Setting” dialog box will appear . (3) Set up the communication p arameters in the PC and DVP-SV , e.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 24 (6) Click on “OK”, and DeviceNetBuilder will st art to scan the entire network. (7) If the bar on the dialog box does not progre ss, it mean s the co nnection between the PC and DVP-SV is abnormal, or there are other program s also u sinig the COM port on the PC.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 25 (9) Click on “IO Configure … ” button in “Nod e Conf iguration" dialog box, and you will then see “R TU Configuration” pag e. (10) Click on “Scan IO”, and the “W arning” dialog box will appear .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 26 (12) Double click on RT U-DNET icon, and y ou will then see “RTU Setup” dialog box.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 27 Item Function Default IO Module Error T r eatment How RTU-DNET will react when it detect s errors. Y ou can choose “Ignored”, “Alarm” o r “S top DeviceNet IO”.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 28 (3) Confirm all the settings and cli c k on “OK”. Next, dow nload the configuration to DVPDNET -SL. If DVP-SV is in RUN mode while you are downl oad ing the co nfiguration, a "W arning” dialog box will appear .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 29 (1) DVPDNET -SL → RTU-DNET Register in DVPDNET -SL Devices in extension module D6287H High byte of CH1 on DVP-02DA .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 30 Register in DVPDNET -SL Devices in extension module D6287H High byte of control word in RTU-DNET D6287L RTU- DNET con.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 31 6 LED Indicator & T rouble-shooting There are five LED indicators on R TU-DNET . POWER LE D displays if the power of R TU-DNET is workin g normally . RUN LED displa ys the wo rking status of R T U-DNET .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 32 LED status Indication How to correct voltage 2. Acquire diagnostic information through DeviceNetBuilder . Red light on Fatal error; errors in configuration dat a Acquire diagnostic information throu gh DeviceNetBuilder .
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 33 Common services Implemented for Service c ode Class Instan ce Service name 0x05 No Y es Reset 0x0E Y es Y es Get_Attr.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 34 Implemented for Service c ode Class Inst ance Service name 0x10 No Y es Set_Attribute_Single 0x4B No Y es Allocate_Ma.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 35 Common services Implemented for Service c ode Class Inst ance Service name 0x05 No Y es Re set 0x0E Y es Y es Get_Att.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 36 Attribute ID Acces s rule Name Range Default Explanation offline treatm ent 0: Ignored 1: Alarm 2: S top DeviceNet IO 12 Get/Set S pecial module error treatment 0 ~ 2 1 How RTU-DNET will react when it detects erro rs.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 37 Attribute ID Acces s rule Name Range Default Explanation 1 S pecial module unidentifiable b5 ~ b15 Reserved 5 Get/Set.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 38 Attribute ID Access rule Name Range Default Explanation for module 1 52 Get/Set S tart CR for module 2 output data N/.
DeviceNet Remote I/O Comm unication Module R TU-DNET DVP-PLC Application Manual 39 Attribute ID Access rule Name Data type … … … UINT 9 Get/Set Content in CR#8 UINT 10 Get/Set Content in CR#9 UI.
Een belangrijk punt na aankoop van elk apparaat Delta Electronics RTU-DNET (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Delta Electronics RTU-DNET heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Delta Electronics RTU-DNET vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Delta Electronics RTU-DNET leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Delta Electronics RTU-DNET krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Delta Electronics RTU-DNET bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Delta Electronics RTU-DNET kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Delta Electronics RTU-DNET . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.