www.eaton.com Net w ork Management Card User manual Network Management Ca rd – User Manual 34003991EN/EB Page 1/118.
Network Management Ca rd – User Manual 34003991EN/EB Page 2/118 Contents 1 EATON NET W O RK SOLUTION 5 1.1 G ENERAL P RESENTATION 5 1.1.1 Connecting the U PS to the Ethernet network 6 1.1.2 Protection of the co mputers/servers 6 1.1.3 Supervision of the UPSs over the network 7 1.
Network Management Ca rd – User Manual 34003991EN/EB Page 3/118 4.3.1 Email Notification 43 4.3.2 E-mail Message Set tings 45 4.4 C ONFIGURATION 47 4.4.1 Network settings 48 4.4.2 System 50 4.4.3 Notified A pplications 52 4.4.4 Central shutdo wn configuration 54 4.
Network Management Ca rd – User Manual 34003991EN/EB Page 4/118 7.4 JBUS TABLE 91 7.4.1 Data for Pulsar 700 / 1000 / 1500 91 7.4.2 Data for Pulsar M 2200 / 3000 93 7.4.3 Data for Pulsar MX 4000 / 5000 / 1 0000 and EX 5 / 7 / 11 RT 95 7.4.4 Data for Pulsar MX frame 15 / 20 97 7.
Network Management Ca rd – User Manual 34003991EN/EB Page 5/118 1 EATON Netw o rk Solution 1.1 General Presentation EATON Network Solution : - Provides infor mation on event s concerning the sup ply.
Network Management Ca rd – User Manual 34003991EN/EB Page 6/118 1.1.1 Connecting the UPS to the Ethernet network This function can be performed t hrough network Cards inserted in the U PS (Network Management Card). A lso a softw are "agent" running on a nearby PC that is called the Network Manageme nt Proxy can be used.
Network Management Ca rd – User Manual 34003991EN/EB Page 7/118 1.1.3 Supervision of the UPSs over the netw o rk Depending on y our needs, y ou can either use: Your Internet bro wser to monitor eac .
Network Management Ca rd – User Manual 34003991EN/EB Page 8/118 1.1.4.1 How to connect UPS / agent / network: Insert the optional card in the U PS and connect the UP S to the computer network. Start the UPS, then the computers. 1.1.4.2 Setting up the protec tion: Set up the Net work Management Card (s ee user manual).
Network Management Ca rd – User Manual 34003991EN/EB Page 9/118 Network Management Ca rds are com patible with the "Enterprise Power Management" superv ision sys tem, with the MGE Office Protect ion Syst ems network protection sy stem and with Po werware Netwatch.
Network Management Ca rd – User Manual 34003991EN/EB Page 10/118 1.3 Technical data 1.3.1 Hardware characteristics Dimensions Dimensions (L x l x H) 132 x 66 x 42 mm Weight (gr) 70 g Storage Storage.
Network Management Ca rd – User Manual 34003991EN/EB Page 11/118 1.3.4 A dminis tration Up to 35 workstat ions(in TCP co nnected mode) or u p to 100(in UDP broa dcasted mode) prot ected by Network Shutdown Modules - Central or l ocal configuration .
Network Management Ca rd – User Manual 34003991EN/EB Page 12/118 ◗ Recording of events and measurements in the card log ◗ Possibility of shutting down the installation in the event of a thres ho.
Network Management Ca rd – User Manual 34003991EN/EB Page 13/118 1.3.8 Default parameters Function Parameter Default value Possible value Network IP address 166.99.16.16 Network IP address Subnet mask 255.255.0.0 Network IP address Gateway A ddress 0.
Network Management Ca rd – User Manual 34003991EN/EB Page 14/118 2 Installation 2.1 Unpacking and check on contents The installation kit contents: ◗ A Network Management Card (661 02) ◗ A serial communication cable for confi guration (34003918 ) ◗ Installation manual (34003905) 2.
Network Management Ca rd – User Manual 34003991EN/EB Page 15/118 Ethernet port LED Colour A ctivit y Description ACT Green ◗ Off ◗ Card not connected t o the net work. ◗ On ◗ Card connected to the network but without activity ◗ Flashing ◗ Port is active in rec eiving / transmission 100M Orange ◗ Off ◗ Port operating at 10 Mbits/s.
Network Management Ca rd – User Manual 34003991EN/EB Page 16/118 2.4 Sensor installation (option) The Environment sens or is available as a n option on the Net work Management Card and is availa ble from MGE Office Protection Sy stems (reference 66 846).
Network Management Ca rd – User Manual 34003991EN/EB Page 17/118 3 Configuration 3.1 Configure IP parameters Once the card has start ed: Connect one end of the cable (3400 3918) to the Service po rt. If the environment sensor was prev iously connected, the card must be restart ed in order to acce ss the conf iguration menu.
Network Management Ca rd – User Manual 34003991EN/EB Page 18/118 3.1.1 Your network is equipped with a DHCP serv er The card is configure d by default with this service activa ted.
Network Management Ca rd – User Manual 34003991EN/EB Page 19/118 3.1.2 Your network is not equipped with a DHCP server In the main menu enter 2, then 2 again .
Network Management Ca rd – User Manual 34003991EN/EB Page 20/118 4 Supervision and a dministration by browser ◗ On a computer equ ipped with a Web browser (Internet Explorer, FireF ox or Netscape reco mmended), enter the address initialised previously in the Installation chapter (e.
Network Management Ca rd – User Manual 34003991EN/EB Page 21/118 4.2 UPS 4.2.1 UPS properties page This page is automatica lly refreshed every 10 sec onds. From this page, acce ss to the m ain UPS information is available thank s to the combo b ox (see scree n copy below).
Network Management Ca rd – User Manual 34003991EN/EB Page 22/118 4.2.1.1 "UPS" zone: general information on the UPS . Indication of the picture and gener ic name of the UPS range Computer room : Customised name of your sy stem. You can change th is name on th e "System" page.
Network Management Ca rd – User Manual 34003991EN/EB Page 23/118 UPS without auto matic by pass Note: In case of loss of commu nication with the UPS , all the ele ments of the sy noptic are grey .
Network Management Ca rd – User Manual 34003991EN/EB Page 24/118 ◗ Battery : Remaining capacity > 50% Remaining capacity < 50% Battery to be checked (battery test result) ◗ Battery Output .
Network Management Ca rd – User Manual 34003991EN/EB Page 25/118 ◗ A C A utomatic By pass Flow : Energy flow present No energy flow ◗ A C A utomatic By pass Status : Powered Not powered Internal.
Network Management Ca rd – User Manual 34003991EN/EB Page 26/118 ◗ UPS measurements : ◗ Boxes showing measure ments appear when sy noptic elements are hovered by the pointer. See ex ample below. These measurements are availa ble for AC to DC convert er, Battery , DC to AC converte r and automatic by pass.
Network Management Ca rd – User Manual 34003991EN/EB Page 27/118 4.2.1.2 "UPS status" zone: Essential informat ion ◗ "Active sources ": (available on paralle l or modular UPS) x UPS + y UPS redundant : x indicates the m inimal number of UPS necessary to power the load, y indicates the number of UPS i n redundancy .
Network Management Ca rd – User Manual 34003991EN/EB Page 28/118 4.2.1.3 Viewing the modules ◗ Click on "UPS Modules" scroll lis t to view the infor mation about the UPS mo dules.
Network Management Ca rd – User Manual 34003991EN/EB Page 29/118 ◗ The Status can take the next forms: or when the mo dule is working properly with no alarm. when the module has at least one alar m (level Warnin g) active. when the module has at least one alar m (level Critical) act ive.
Network Management Ca rd – User Manual 34003991EN/EB Page 30/118 4.2.1.4 Viewing the alarms Click on "A larm Table" scroll list to vie w the list of current alarms.
Network Management Ca rd – User Manual 34003991EN/EB Page 31/118 ◗ A larm table for modular UPS.
Network Management Ca rd – User Manual 34003991EN/EB Page 32/118 4.2.1.5 Viewing the “Abou t your UPS” window Click on "A bout your UPS" scroll list to view the informati on about the U PS and the card .
Network Management Ca rd – User Manual 34003991EN/EB Page 33/118 4.2.2 On-line help On-line contextual help in Engli sh is available at the top of each page by clicking on the Help link, which is a lway s located on the top r ight corner. T he navigation menu of the on-line he lp is identical to that of the card's pa ges.
Network Management Ca rd – User Manual 34003991EN/EB Page 34/118 4.2.3 UPS control Click on the "UPS C ontrol" section in the menu The parameters of t his menu can on ly be modified af ter entering the "Log in" and "Pass word".
Network Management Ca rd – User Manual 34003991EN/EB Page 35/118 UPS configuration may prevent the shutdown and rest art comma nds from being properly run. Read the UP S user manual for more information. This page enables tr iggering of startup and shutdo wn sequence s for the UPS main output and c ontrolled outlets.
Network Management Ca rd – User Manual 34003991EN/EB Page 36/118 "Immediate On" : A sequenc e to switch on output p ower is launc hed immediately .
Network Management Ca rd – User Manual 34003991EN/EB Page 37/118 4.2.4 UPS weekly schedule programmi ng Click on the "Weekly schedule" section of the menu . UPS configuration may prevent the shutdown and rest art comma nds from being properly run.
Network Management Ca rd – User Manual 34003991EN/EB Page 38/118 4.2.5 Shutdown parameters This page enables v iewing and configurat ion of UPS operat ing parameters in batt ery mode and for power restoration. Click on the "Shutdo wn paramet ers" section in the men u to see the list of parameters.
Network Management Ca rd – User Manual 34003991EN/EB Page 39/118 For the main outlet ( "Master" by default) The first shutdow n criteria initiates the re start of the shutdow n sequence .
Network Management Ca rd – User Manual 34003991EN/EB Page 40/118 4.2.6 Measurements Click on " Meas urements " in the menu ◗ The next windo w shows the me asurements for a mono phases U PS. The following measurements ar e saved and time-st amped (env.
Network Management Ca rd – User Manual 34003991EN/EB Page 41/118 4.2.7 Event log ◗ Click on "Event Log ". in the menu ◗ "Save log" enables a ll saved values to be opened or saved in CSV format . (compatible with Excel ty pe spreadsheets) ◗ "Clear log" enables de letion of all records.
Network Management Ca rd – User Manual 34003991EN/EB Page 42/118 4.2.8 System log ◗ Click on "System l og". in the m enu ◗ "Save log" enables a ll saved values to be opened or saved in CSV format . (compatible with Excel ty pe spreadsheets) ◗ "Clear log" enables de letion of all records.
Network Management Ca rd – User Manual 34003991EN/EB Page 43/118 4.3 Notification 4.3.1 Email Notification The card offers the possibility of redirecting UPS alar ms to an e-mail server. The format of thes e e-mails is compatible with mobile telephone trans fer sy stems using text messages (S MS).
Network Management Ca rd – User Manual 34003991EN/EB Page 44/118 ◗ Recipient List: On the left side of t his page, up to four recipients can be configured to receive e-mails fro m the card. Each addressee has its o wn trigger event s, selected from the r ight side of the page , for which an e- mail is sent.
Network Management Ca rd – User Manual 34003991EN/EB Page 45/118 4.3.2 E-mail Message Se tti ngs This page enables c ustomisation of the content of the messages received by recipients of e-ma ils sent by the card. Customisation is c ommon to th e four recipients that can be notified (se e E-mail notificati on ).
Network Management Ca rd – User Manual 34003991EN/EB Page 46/118 The body of the e-mail sent is comp osed of: - Message text, whic h is free tex t. - The date and ti me of the event, as sav ed in the log. - URL of the card, enab ling a direct link with the card to be established.
Network Management Ca rd – User Manual 34003991EN/EB Page 47/118 4.4 Configuration The parameters of t his menu can on ly be modified af ter entering the "Log in" and "Pass word". The following screen is proposed automat ically : The default login an d password are : admin/admin Each field accepts up to 10 char acters max.
Network Management Ca rd – User Manual 34003991EN/EB Page 48/118 4.4.1 Network settings Click on "Network" in the menu. This menu enables the administ rator to configure the network paramete rs of the card and a uthorisation of the remote upgrade of the embe dded sy stem.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 49/118 If the hostname is not used, the IP addres s supplied by the DHCP server must be fixed to maintain connectio n with the clients installed on the stat ions to be prote cted.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 50/118 4.4.2 System Click on " System " in the menu. This menu enables the custo m isa tion of the information on the UPS propert ies pages. ◗ UPS Contact: Th is text field is limited to 49 characters .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 51/118 ◗ Factory Reset button: enables r estoration of the defau lt configuration of al l the card’s para m eters. TC P/IP parameters: IP addre ss, subnet mask, gat eway and BootP/DH CP value are maintained if the " Keep T CP/IP parameters" option is selected.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 52/118 4.4.3 Notified Applications Click on " Notified Appl ications " in the m enu. Security : The administrator has t o enter his/her login/pass word in order to view this informati on.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 53/118 application) or Central (co ming from the card). The Central sh utdown configuration is available by clicking on the Configuration link. ◗ Shutdown duratio n: the shutdown durat i on nece ssary to properly shutdown the co mputer.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 54/118 4.4.4 Central shutdown configuration Click on "Notified A pplications" in the menu, then "C onfiguration".
Network Management Ca rd – User M anual 3400 3991EN/EB Page 55/118 4.4.5 A cces s control Click on " Acces s Control " in th e menu. To access this page , the login and pass w ord are sy stematicall y requeste d if they have not alrea dy been enter ed.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 56/118 ◗ SSL A ccess: When selected, access to the Web interface is made in secure mo de (https). Connections with Network Shutdo w n Modules stay in standard mode (secure TCP) SSL Security I mplementation : SSL version 3.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 57/118 4.4.6 Date and time Click on " Date and Time " in the menu . This menu enables initialisation of the date and time of the card in three diffe rent way s.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 58/118 ◗ Synchronize with NT P server : Ena bles connection with a time s erver, ei ther availa ble on the company ’s internal network or on the Web. This ser ver communicates G MT time.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 59/118 4.4.7 Firmware upload Click on " Firmware Upload " in t he menu. This menu enables a ne w firmware version to be uploaded To upload a ne w version of the card's fir mware, select the file to be loaded us i ng the " Bro wse…" button and c l ick Upload.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 60/118 4.5 Environment Sensor (option ) The environment sens or (6684 6) is an option that ena bles temperature and hu midity to be meas ured, and indication of the position of t wo external cont acts.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 61/118 4.5.2 Environment Status For both measure m ents, a grad uated gauge proposes the follo wi ng funct ions: The cursor indicates the current value. Two red zones to the l eft and right represent the high and lo w thresholds that can be set on the Environment Settings page.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 62/118 4.5.3 Environment Settings The environment sens or measures temperature, hum idity and gives the status of the 2 contacts (used for door, alarms or generator unit).
Network Management Ca rd – User M anual 3400 3991EN/EB Page 63/118 The low alarm d isappears when the va lue returns above the Low threshold + Hysteres is value Input #1 and Input #2 : E nter an i dentifier correspondin g to the acquired contact (e.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 64/118 4.5.4 Log The two environ ment sensor measure ments: Temperature and Humidity are recorded at an interval defined by the Environment log interv al in the System settings pa ge. By default, this peri od is 300 seconds.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 65/118 5 Server protection 5.1 Set-up of the shutdown pa ram eters The protection appl ication : Network Shutdown Modu le or Netwat ch, on.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 66/118 Start of the shutdo wn sequence Delay before shutdown Utility fa ilure Remaining autono my 100% Shutdown after : If remaining time und er UPS Shut off Card param eters UPS parameters Shutdown duration Battery capacity 0% Shutdown if remainig capacity under t 5.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 67/118 5.1.1.3 Shutdown when backu p time is less than When the Network Management Card detec ts that the percenta ge of backup ti me remaining is less than the va lue set, the shutdown seq uence is started.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 68/118 5.1.2 Controlled outlets Certain UPS mode ls are equipped with controlled outlet s (generally 2) which are al w ay s dependant on the UPS's main outlet. Shutdown of the main outlet sys tematically cause s shutdown of the progra mmable outlets.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 69/118 5.1.3.2 Sequential startup It is possible to de lay outlet po wer-on to reduce inrus h currents on startup or to sequence the startup of several devices. Controlled outlet star tup after a given t i me is based on startup o f the main outlet.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 70/118 Shutdown duration Start shutdown main output Utility failure Utility Battery c apacity under : NSM 2 on output 1 NSM 1 on main output Main output Utility restor e Start shutdown output 1 Output 1 Shutdown duration output 1 Battery capacity under : (output 1) 5.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 71/118 5.3 Shutdown management with 2 NMC bo ards Certain UPS can have 2 NMC boa rds in order to: ◗ Increase the nu mber of protected serv ers, ◗ Protect 2 groups of serv er connect ed to different net works physically separat ed.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 72/118 6 Configuration via R S232 ◗ Use the cord supp lied with the c ard. ◗ Connect the card to a co mputer equipped with a hy perterminal ty p e emulator. The seria l link must be set at 9600 baud, 8 bits, no parity, 1 stop bit , and without flo w control.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 73/118 6.1 Choice 1: Restart / Reset Use this function to restart the c ard; two choices are possible 1 : Hardware Reset: Equivalent to a resta rt of the elect rical power supply . 2 : Restart applicat ion: Restarts only the appl icati on part.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 74/118 6.2.2 Choice 2: Modif y Netw ork settings Enables the modificat ion of network parameters For each of the fol lowing questions, y ou can press <Return> to se lect the value shown in braces, or you can ent er a new value.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 75/118 6.3 Choice 3: Lost password / Set Login Pa ssw ord to Default In the even the login or password is lost, choice 3 enab les the retu.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 76/118 6.4 Choice 4: Return to Default Configuration Enables restoratio n of the default confi guration of all the card’s parameter s --.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 77/118 7 Industrial Net w o rk Management Car d (INMC option) 7.1 Presentation 7.1.1 Overview 7.1.2 Functions The Industrial Net w ork Management Card (INMC) provides the same functions than the N M C card descri bed in t he previous section of this docume nt.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 78/118 7.1.3 Technical characteristics Functions Parameters Default values Possible values JBUS/MODBUS communication - Baud rate - Parity .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 79/118 7.2 Installation 7.2.1 RS232 link configuration and c onnection Set the SA2 switches like below: The next figure sho w s the detai .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 80/118 7.2.2 RS485 link configuration and c onnection 7.2.2.1 RS485 connection The EIA RS485 link, 2 wires or 4 wires, must be polarized at a unique point of the link and must be adapted at b oth ends for a good work ing.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 81/118 The settings of the RS485 link are made through the SA 1 swi tch es: SA1 description: 1: reserved 2: reserved 3: link termination b.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 82/118 7.2.2.2 RS485 link configura tion for 2 wires conn exion Set the SA2 switches like below to set the RS485 mode: Set the SA1 switche.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 83/118 Set the SA1 switches to select t he two wires config uration with te rmination: The next figure gives a ty pical bus structure in t.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 84/118 7.2.2.3 RS485 link configura tion for 4 wires conn exion Set the SA2 switches like below: Set the SA1 switches to select t he four .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 85/118 Set the SA1 switches to select t he four wires configura tion with te rmination: The next figure gives a ty pical bus structure in .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 86/118 7.2.3 Configuration of the JBUS/MODBUS communication parame ters ◗ Use the cord supp lied with the c ard. ◗ Connect the card to a co mputer equipped with a Hy per termi nal ty pe emu lator.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 87/118 ◗ The next menu appears : ----------- ------------------------- ------------------------- ---------------- EATON NETWORK MA N A G.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 88/118 Setting Jbus config uration : Set Slave number : 0x7 Set the Baud Rate [1 : 38400, 2: 1 9200, 3: 9600, 4: 4800 , 5: 2400, 6: 1200] .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 89/118 7.2.3.6 Choice 6: Display Jbus frames Enables the disp lay of the Jbus frames: Recv : 01 01 00 00 00 64 3d e1 Send : 01 81 02 c1 91 Recv : 01 03 00 62 00 64 e5 ff Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 90/118 7.3 Additional Web pages The INMC card Jbus parameters could be set through the next pa ge:.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 91/118 7.4 JBUS table 7.4.1 Data for Pulsar 700 / 1000 / 1500 7.4.1.1 Status table Status description Status to 0 Status to 1 Word (hex) B.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 92/118 7.4.1.2 Measurements tab le Description of the physical quant ity Word (hex) Unit I output 109 A U output 124 V U battery 12D V Out.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 93/118 7.4.2 Data for Pulsar M 2200 / 3000 7.4.2.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Load protected n.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 94/118 7.4.2.2 Measurements tab le Description of the physical quant ity Word (hex) Unit I mains 2 106 A I output 109 A U mains 2 11E V U .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 95/118 7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT 7.4.3.1 Status table Status description Status to 0 Status to 1 W.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 96/118 7.4.3.2 Measurements tab le Description of the physical quant ity Word (hex) Unit I mains 1 100 A I mains 2 106 A I output 109 A I .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 97/118 7.4.4 Data for Pulsar MX frame 15 / 20 7.4.4.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Load protecte.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 98/118 7.4.4.2 Modular fault table Description du Status Status to 0 Status to 1 Word (hex) Bit General alarm A bsent Present 61 0 Fan fai.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 99/118 Description du Status Status to 0 Status to 1 Word (hex) Bit General alarm A bsent P resent 65 0 Fan failure A bsent Present 65 1 I.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 100/118 7.4.4.3 Measurements tab le Description of the physical quant ity Word (hex) Unit I1 (I phase 1) mains 1 100 A I2 (I phase 2) main.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 101/118 Description of the physical quant ity Word (hex) Unit U mains 1 (phase 1) 150 V U mains 1 (phase 2) 151 V U mains 1 (phase 3) 152 .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 102/118 7.4.5 Sensor data 7.4.5.1 Status table Status description Status to 0 Status to 1 Word (hex) Bit Input 1 alarm no y e s 45 5 Input.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 103/118 7.4.5.2 Measurements tab le Description of the physical quant ity Word (hex) Unit Temperature measure 180 ° C / ° F Maximum temp.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 104/118 7.4.5.3 Read of the personal ization table Description Word (hex) Unit High threshold te m perature (° C) 32C 0 Low threshold tem.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 105/118 7.4.6 Other data Information descri ption Word (hex) Example Manufacturer name 1 A 0 « MGE Office Protecti on Systems » Product .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 106/118 8 Append ices 8.1 Tables of alarms and events 8.1.1 Table of alarms List of time dated alarms Alarm on A larm off Battery fuse blo.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 107/118 Inverter overload Inverte r load OK Inverter over temperature Inverter temperat ure OK Inverter short circu it Inverter OK Inverte.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 108/118 If the UPS is modular UPS, for each m odule: Battery fuse blow n B attery fuse OK No Battery Battery present Battery temperature f.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 109/118 Positive DC bus too low Positive DC bus OK Output switch (Q5N) open Output switch (Q5N) closed Normal AC NOK Normal A C OK UPS on .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 110/118 Inverter fault Inverter OK Inverter overload Inverter loa d OK Inverter overtempera ture Inverter temperat ure OK Inverter short c.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 111/118 8.1.3 Table of system alarms Network Management Ca rd startup Send test mail SUCC ESS Send test mail ERROR Send mail to <rec ip.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 112/118 8.2 SNMP objects 8.2.1 MGE MIB The NMC card imple m ent re duce MGE Office Protecti on Sy stems MIB, with the objects be llow managed. The entire MIB descr i ption is available on www.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 113/118 mgoutputFrequency _1 deciHz {7,2,1,3,1,0} mgoutputFrequency _2 deciHz {7,2,1,3,2,0} mgoutputFrequency _3 deciHz {7,2,1,3,3,0} mgou.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 114/118 If the Environment Sensor is det ected , the follo wing informatio n are managed.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 115/118 8.2.2 Table des TRAPS : (1.3.6 .1.4.1. 705.1.11) SNMP traps are sent when alar ms appears and desappears .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 116/118 - upsEnvironment Input1Open Trap 62 Level 2 - upsEnvironment Input2Open Trap 64 Level 2 - upsEnvironment Input2Closed Trap 63 Level 2 The level is used to se l ect tra ps to be sent to the supervis or.
Network Management Ca rd – User M anual 3400 3991EN/EB Page 117/118 9 Glossary Bootp: Protocol based on UDP used to a llocate an IP address corres ponding to an Ethernet card during the startup phase .
Network Management Ca rd – User M anual 3400 3991EN/EB Page 118/118 NMS NET WORK MANA GEMENT STATION (SNMP) The dedicated PC or workstation is used on the company ’s netw orks to administrate a ll devices connected t o the network. Data are transmitted using the SNMP protocol .
Een belangrijk punt na aankoop van elk apparaat Eaton Electrical 34003991EN/EB (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Eaton Electrical 34003991EN/EB heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Eaton Electrical 34003991EN/EB vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Eaton Electrical 34003991EN/EB leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Eaton Electrical 34003991EN/EB krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Eaton Electrical 34003991EN/EB bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Eaton Electrical 34003991EN/EB kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Eaton Electrical 34003991EN/EB . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.