Powerware Series Eaton 9170 + UPS 3–18 kVA User's Guide ®.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC .
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Warnings 2 .
TABLE OF CONTENTS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality ii Startup for Hardwired Units 71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 1 Chapter 1 Introduction The Eaton ® 9170 + uninterruptible power system (UPS) is a modular UPS that contains battery modules and power control modules (referred to as power modules).
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 3 Consignes de Sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS Ce ma.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 4 Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y el mantenimiento del SIE y de las baterías.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 5 Physical Features The Eaton 9170+ UPS is available in four cabinet sizes. Figure 1 through Figure 6 show the 3-slot and 9-slot configurations and identify basic Eaton 9170+ system features.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 6 Front Panel Display Front Cover Cabinet Base Figure 3.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 7 Communication Slots Power Outlets (optional) Input Power Cable (optional) DB-9 Communication Port Wiring Access Figure 4. Nine-Slot Cabinet (Rear View) Handle/Latch Release Insertion/Extraction Cams Handle Thumbscrew Figure 5.
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 8.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 9 Chapter 2 Installation Setup This chapter explains how to set up and install the Eaton 9170+ cabinets: S .
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 10 Location Requirements Install the Eaton 9170+ UPS as close as possible to the equipment or the load distribution panel it will protect. If this distance is more than 7.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 11 5. If installing the 3- or 6-slot cabinet in a rack, see ”Rack-Mount Installation (Three- and Six-Slot Cabinets)” on page 14 to install the cabinet in the rack.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 12 5. If installing the 9- or 12-slot cabinet in a rack, follow the installation instructions with the 9- and 12-slot rack-mount kit.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 13 To install the caster cart: 1. Place the caster cart (shipped separately from the UPS cabinet) under the cabinet before installing power and battery modules and before making connections to the intended power source.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 14 4. Turn all four caster bolts counter-clockwise until the cabinet rests on the floor.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 15 3. Carefully replace the UPS cabinet top cover and secure with the four screws removed in Step 1. Position the cover lip to fit behind the front panel display.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 16 6. Select the position for the UPS in the equipment rack. 7. Select the proper holes in the rail that position the UPS at the desired location in the rack.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 17 B A Floor Anchor Bracket Figure 11. Floor Anchor Brackets Bolted to UPS Cabinet Moving the Cabinets C A U T I O N Do NOT attempt to raise the cabinet with the power or battery modules installed.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 18 4. Pry the caps out of the bolt access holes. 5. Use a 1/2 ” hex-style socket wrench to turn each of the four bolts clockwise. Doing so lowers the casters to allow the cabinet to roll on the casters.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 19 Chapter 3 UPS with Bypass Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on page 67.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 20 External Bypass Switch Off Service Line Off Service Line UPS UPS Off Service Line UPS User-Supplied (if required) External Batteries (optional) Building Service Panel Load Distribution Panel Figure 12.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 21 Input Current Ratings Table 1 contains the required circuit breaker ratings for hardwired installations.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 22 See Table 2 for recommended conductor sizes to wire the input circuit breakers. Table 2. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque 25A 5.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 23 NOTE In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS. Table 3.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 24 After turning the load position handle to the UPS position and releasing the red button, the Eaton 9170+ UPS remains in Bypass mode.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 25 Table 4. Bypass Switch Specifications Bypass Switch Models Ratin.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 26 UPS Installation with an External Bypass Switch W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electrical installation.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 27 Entrance Panel Battery Cable Wiring Access Hole for Optional EPO and Bypass Input Signals Wiring Access Hole for an Optional Generator Input Signal Figure 14.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 28 6. Install the conduit adapters.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 29 7. Find the terminal strip inside the bypass switch cabinet.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 30 9. Wire the UPS for the proper input voltage as shown in Figure 17.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 31 Figure 18 and Figure 19 describe output wiring configurations for various output voltages. You must also set the operating menu 4 2 4 for the required output voltage as shown in the wiring configuration drawings.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 32 13. If the bypass switch is an MBB style, notice the cable routed out of the left side of the bypass switch cabinet.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 33 14. If any external hardwired control signals are required (EPO or Generator On), connect the wiring as shown in Figure 21.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 34 System Wiring Diagrams Select wiring diagrams from Table 5 based upon the installation voltage.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 35 The following notes are referenced in the system wiring diagrams (Figure 22 through Figure 24). NOTE 1 The customer must provide input overcurrent protection.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 36 S 110/220 Input, 110/220 Output S 120/208 Input, 120/208 Output S 120/240 Input, 120/240 Output S 100/200 Input, 100/200 Output S 127/220 Input, 127/220 Output 3 2 3 2 3 3 7 4 5 7 6 1 Figure 22.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 37 2 S 200 Input, 200 Output S 208 Input, 208 Output S 220 Input, 220 Output S 230 Input, 230 Output S 240 Input, 240 Output 1 3 2 3 3 3 7 4 5 7 6 Figure 23.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 38 S 220 Input, 220 Output S 230 Input, 230 Output S 240 Input, 240 Output 2 1 3 2 3 3 3 7 4 5 7 6 Figure 24.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 39 Chapter 4 UPS Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on page 67.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 40 Input Current Ratings Table 6 contains the required circuit breaker ratings for hardwired installations. Circuit breaker ratings for units having an input line cord are determined by the current capacity of the line cord.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 41 See Table 7 for recommended conductor sizes to wire the input circuit breakers. Table 7. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque 25A 5.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 42 UPS Electrical Installation W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electrical installation.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 43 Entrance Panel Battery Cable Wiring Access Hole for Optional EPO Wiring Access Hole for an Optional Generator Input Signal Figure 26.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 44 3. Install the conduit adapters. AC input and AC output conductors must be run through separate conduits. UPS output circuits must be installed in dedicated conduit systems and not shared with other electrical circuits.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 45 5. Wire the UPS for the proper input voltage as shown in Figure 28.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 46 Figure 29 and Figure 30 describe output wiring configurations for various output voltages. You must also set the operating menu 4 2 4 for the required output voltage as shown in the wiring configuration drawings.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 47 8. If any external hardwired control signals are required (EPO or Generator On), unscrew and remove the top rear cover of the cabinet and locate the terminal block (see Figure 31).
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 48 System Wiring Diagrams Select wiring diagrams from Table 8 based upon the installation voltage.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 49 The following notes are referenced in the system wiring diagrams (Figure 32 through Figure 34). NOTE 1 The customer must provide input overcurrent protection.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 50 3 S 110/220 Input, 110/220 Output S 120/208 Input, 120/208 Output S 120/240 Input, 120/240 Output S 100/200 Input, 100/200 Output S 127/220 Input, 127/220 Output 2 2 4 6 6 5 1 Figure 32.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 51 S 200 Input, 200 Output S 208 Input, 208 Output S 220 Input, 220 Output S 230 Input, 230 Output S 240 Input, 240 Output 1 2 2 4 6 6 5 Figure 33.
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 52 S 220 Input, 220 Output S 230 Input, 230 Output S 240 Input, 240 Output 1 2 2 4 6 6 5 Figure 34. No External Bypass (L1, N), Universal Power Modules NOTE To use Figure 34, refer to the list of Notes on page 49 .
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 53 Chapter 5 Isolated Output Wiring Diagrams NOTE This chapter is only for units manufactured before 2009.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 54 100, 110, 115, or 120 X2 50 or 60 Hz 100/200, 110/220, 115/230, or 120/240V Out with Isolated Output Option Menu 4 2 4 set to 200, 220, 230, or 240, as required.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 55 Ground terminations, inside the UPS rear cover, are located directly below the line input terminals. Figure 15 on page 28 shows input and output wiring terminals inside the Eaton 9170+ UPS cabinet.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 56 System Wiring Diagrams The following notes are referenced in the isolated system wiring diagrams (Figure 38 through Figure 41).
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 57 S 100/200 Input, 100/200 Output S 120/208 Input, 120/240 Output (BBM bypass required) S 110/220 Input, 110/220 Output S 115/230 Input, 115/230 Output S 120/240 Input, 120/240 Output 1 4 2 4 2 3 4 4 9 5 7 9 6 8 Figure 38.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 58 S 100/200 Input, 100/200 Output S 120/208 Input, 120/240 Output S 110/220 Input, 110/220 Output S 115/230 Input, 115/230 Output S 120/240 Input, 120/240 Output 1 4 3 4 7 9 9 6 8 Figure 39.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 59 (Voltages require the bypass switch to be BBM; contact your service representative for details.) S 120/208 Input, 120/208 Output S 127/220 Input, 127/220 Output 1 4 2 4 2 3 4 4 9 5 7 9 6 8 10 Figure 40.
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 60 S 120/208 Input, 120/208 Output S 127/220 Input, 127/220 Output 1 4 3 4 7 9 8 9 6 10 Figure 41.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 61 Chapter 6 Battery Cabinet Installation If you are not installing battery modules into a separate external battery cabinet, continue to “UPS Startup” on page 67.
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 62 Entrance Panel Battery Cable Figure 42. UPS Power Entrance Panel 3. Use a pair of pliers to bend the narrow links (1 and 2 in Figure 43) between the outer edge of the lower breakaway panel and the rear panel.
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 63 Cable Assembly Backplane Ring Terminal Compression Lug Bus-Bar Extension Assembly Figure 44. Bus-Bar Extension Installation 6.
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 64 Cable Assembly Figure 45. Battery Cable Assembly Installation 12. Align the screw holes of the cable assembly's entry plate with holes on the cabinet side cover as shown in Figure 45.
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 65 ‒ + Figure 46. Battery Cable Installed in Battery Cabinet 17. Secure the + , the ‒ , and the conductors to the proper compression lugs on the battery cabinet backplane as shown in Figure 46.
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 66 To UPS or Previous Battery Cabinet To Next Battery Cabinet Figure 47. Connecting Additional Battery Cabinets 20. Reinstall the remaining rear covers using the original screws.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 67 Chapter 7 UPS Startup This section provides step-by-step instructions for starting your Eaton 9170+ system.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 68 NOTE All power modules in the Eaton 9170+ UPS cabinet must be of the same type: Split-phase power modules have brown labels; universal (single-phase) power modules have black labels.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 69 Startup for Plug-Receptacle Units To start a plug-receptacle unit: 1. Plug the power cable of the unit into an approved, functional power outlet.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 70 6. If applicable, test proper operation of optional external control signals and computer communication before connecting the load. (See “DB-9 Communication Port” on page 92 for details.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 71 Startup for Hardwired Units To start a hardwired unit: 1. Confirm that an electrician has completed and tested the connection to the proper power source.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 72 8. If external battery cabinets are installed, close the DC disconnect switch button on the back of each external battery cabinet. Insert the switch key supplied with the cabinet into the button and turn clockwise 1/2-turn.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 73 11. If the bypass switch is a Break-Before-Make type, skip this step and proceed to Step 12. If the bypass switch is a Make-Before-Break type, verify that the AC voltages from the UPS and the AC line input are in phase.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 74 18. The UPS front panel display automatically turns on whenever input power is present and at least one power module is installed.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 75 2. Select the desired language for the display. Use the Y and B buttons to scroll between English, French, German, and Spanish. Enter your selection by pressing the button.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 76 6. The system signals an alarm when the required output cannot be maintained with the loss of redundant power modules. The alarm is essentially disabled with a redundancy level set at 0.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 77 Chapter 8 Operation The Eaton 9170+ UPS operates in several different modes. Normally it operates under internal control (Auto mode) to automatically protect loads connected to it.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 78 Off mode turns off the output and most internal circuitry. Within this mode, Sleep mode turns off all internal circuitry when AC line is not present and battery voltage drops to a low threshold.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 79 Turning the UPS On The unit has no physical On/Off switch. Access the UPS On/Off function through the front panel display. If the UPS is off, press the ON button through the front panel display to turn the UPS on again.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 80 Front Panel Display The front panel has an alphanumeric display, three LED indicators, and six pushbuttons as described in Figure 54 and in Table 10.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 81 Using the Front Panel Display Figure 55 shows an example of the front panel display. The numbers in the upper left corner (1 2 9 in Figure 55) indicate the menu level.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 82 During normal operation, the display appears as shown in Figure 56: Md: Current UPS operating .
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 83 Parameters The parameters describe the UPS operation. Some useful parameters are input and output voltage, input and output current, and battery voltage, among others.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 84 Reading the Eaton 9170+ System Logs The Eaton 9170+ system makes an entry in its logs each time it sounds an alarm or runs on battery power. This information can help in diagnosing power problems.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 85 Alarm Log The alarm log is in menu 2 2. Move through the menu structure by pressing the Menu button and pressing the B button to move down to menu 2.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 86 Table 12 lists the alarm log messages. Table 12. Alarm Log Messages Message Explanation Open Cell Battery failure caused by open cell. Weak Battery Battery failure caused by load test.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 87 Menu Map Figure 60 shows all the Eaton 9170+ system parameters. The menu structure has six primary-level menus, System Status Menu (1) through Service Menu (6).
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 88 (ESC) (Menu) (Top) (ESC) (ESC) 3 1 2 1 Battery Results 3 1 2 2 Runtime at EOT 3 1 2 3 DC.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 89 Chapter 9 Communication Eaton offers several methods of communicating with your Eaton 9170+ system in ad.
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 90 ConnectUPS t Web/SNMP Card (BD Model) The ConnectUPS-BD Web/SNMP Card provides the Eaton 9170+ system with its own ethernet network connection, allowing it to be remotely monitored and controlled via industry-standard Internet browsers.
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 91 On-Generator: An external signal can indicate that the input power is being supplied by a generator.
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 92 DB-9 Communication Port Table 13 explains the functions of the pins on the Eaton 9170+ DB-9 communication port. This port is on the Eaton 9170+ UPS rear panel, as shown in Figure 49 on page 69.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 93 Chapter 10 Maintenance Routine Maintenance NOTE Observe important safety precautions while performing these checks. NOTE Eaton recommends that you schedule preventive maintenance checks at least every six months.
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 94 Storage Temperature Store the Eaton 9170+ battery modules (in the UPS or external battery cabinet) at –20 to +40 ° C (–4 to +104 ° F). Batteries will have a longer shelf life if they are kept below +25 ° C (+77 ° F).
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 95 3. Pull the module out approximately 17 cm (7 ” ) to the secondary stop on top of the module.
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 96 3. Use two hands to support the module. When fully extended, lower the front down slightly and lift the rear edge over the safety stop on the center support rail.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 97 Chapter 11 Specifications This section provides the following specifications for the Eaton 9170+ models: S Electrical input and output S Model specifications S Environmental and safety S Battery S Weights and dimensions Table 14.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 98 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) Three-Slot Cabine.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 99 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 100 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 101 Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674).
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 102 Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 103 Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 104 Table 18. Environmental and Safety Operating Temperature 0 ° C to 40 ° C (32 ° F to 1.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 105 Table 20. Weights and Dimensions Cabinet Size Height Width Depth Weight* 3-slot 45 cm (17.75 ” ) 43 cm (17.0 ” ) 65 cm (25.5 ” ) 30 kg (66 lb) 3-slot (with caster cart) 49.
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 106.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 107 Chapter 12 Troubleshooting The following table provides answers to commonly asked questions. Table 21. Frequently Asked Questions Question: “How do I...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 108 Answer Question: “How do I... ” Check the condition of the batteries? The results of the most recent battery test are stored at menu 3 1 2 1.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 109 Alarms Figure 61 shows a typical alarm display.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 110 When an alarm occurs, follow these steps: 1. Observe the display to see which alarm is active. NOTE To find out if more than one alarm is active, press .
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 111 What to Do What It Means Alarm Message P EPO The Emergency Power-off function has been activated. Deactivate the external EPO switch and restart the UPS by pressing the ON button through the front panel display.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 112 Table 23 contains descriptions of non-critical alarm messages. Non-critical alarms are not as urgent as critical alarms, but should be attended to as soon as convenient to avoid the problem becoming critical.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 113 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Eaton Customer Support Center at one of the following telephone numbers.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 114.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 115 Chapter 13 Warranty Two-Year Limited Warranty (US and Canada) Eaton UPS Models: 9155, 9170+ and FERRUPS ® 4.
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 116 In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for return of defective equipment and replacement of Warranted Items.
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 117 OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any).
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 118 WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User's equipment does not include reimbursement for or restoration of any data loss.
Een belangrijk punt na aankoop van elk apparaat Eaton Electrical ASY0567 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Eaton Electrical ASY0567 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Eaton Electrical ASY0567 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Eaton Electrical ASY0567 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Eaton Electrical ASY0567 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Eaton Electrical ASY0567 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Eaton Electrical ASY0567 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Eaton Electrical ASY0567 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.