Gebruiksaanwijzing /service van het product Model 1700 van de fabrikant Emerson
Ga naar pagina of 350
Configuration and Use Manual MMI-20021712, Rev A B April 201 3 Micro Motion ® Model 1700 Transmitters with Analog Outputs Includes the Chinese-Language Display Option.
Safety messages Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step. Micro Motion customer service Email • Worldwide: flow.support@emerson.com • Asia-Pacific: APflow.
Contents Part I Getting Started Chapter 1 Before you begin ............................................................................................................ 2 1.1 About this manual ...........................................................
6.4 Configure the discrete output ................................................................................................... 93 6.5 Configure events .............................................................................................
10.22 Check Frequency Output Fault Action ............................................................................................. 206 10.23 Check Flow Direction ....................................................................................
Contents iv Micro Motion ® Model 1700 Transmitters with Analog Outputs.
Part I Getting Started Chapters covered in this part: • Before you begin • Quick start Getting Started Configuration and Use Manual 1.
1 Before you begin Topics covered in this chapter: • About this manual • Transmitter model code • Communications tools and protocols • Additional documentation and resources 1.1 About this manual This manual provides information to help you configure, commission, use, maintain, and troubleshoot the Micro Motion transmitter.
Communications tools, protocols, and related information Table 1-1: Communica- tions tool Supported protocols Scope In this manual For more information Display (stand- ard) Not applicable Basic configuration and commissioning Complete user informa- tion.
Additional documentation and resources Table 1-2: Topic Document Sensor Sensor documentation Transmitter installation Hazardous area installation See the approval documentation shipped with the transmitter, or download the appropriate documentation from the Micro Motion web site at www.
2 Quick start Topics covered in this chapter: • Power up the transmitter • Check flowmeter status • Make a startup connection to the transmitter • Characterize the flowmeter (if required) • Verify mass flow measurement • Verify the zero 2.
1. Wait approximately 10 seconds for the power-up sequence to complete. Immediately after power-up, the transmitter runs through diagnostic routines and checks for error conditions. During the power-up sequence, Alarm A009 is active. This alarm should clear automatically when the power-up sequence is complete.
2.3 Make a startup connection to the transmitter For all configuration tools except the display, you must have an active connection to the transmitter to configure the transmitter. Follow this procedure to make your first connection to the transmitter.
2.4 Characterize the flowmeter (if required) Display (standard) Not available Chinese-language display Offline Maintain > Configuration > Calibrate Sensor ProLink II • ProLink > Configurati.
2.4.1 Sample sensor tags Tag on older curved-tube sensors (all sensors except T-Series) Figure 2-1: Tag on newer curved-tube sensors (all sensors except T-Series) Figure 2-2: Quick start Configuration.
Tag on older straight-tube sensor (T-Series) Figure 2-3: Tag on newer straight-tube sensor (T-Series) Figure 2-4: 2.4.2 Flow calibration parameters ( FCF , FT ) Two separate values are used to describe flow calibration: a 6-character FCF value and a 4- character FT value.
Example: Concatenating FCF and FT FCF = x.xxxx FT = y.yy Flow calibration parameter: x.xxxxy.yy Example: Splitting the concatenated Flowcal or FCF value Flow calibration parameter: x.
• Connect to the transmitter with the Field Communicator and read the value for Mass Flow Rate in the Process Variables menu ( On-Line Menu > Overview > Primary Purpose Variables ). Postrequisites If the reported mass flow rate is not accurate: • Check the characterization parameters.
b. Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature. c. Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if available.
b. Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature. c. Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if available.
Terminology used with zero verification and zero calibration (continued) Table 2-2: Term Definition Zero Time The time period over which the Zero Calibration procedure is performed. Unit = seconds. Field Verification Zero A 3-minute running average of the Live Zero value, calculated by the transmitter.
Part II Configuration and commissioning Chapters covered in this part: • Introduction to configuration and commissioning • Configure process measurement • Configure device options and preference.
3 Introduction to configuration and commissioning Topics covered in this chapter: • Configuration flowchart • Default values and ranges • Enable access to the off-line menu of the display • Disable write-protection on the transmitter configuration • Restore the factory configuration 3.
Configuration flowchart Figure 3-1: Integrate device with control system Configure device options and preferences Configure process measurement Configure mass flow measurement Configure volume flow me.
3.2 Default values and ranges See Section F.1 to view the default values and ranges for the most commonly used parameters. 3.3 Enable access to the off-line menu of the display Display (standard) OFF-.
Tip Write-protecting the transmitter prevents accidental changes to configuration. It does not prevent normal operational use. You can always disable write-protection, perform any required configuration changes, then re-enable write-protection.
4 Configure process measurement Topics covered in this chapter: • Configure mass flow measurement • Configure volume flow measurement for liquid applications • Configure gas standard volume (GSV.
Tip If the measurement unit you want to use is not available, you can define a special measurement unit. Options for Mass Flow Measurement Unit The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit , plus one user-defined special measurement unit.
Define a special measurement unit for mass flow Display (standard) Not available Chinese-language display Offline Maintain > Configuration > Units > Special Mass Flow ProLink II ProLink > .
3. Calculate Mass Flow Conversion Factor : a. 1 lb/sec = 16 oz/sec b. Mass Flow Conversion Factor = 1/16 = 0.0625 4. Set Mass Flow Conversion Factor to 0.
• Whenever the damping value is non-zero, the reported measurement will lag the actual measurement because the reported value is being averaged over time. • In general, lower damping values are preferable because there is less chance of data loss, and less lag time between the actual measurement and the reported value.
Overview Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All mass flow rates below this cutoff will be reported as 0. Procedure Set Mass Flow Cutoff to the value you want to use. The default value for Mass Flow Cutoff is 0.
• If the mass flow rate drops below 15 g/sec but not below 10 g/sec: - The mA output will report zero flow. - The frequency output will report the actual flow rate, and the actual flow rate will be used in all internal processing.
4.2.2 Configure Volume Flow Measurement Unit for liquid applications Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > UNITS > VOL Chinese-language display Offline Maintain > Configurat.
Options for Volume Flow Measurement Unit for liquid applications (continued) Table 4-3: Unit description Label Display (stand- ard) Chinese-lan- guage display ProLink II ProLink III Field Commu- nicat.
Define a special measurement unit for volume flow Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Special Units ProLink III Device To.
3. Calculate the conversion factor: a. 1 gal/sec = 8 pints/sec b. Volume Flow Conversion Factor = 1/8 = 0.1250 4. Set Volume Flow Conversion Factor to 0.
• AO Cutoff : 10 l/sec • Volume Flow Cutoff : 15 l/sec Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and 0 will be used in all internal processing.
4.3.1 Configure Volume Flow Type for gas applications Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Flow > Vol Flow Type ProLink.
4.3.3 Configure Gas Standard Volume Flow Measurement Unit Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > UNITS > GSV Chinese-language display Offline Maintain > Configuration > Un.
Options for Gas Standard Volume Measurement Unit (continued) Table 4-4: Unit description Label Display (stand- ard) Chinese-lan- guage display ProLink II ProLink III Field Commu- nicator Normal cubic .
Define a special measurement unit for gas standard volume flow Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Special Units ProLink .
Example: Defining a special measurement unit for gas standard volume flow You want to measure gas standard volume flow in thousands of standard cubic feet per minute. 1. Set Base Gas Standard Volume Unit to SCFM . 2. Set Base Time Unit to minutes (min).
Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values reported via outputs and the gas standard volume flow values used in other transmitter behavior (e.g., events defined on gas standard volume flow). AO Cutoff affects only flow values reported via the mA output.
Overview Flow Direction controls how forward flow and reverse flow affect flow measurement and reporting. Flow Direction is defined with respect to the flow arrow on the sensor: • Forward flow (positive flow) moves in the direction of the flow arrow on the sensor.
Effect of Flow Direction on mA outputs Flow Direction affects how the transmitter reports flow values via the mA outputs. The mA outputs are affected by Flow Direction only if mA Output Process Variable is set to a flow variable.
Effect of Flow Direction on the mA output: Lower Range Value < 0 Figure 4-2: Flow Direction = Forward mA output -x 0 x Reverse flow Forward flow 20 12 4 Flow Direction = Reverse, Negate Forward mA .
• Under conditions of forward flow, if (the absolute value of) the flow rate equals or exceeds 100 g/sec, the mA output is proportional to the flow rate up to 20.
Effect of Flow Direction on discrete outputs The Flow Direction parameter affects the discrete output behavior only if Discrete Output Source is set to Flow Direction .
Effect of the Flow Direction parameter and actual flow direction on flow totals and inventories Table 4-9: Flow Direction setting Actual flow direction Forward Zero flow Reverse Forward Totals increas.
The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter). Options for Density Measurement Unit The transmitter provides a standard set of measurement units for Density Measurement Unit . Different communications tools may use different labels.
Overview The slug flow parameters control how the transmitter detects and reports two-phase flow (gas in a liquid process or liquid in a gas process). Procedure 1. Set Slug Low Limit to the lowest density value that is considered normal in your process.
Tip To decrease the occurrence of slug flow alarms, lower Slug Low Limit or raise Slug High Limit . A slug flow condition occurs whenever the measured density goes below Slug Low Limit or above Slug High Limit . If this occurs: • A slug flow alarm is posted to the active alarm log.
Core processor type Update Rate setting Density Damping range Enhanced Not applicable 0 to 40.96 seconds Tips • A high damping value makes the process variable appear smoother because the reported value changes slowly. • A low damping value makes the process variable appear more erratic because the reported value changes more quickly.
4.5.4 Configure Density Cutoff Display (standard) Not available Chinese-language display Offline Maintain > Configuration > Low Flow Cutoff > Density Cutoff ProLink II ProLink > Configurat.
4.6.1 Configure Temperature Measurement Unit Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > UNITS > TEMP Chinese-language display Offline Maintain > Configuration > Units > Tem.
4.6.2 Configure Temperature Damping Display (standard) Not available Chinese-language display Offline Maintain > Configuration > Damping > Temperature Damping ProLink II ProLink > Configur.
4.7 Configure pressure compensation Pressure compensation adjusts process measurement to compensate for the pressure effect on the sensor. The pressure effect is the change in the sensor’s sensitivity to flow and density caused by the difference between the calibration pressure and the process pressure.
6. Determine how the transmitter will obtain pressure data, and perform the required setup. Option Setup A user-configured static pressure val- ue a. Set Pressure Units to the desired unit. b. Set External Pressure to the desired value. Polling for pres- sure (4) a.
The calibration pressure is the pressure at which your sensor was calibrated, and defines the pressure at which there is no pressure effect. If the data is unavailable, enter 20 PSI. 4. Enter Flow Factor for your sensor. The flow factor is the percent change in the flow rate per PSI.
b. Set Static or Current Pressure to the value to use, and click Apply 9. If you want to use digital communications, click Apply , then perform the necessary host programming and communications setup to write pressure data to the transmitter at appropriate intervals.
Option Setup A user-configured static pressure val- ue a. Set Pressure Unit to the desired unit. b. Set Compensation Pressure to the desired value. Polling for pres- sure (6) a. Ensure that the primary mA output has been wired to support HART polling.
Options for Pressure Measurement Unit (continued) Table 4-13: Unit description Label Display (stand- ard) Chinese-lan- guage display ProLink II ProLink III Field Commu- nicator Millimeters water @ 4 .
5 Configure device options and preferences Topics covered in this chapter: • Configure the transmitter display • Enable or disable operator actions from the display • Configure security for the display menus • Configure response time parameters • Configure alarm handling • Configure informational parameters 5.
Procedure Select the language you want to use. Tip For devices with the Chinese-language display, you can use a shortcut key, or an optical switch combination, to change the language without having to access the display menu. The optical switch combination is shown on the front of the display.
Example: Default display variable configuration Display variable Process variable assignment Display Variable 1 Mass flow Display Variable 2 Mass total Display Variable 3 Volume flow Display Variable .
Display Variable 1 will automatically be set to match mA Output Process Variable for the primary mA output. If you change the configuration of mA Output Process Variable , Display Variable 1 will be updated automatically.
Overview You can set Update Period to control how frequently data is refreshed on the display. Procedure Set Update Period to the desired value. The default value is 200 milliseconds. The range is 100 milliseconds to 10,000 milliseconds (10 seconds). 5.
5.1.6 Enable or disable the display backlight Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > BKLT Chinese-language display Offline Maintain > Configuration > Display >.
5.2 Enable or disable operator actions from the display You can configure the transmitter to let the operator perform specific actions using the display. You can configure the following: • Totalizer Start/Stop • Totalizer Reset • Acknowledge All Alarms 5.
Option Description Disabled (default) Operators cannot start and stop totalizers and inventories from the dis- play. 5.2.2 Enable or disable Totalizer Reset from the display Display (standard) OFF-LIN.
5.2.3 Enable or disable the Acknowledge All Alarms display command Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > ALARM Chinese-language display Offline Maintain > Configur.
Overview You can control operator access to different sections of the display off-line menu. You can also configure a password to control access. Procedure 1. To control operator access to the maintenance section of the off-line menu, enable or disable Off-Line Menu .
If both Off-Line Password and Alarm Password are enabled, the operator is prompted for the off-line password to access the off-line menu, but is not prompted thereafter. 5. (Optional) Set Off-Line Password to the desired value. The same value is used for both the off-line password and the alarm password.
• Contact Micro Motion. Procedure 1. Set Update Rate as desired. Option Description Normal All process data is polled at the rate of 20 times per second (20 Hz). All process variables are calculated at 20 Hz. This option is appropriate for most applications.
Special mode and process variable updates Table 5-1: Always polled and updated Updated only when the petroleum measurement application is disa- bled Never updated • Mass flow • Volume flow • Gas.
Option Description Normal Transmitter calculates process variables at the standard speed. Special Transmitter calculates process variables at a faster speed. 5.5 Configure alarm handling The alarm handling parameters control the transmitter’s response to process and device conditions.
If the fault timeout period expires while the alarm is still active, the fault actions are performed. If the alarm condition clears before the fault timeout expires, no fault actions are performed. Tip ProLink II allows you to set Fault Timeout in two locations.
Option Description Fault Actions when fault is detected: • The alarm is posted to the Alert List. • Outputs go to the configured fault action (after Fault Timeout has expired, if applicable). • Digital communications go to the configured fault action (after Fault Timeout has expired, if applicable).
Status alarms and Status Alarm Severity (continued) Table 5-2: Alarm code Status message Default severity Notes Configurable? A014 Transmitter Failure Fault No A016 Sensor RTD Failure Fault Yes A017 T.
Status alarms and Status Alarm Severity (continued) Table 5-2: Alarm code Status message Default severity Notes Configurable? A103 Data Loss Possible (Totals and Inventories) Informational Applies only to flowmeters with the standard core processor. Can be set to either Informational or Ignore , but cannot be set to Fault .
5.6 Configure informational parameters The informational parameters can be used to identify or describe your flowmeter but they are not used in transmitter processing and are not required.
5.6.2 Configure Message Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Device > Message ProLink III Device Tools > Configurati.
5.6.4 Configure Sensor Serial Number Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Sensor > Sensor S/N ProLink III Device Tools .
5.6.6 Configure Sensor Liner Material Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Sensor > Liner Matl ProLink III Device Tools.
6 Integrate the meter with the control system Topics covered in this chapter: • Configure the transmitter channels • Configure the mA output • Configure the frequency output • Configure the discrete output • Configure events • Configure digital communications 6.
Postrequisites For each channel that you configured, perform or verify the corresponding input or output configuration. When the configuration of a channel is changed, the channel’s behavior will be.
• If you are using the HART variables, be aware that changing the configuration of mA Output Process Variable will change the configuration of the HART Primary Variable (PV) and the HART Tertiary Variable (TV).
Overview The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA output, that is, to define the relationship between mA Output Process Variable and the mA output level.
Default values for Lower Range Value (LRV) and Upper Range Value (URV) Table 6-2: Process variable LRV URV All mass flow variables –200.000 g/sec 200.000 g/sec All liquid volume flow variables –0.200 l/sec 0.200 l/sec Gas standard volume flow –423.
Example: Cutoff interaction Configuration: • mA Output Process Variable = Mass Flow Rate • Frequency Output Process Variable = Mass Flow Rate • AO Cutoff = 10 g/sec • Mass Flow Cutoff = 15 g/sec Result: If the mass flow rate drops below 15 g/sec, all outputs representing mass flow will report zero flow.
Note Added Damping is not applied if the mA output is fixed (for example, during loop testing) or if the mA output is reporting a fault. Added Damping is applied while sensor simulation is active. Procedure Set Added Damping to the desired value. The default value is 0.
6.2.5 Configure mA Output Fault Action and mA Output Fault Level Display (standard) Not available Chinese-language display Not available ProLink II • ProLink > Configuration > Analog Output &g.
CAUTION! If you set mA Output Fault Action or Frequency Output Fault Action to None , be sure to set Digital Communications Fault Action to None . If you do not, the output will not report actual process data, and this may result in measurement errors or unintended consequences for your process.
Overview Frequency Output Polarity controls how the output indicates the ON (active) state. The default value, Active High , is appropriate for most applications. Active Low may be required by applications that use low-frequency signals. Procedure Set Frequency Output Polarity as desired.
Option Description Pulses/Unit A user-specified number of pulses represents one flow unit Units/Pulse A pulse represents a user-specified number of flow units 2. Set additional required parameters. • If you set Frequency Output Scaling Method to Frequency=Flow , set Rate Factor and Frequency Factor .
FrequencyFactor = x 10 2000 60 333.33 FrequencyFactor = FrequencyFactor = x N RateFactor T Set parameters as follows: • Rate Factor : 2000 • Frequency Factor : 333.
The default value is 277 milliseconds. You can set Frequency Output Maximum Pulse Width to 0 milliseconds or to a value between 0.5 milliseconds and 277.5 milliseconds. The transmitter automatically adjusts the value to the nearest valid value. Tip Micro Motion recommends leaving Frequency Output Maximum Pulse Width at the default value.
Options for Frequency Output Fault Action Options for Frequency Output Fault Action Table 6-7: Label Frequency output behavior Upscale Goes to configured Upscale value: • Range: 10 Hz to 15000 Hz .
6.4.1 Configure Discrete Output Source Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > DO SRC Chinese-language display Offline Maintain > Configuration >.
Options for Discrete Output Source (continued) Table 6-8: Option Label Condition Discrete output volt- age Display (standard) Chinese-lan- guage dis- play ProLink II ProLink III Field Com- municator F.
3. Set Flow Switch Setpoint to the value at which the flow switch will be triggered (after Hysteresis is applied). • If the flow rate is below this value, the discrete output is ON. • If the flow rate is above this value, the discrete output is OFF.
Options for Discrete Output Polarity Options for Discrete Output Polarity Table 6-9: Polarity Description Active High • When asserted (condition tied to DO is true), the circuit provides a pull-up to 24 V. • When not asserted (condition tied to DO is false), the circuit provides 0 V.
6.4.3 Configure Discrete Output Fault Action Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Frequency/Discrete Output > Discrete .
Options for Discrete Output Fault Action (continued) Table 6-10: Label Discrete output behavior Polarity= Active High Polarity= Active Low None (default) Discrete output is controlled by its assignmen.
Procedure 1. Select the event that you want to configure. 2. Specify Event Type . Options Description HI x > A The event occurs when the value of the assigned process variable ( x ) is greater than the setpoint ( Setpoint A ), endpoint not included.
Options Description HI x > A The event occurs when the value of the assigned process variable ( x ) is greater than the setpoint ( Setpoint A ), endpoint not included. LO x < A The event occurs when the value of the assigned process variable ( x ) is less than the setpoint ( Setpoint A ), endpoint not included.
Options for Enhanced Event Action (continued) Table 6-11: Action Label Display (stand- ard) Chinese-lan- guage display ProLink II ProLink III Field Communi- cator Reset mass total RESET MASS Reset Mas.
Overview HART/Bell 202 communications parameters support HART communication with the transmitter's primary mA terminals over a HART/Bell 202 network.
Configure burst parameters Display (standard) Not available Chinese-language display Not available ProLink II ProLink > Configuration > Device > Burst Setup ProLink III Device Tools > Conf.
Label Description ProLink II ProLink III Field Communi- cator Transmitter vars Transmitter varia- bles Fld dev var The transmitter sends four user- specified process variables in each burst. 3. Ensure that the burst output variables are set appropriately.
Options for HART variables (continued) Table 6-12: Process variable Primary Varia- ble (PV) Secondary Variable (SV) Third Variable (TV) Fourth Varia- ble (QV ) Mass inventory ✓ Line (Gross) Volume i.
Overview HART/RS-485 communications parameters support HART communication with the transmitter's RS-485 terminals. HART/RS-485 communication parameters include: • Protocol • HART Address (Polling Address) • Parity , Stop Bits , and Baud Rate Restriction Devices with the Chinese-language display do not support HART/RS-485 communications.
Overview Modbus/RS-485 communications parameters control Modbus communication with the transmitter's RS-485 terminals. Modbus/RS-485 communications parameters include: • Disable Modbus ASCII .
Code Byte order 3 4–3 2–1 See Table 6-14 for the bit structure of bytes 1, 2, 3, and 4. Bit structure of floating-point bytes Table 6-14: Byte Bits Definition 1 SEEEEEEE S=Sign E=Exponent 2 EMMMMMMM E=Exponent M=Mantissa 3 MMMMMMMM M=Mantissa 4 MMMMMMMM M=Mantissa 6.
Procedure Set Digital Communications Fault Action as desired. The default setting is None . Options for Digital Communications Fault Action Options for Digital Communications Fault Action Table 6-15: .
Restriction If you set Digital Communications Fault Action to NAN , you cannot set mA Output Fault Action or Frequency Output Fault Action to None . If you try to do this, the transmitter will not accept the configuration.
7 Completing the configuration Topics covered in this chapter: • Test or tune the system using sensor simulation • Back up transmitter configuration • Enable write-protection on the transmitter configuration 7.
Option Required values Sawtooth Period Minimum Maximum Sine Period Minimum Maximum 4. For density, set Wave Form as desired and enter the required values. Option Required values Fixed Fixed Value Sawtooth Period Minimum Maximum Sine Period Minimum Maximum 5.
When sensor simulation is enabled, the simulated values are stored in the same memory locations used for process data from the sensor. The simulated values are then used throughout transmitter functioning.
The backup file is saved to the specified name and location. It is saved as a text file and can be read using any text editor. 7.3 Enable write-protection on the transmitter configuration Display (sta.
Part III Operations, maintenance, and troubleshooting Chapters covered in this part: • Transmitter operation • Measurement support • Troubleshooting Operations, maintenance, and troubleshooting .
8 Transmitter operation Topics covered in this chapter: • Record the process variables • View process variables • View transmitter status using the status LED • View and acknowledge status alarms • Read totalizer and inventory values • Start and stop totalizers and inventories • Reset totalizers • Reset inventories 8.
8.2 View process variables Display (standard) Scroll to the desired process variable. If AutoScroll is enabled, you can wait until the proc- ess variable is displayed. See Section 8.2.1 for more information. Chinese-language display Scroll to the desired process variable.
Transmitter display features Figure 8-1: A B C D E F G H A. Status LED B. Display (LCD panel) C. Process variable D. Scroll optical switch E. Optical switch indicator: turns red when either Scroll or Select is activated F. Select optical switch G. Unit of measure for process variable H.
Chinese-language display features Figure 8-2: A C D E F G B A. Process variable B. Current value of the process variable C. Scroll up optical switch D. Scroll down optical switch E. Select optical switch F. Unit of measure for process variable G. Display (LCD panel) 8.
• If your transmitter does not have a display, it does not have a status LED. This option is not available. To interpret the status LED, see the following table. Restriction If LED Blinking is disabled, the status LED will flash only during calibration.
Procedure See Figure 8-3 . Transmitter operation 122 Micro Motion ® Model 1700 Transmitters with Analog Outputs.
Using the display to view and acknowledge the status alarms Figure 8-3: SEE ALARM Y es Scroll and Select simultaneously for 4 seconds ACK ALL Y es EXIT Select No Alarm code Scroll ACK Y es Select No A.
Postrequisites • To clear the following alarms, you must correct the problem, acknowledge the alarm, then power-cycle the transmitter: A001, A002, A010, A011, A012, A013, A018, A019, A022, A023, A024, A025, A028, A029, A031. • For all other alarms: - If the alarm is inactive when it is acknowledged, it will be removed from the list.
Using the Chinese-language display to view and acknowledge the status alarms Figure 8-4: Acknowledge All* Y es Exit Select No Down Select *This screen is displayed only if the Acknowledge All function is enabled and there are unacknowledged alarms.
- If the alarm is inactive when it is acknowledged, it will be removed from the list. - If the alarm is active when it is acknowledged, it will be removed from the list when the alarm condition clears. 8.4.3 View and acknowledge alarms using ProLink II You can view a list containing all alarms that are active, or inactive but unacknowledged.
Category Description Failed: Fix Now A meter failure has occurred and must be addressed immediately. Maintenance: Fix Soon A condition has occurred that can be fixed at a later time. Advisory: Informational A condition has occurred, but requires no maintenance from you.
• Recent Alerts Alarm data in transmitter memory Table 8-2: Alarm data structure Transmitter action if condition occurs Contents Clearing Alert List As determined by the alarm status bits, a list of.
8.6 Start and stop totalizers and inventories Display (standard) See Section 8.6.1 . Chinese-language display Offline Maintain > Totalizer Mgmt > Start Totals Offline Maintain > Totalizer Mgm.
4. Select . 5. Select again to confirm. 6. Scroll to EXIT . • To stop all totalizers and inventories using the display: 1. Scroll until the word TOTAL appears in the lower left corner of the display. Important Because all totalizers are started or stopped together, it does not matter which total you use.
Tip When you reset a single totalizer, the values of other totalizers are not reset. Inventory values are not reset. 8.7.1 Reset totalizers using the display (standard option) Prerequisites The Totalizer Reset display function must be enabled. The totalizer that you want to reset must be configured as a display variable.
6. Scroll to EXIT . 7. Select . 8.8 Reset inventories ProLink II ProLink > Totalizer Control > Reset Inventories ProLink > Totalizer Control > Reset Mass Inventory ProLink > Totalizer C.
9 Measurement support Topics covered in this chapter: • Options for measurement support • Use Smart Meter Verification • Zero the flowmeter • Validate the meter • Perform a (standard) D1 and D2 density calibration • Perform a D3 and D4 density calibration (T-Series sensors only) • Perform temperature calibration 9.
9.2.1 Smart Meter Verification requirements To use Smart Meter Verification, the transmitter must be paired with an enhanced core processor, and the Smart Meter Verification option must be ordered for the transmitter.
Smart Meter Verification has an output mode called Continuous Measurement that allows the transmitter to keep measuring while the test is in progress. If you choose to run the test in Last Measured Value or Fault modes instead, the transmitter outputs will be held constant for the two minute duration of the test.
Option Description Last Value During the test, all outputs will go to their configured fault action. The test will run for approximately 140 seconds. While the test is in progress, dots traverse the display and test progress is shown. Postrequisites View the test results and take any appropriate actions.
Smart Meter Verification flowchart: Running a test using the display Running a Smart Meter Verification test using the display Figure 9-2: OUTPUTS ARE YOU SURE/YES? .
Smart Meter Verification – Top-level menu Figure 9-3: Run V erify Read Results Schedule V erify Exit Down Down Down Down Select Select Select Select *This option is displayed only if the transmitter is connected to an enhanced core processor (V3.6 or higher) and the meter verification software is installed on the transmitter.
Smart Meter Verification flowchart: Running a test using the Chinese-language display Running a Smart Meter Verification test using the Chinese-language display Figure 9-4: Stop?/Y es .
Option Description Outputs Continue Measuring During the test, all outputs will continue to report their assigned proc- ess variable. The test will run for approximately 90 seconds. Outputs Held at Last Value During the test, all outputs will report the last measured value of their assigned process variable.
• Overview > Shortcuts > Meter Verification • Service Tools > Maintenance > Routine Maintenance > Meter Verification 2. Choose Manual Verification .
If you use ProLink II or ProLink III to run a test, a test result chart and a test report are displayed at the completion of the test. On-screen directions are provided to manipulate the test data or export the data to a CSV file for offline analysis.
Smart Meter Verification flowchart: Viewing test results using the display (standard option) Viewing Smart Meter Verification test results using the display (standard option) Figure 9-6: RESUL TS READ.
View test result data using the Chinese-language display 1. If you have just run a test, results are displayed automatically at the end of the test. 2.
Smart Meter Verification flowchart: Viewing test results using the Chinese- language display Viewing Smart Meter Verification test results using the Chinese-language display Figure 9-8: Read Results S.
View test result data using ProLink III 1. Choose Device Tools > Diagnostics > Meter Verification and click Previous Test Results . The chart shows test results for all tests stored in the ProLink III database. 2. (Optional) Click Next to view and print a test report.
Abort A problem occurred with the meter verification test (e.g., process instability) or you stopped the test manually. See Table 9-3 for a list of abort codes, a descript of each code, and possible actions you can take in response.
Smart Meter Verification – Top-level menu Figure 9-9: Scroll and Select simultaneously for 4 seconds ENTER METER VERFY Scroll RUN VERFY RESUL TS READ SCHEDULE VERFY Select EXIT Scroll Scroll Scroll Scroll Select Select Select Select 2. Scroll to Schedule Verfy and press Select .
Smart Meter Verification flowchart: Scheduling test execution using the display (standard option) Scheduling Smart Meter Verification test execution using the display (standard option) Figure 9-10: SC.
Smart Meter Verification – Top-level menu Figure 9-11: Run V erify Read Results Schedule V erify Exit Down Down Down Down Select Select Select Select *This option is displayed only if the transmitter is connected to an enhanced core processor (V3.6 or higher) and the meter verification software is installed on the transmitter.
Smart Meter Verification flowchart: Scheduling test execution using the Chinese- language display Scheduling Smart Meter Verification test execution using the Chinese-language display Figure 9-12: Sch.
3. To schedule recurring execution, specify a value for Hours Between Recurring Runs . 4. To disable scheduled execution: • To disable execution of a single scheduled test, set Hours Until Next Run to 0. • To disable recurring execution, set Hours Between Recurring Runs to 0.
9.3.1 Zero the flowmeter using the display (standard option) Zeroing the flowmeter establishes a baseline for process measurement by analyzing the sensor's output when there is no flow through the sensor tubes. Restriction You cannot change the Zero Time setting from the display.
• Set Zero Time to a lower value, then retry. • If the zero continues to fail, contact Micro Motion. • If you want to return the flowmeter to operation using a previous zero value: - To restore the zero value set at the factory: OFFLINE MAINT > ZERO > RESTORE ZERO > RESTORE/YES? .
• Ensure that there is no flow through the sensor, then retry. • Remove or reduce sources of electromechanical noise, then retry. • Set Zero Time to a lower value, then retry.
• If the zero procedure was successful, the Calibration in Progress light returns to green and a new zero value is displayed. • If the zero procedure failed, the Calibration Failure light turns red. Postrequisites Restore normal flow through the sensor by opening the valves.
2. Choose Device Tools > Calibration > Zero Verification and Calibration . 3. Click Calibrate Zero . 4. Modify Zero Time , if desired. Zero Time controls the amount of time the transmitter takes to determine its zero- flow reference point. The default Zero Time is 20 seconds.
d. Verify that the sensor is blocked in, that flow has stopped, and that the sensor is completely full of process fluid. e. Observe the drive gain, temperature, and density readings. If they are stable, check the Live Zero or Field Verification Zero value.
9.4 Validate the meter Display (standard) OFF-LINE MAINT > CONFG > UNITS > MTR F Chinese-language display Offline Maintain > Configuration > Meter Factor ProLink II ProLink > Configu.
Important For good results, the reference device must be highly accurate. Procedure 1. Determine the meter factor as follows: a. Use the flowmeter to take a sample measurement.
Procedure 1. Calculate the meter factor for density, using the standard method (see Section 9.4 ). 2. Calculate the meter factor for volume flow from the meter factor for density: MeterFactor V olume 1 MeterFactor Density = Note The following equation is mathematically equivalent to the first equation.
• If LD Optimization is enabled on your meter, disable it. To do this, choose ProLink > Configuration > Sensor and ensure that the checkbox is not checked. LD Optimizatio n is used only with large sensors in hydrocarbon applications. In some installations, only Micro Motion customer service has access to this parameter.
Postrequisites If you disabled LD Optimization before the calibration procedure, re-enable it. 9.5.2 Perform a D1 and D2 density calibration using ProLink III Prerequisites • During density calibrat.
D1 and D2 density calibration using ProLink III Figure 9-14: Enter density of D1 fluid D1 calibration Close shutoff valve downstream from sensor Fill sensor with D1 fluid Done Device T ools > Calib.
• Before performing the calibration, record your current calibration parameters. If the calibration fails, restore the known values. Restriction For T-Series sensors, the D1 calibration must be performed on air and the D2 calibration must be performed on water.
9.6 Perform a D3 and D4 density calibration (T- Series sensors only) For T-Series sensors, the optional D3 and D4 calibration could improve the accuracy of the density measurement if the density of your process fluid is less than 0.8 g/cm 3 or greater than 1.
D3 or D3 and D4 density calibration using ProLink II Figure 9-16: Enter density of D3 fluid Calibration in Progress light turns green Calibration in Progress light turns red D3 calibration Close shuto.
- Minimum difference of 0.1 g/cm 3 between the density of the D4 fluid and the density of the D3 fluid. The density of the D4 fluid must be greater than the density of the D3 fluid. - Minimum difference of 0.1 g/cm 3 between the density of the D4 fluid and the density of water.
• For D3 density calibration, the D3 fluid must meet the following requirements: - Minimum density of 0.6 g/cm 3 - Minimum difference of 0.1 g/cm 3 between the density of the D3 fluid and the density of water. The density of the D3 fluid may be either greater or less than the density of water.
D3 or D3 and D4 density calibration using the Field Communicator Figure 9-18: Enter density of D3 fluid Density Calibration Complete message Calibration in Progress message D3 calibration Close shutof.
Prerequisites The temperature calibration is a two-part procedure: temperature offset calibration and temperature slope calibration. The two parts must be performed without interruption, in the order shown. Ensure that you are prepared to complete the process without interruption.
Prerequisites The temperature calibration is a two-part procedure: temperature offset calibration and temperature slope calibration. The two parts must be performed without interruption, in the order shown. Ensure that you are prepared to complete the process without interruption.
10 Troubleshooting Topics covered in this chapter: • Status LED states • Status alarms • Flow measurement problems • Density measurement problems • Temperature measurement problems • Milli.
10.1 Status LED states The status LED on the transmitter indicates whether or not alarms are active. If alarms are active, view the alarm list to identify the alarms, then take appropriate action to correct the alarm condition. Your transmitter has a status LED only if it has a display.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A003 No Sensor Response The transmitter is not receiving one or more basic electrical sig- nals from the sensor.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A005 Mass Flow Rate Overrange The sensor is signaling a flow rate that is out of range for the sen- sor. 1. If other alarms are present, resolve those alarm conditions first.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A008 Density Overrange The sensor is signaling a density reading below 0 g/cm 3 or above 10 g/cm 3 .
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A010 Calibration Failure This alarm is typically caused by flow through the sensor during the zero, or by a zero offset result that is out of range.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A016 Sensor RTD Failure The sensor RTD is signaling a resistance that is out of range for the sensor. 1. Check the wiring between the sensor and the transmitter.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A019 RAM Error (Transmitter) Power to the transmitter must be cycled to clear this alarm. 1. Check that all wiring compartment covers are installed prop- erly.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A026 Sensor/Transmitter Communi- cations Failure The transmitter has lost communication with the core processor on the sensor.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A031 Low Power The core processor on the sensor is not receiving sufficient pow- er. Check the wiring between the transmitter and the sensor. Power to the transmitter must be cycled to clear this alarm.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A100 mA Output 1 Saturated The calculated mA output value is outside of the meter's config- ured range. 1. Check the Upper Range Value and Lower Range Value parame- ters.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A110 Frequency Output Saturated The calculated frequency output is outside the configured range. 1. Check the Frequency Output Scaling Method parameter.
Status alarms and recommended actions (continued) Table 10-2: Alarm code Description Recommended actions A117 Density Overrange (Petrole- um) 1. Check your process conditions against the values reported by the flowmeter. 2. Verify the configuration of the petroleum measurement ta- ble type and density.
10.3 Flow measurement problems Flow measurement problems and recommended actions Table 10-3: Problem Possible causes Recommended actions Flow indication at no flow conditions or zero offset • Misali.
Flow measurement problems and recommended actions (continued) Table 10-3: Problem Possible causes Recommended actions Erratic non-zero flow rate when flow is steady • Slug flow • Damping value too.
10.4 Density measurement problems Density measurement problems and recommended actions Table 10-4: Problem Possible causes Recommended actions Inaccurate density reading • Problem with process fluid.
10.5 Temperature measurement problems Temperature measurement problems and recommended actions Table 10-5: Problem Possible causes Recommended actions Temperature reading significantly different from process temper- ature • RTD failure • Wiring problem • Check junction box for moisture or verdi- gris.
10.6 Milliamp output problems Milliamp output problems and recommended actions Table 10-6: Problem Possible causes Recommended actions No mA output • Wiring problem • Circuit failure • Channel not configured for desired output • Check the power supply and power supply wiring.
Milliamp output problems and recommended actions (continued) Table 10-6: Problem Possible causes Recommended actions Consistently incorrect mA measurement • Loop problem • Output not trimmed corre.
10.8 Use sensor simulation for troubleshooting When sensor simulation is enabled, the transmitter reports user-specified values for mass flow, temperature, and density.
6. Reapply power to the transmitter. CAUTION! If the transmitter is in a hazardous area, do not reapply power to the transmitter with the housing cover removed. Reapplying power to the transmitter while the housing cover is removed could cause an explosion.
Procedure Refer to the sensor and transmitter installation manuals for grounding requirements and instructions. 10.12 Perform loop tests A loop test is a way to verify that the transmitter and the remote device are communicating properly. A loop test also helps you know whether you need to trim mA outputs.
2. Test the frequency output(s). a. Choose OFFLINE MAINT > SIM > FO SIM , and select the frequency output value. The frequency output can be set to 1, 10, or 15 kHz.
Procedure 1. Test the mA output(s). a. Choose Offline Maintain > Simulation > Milliamp Output and select a low value, e.g., 4 mA. Dots traverse the display while the output is fixed. b. Read the mA current at the receiving device and compare it to the transmitter output.
c. At the transmitter, activate Select . d. Scroll to and select Off . e. Verify the signal at the receiving device. f. At the transmitter, activate Select . Postrequisites • If the mA output reading at the receiving device was slightly inaccurate, you can correct this discrepancy by trimming the output.
The readings do not need to match exactly. If the values are slightly different, you can correct the discrepancy by trimming the output. i. Click UnFix mA . 2. Test the frequency output(s). a. Choose ProLink > Test > Fix Freq Out . b. Enter the frequency output value in Set Output To .
Procedure 1. Test the mA output(s). a. Choose Device Tools > Diagnostics > Testing > mA Output 1 Test or Device Tools > Diagnostics > Testing > mA Output 2 Test . b. Enter 4 in Fix to: . c. Click Fix mA . d. Read the mA current at the receiving device and compare it to the transmitter output.
• If the mA output reading at the receiving device was significantly inaccurate, or if at any step the reading was faulty, verify the wiring between the transmitter and the remote device, and try again. • If the discrete output reading is reversed, check the setting of Discrete Output Polarity .
b. Read the frequency signal at the receiving device and compare it to the transmitter output. c. Choose End . 3. Test the discrete output(s). a. Press Service Tools > Simulate > Simulate Outputs > Discrete Output Test . b. Choose Off . c. Verify the signal at the receiving device.
2. Follow the instructions in the guided method. Important If you are using a HART/Bell 202 connection, the HART signal over the primary mA output affects the mA reading. Disconnect the wiring between ProLink II and the transmitter terminals when reading the primary mA output at the receiving device.
Prerequisites Ensure that the mA output is wired to the receiving device that will be used in production. Procedure 1. Choose . 2. Follow the instructions in the guided method. Important The HART signal over the primary mA output affects the mA reading.
10.15 Check HART Address and Loop Current Mode If the transmitter is producing a fixed current from the mA output, the Loop Current Mode parameter may be disabled. When Loop Current Mode is disabled, the mA output produces a fixed value, and does not report process data or implement its fault action.
2. If there are active fault conditions, the transmitter is performing correctly. If you want to change its behavior, consider the following options: • Change the setting of mA Output Fault Action . • For the relevant status alarms, change the setting of Alarm Severity to Ignore .
10.22 Check Frequency Output Fault Action The Frequency Output Fault Action controls the behavior of the frequency output if the transmitter encounters an internal fault condition. If the frequency output is reporting a constant value, the transmitter may be in a fault condition.
10.25 Check for slug flow (two-phase flow) Slug flow (two-phase flow, entrained gas) can cause spikes in the drive gain. This may cause the transmitter to report zero flow, or to post several different alarms. 1. Check for slug flow alarms. If the transmitter is not generating slug flow alarms, slug flow is not the source of your problem.
Possible causes and recommended actions for excessive (saturated) drive gain (continued) Table 10-8: Possible cause Recommended actions Bent flow tube Check the pickoff voltages (see Section 10.27 ). If either of them are close to zero (but neither is zero), the flow tubes may be bent.
To know whether your pickoff voltage is unusually low, you must collect pickoff voltage data during the problem condition and compare it to pickoff voltage data from a period of normal operation.
Possible causes and recommended actions for electrical shorts Table 10-11: Possible cause Recommended action Moisture inside the junction box Ensure that the junction box is dry and no corrosion is present. Liquid or moisture inside the sensor case Contact Micro Motion.
Coils and test terminal pairs (continued) Table 10-12: Coil Sensor model Terminal colors Composite RTD T-Series Yellow to orange Fixed resistor (see note) CMF400 Yellow to orange Note The CMF400 fixed resistor applies only to certain specific CMF400 releases.
1. Plug the terminal blocks into the terminal board. 2. Replace the end-cap on the core processor housing. 3. Replace the lid on the sensor junction box. Important When reassembling the meter components, be sure to grease all O-rings. 10.29 Check the core processor LED The core processor has an LED that indicates different meter conditions.
4. If you have a 9-wire remote installation: a. Remove the end-cap. 9-wire remote installation components Figure 10-2: Transmitter Core processor 4 x cap screws (4 mm) End-cap b. Inside the core processor housing, loosen the three screws that hold the core processor mounting plate in place.
• For a 9-wire remote installation: 1. Without pinching or stressing the wires, slide the mounting plate into place. 2. Rotate the mounting plate so that the screws are in the locked position. 3. Tighten the screws, torquing to 6 to 8 in-lbs (0.7 to 0.
Enhanced core processor LED states Table 10-14: LED state Description Recommended action Solid green Normal operation No action required. Flashing yellow Zero in progress No action required. Solid yellow Low-severity alarm Check alarm status. Solid red High-severity alarm Check alarm status.
Integral installation components Figure 10-3: Base 4 x cap screws (4 mm) Transition ring Transmitter Core processor b. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked position. c. Gently lift the transmitter straight up, disengaging it from the cap screws.
5. At the core processor, disconnect the 4-wire cable between the core processor and the transmitter. 6. Measure the resistance between core processor terminal pairs 3–4, 2–3, and 2–4.
Appendix A Using the standard transmitter display Topics covered in this appendix: • Components of the transmitter interface • Use the optical switches • Access and use the display menu system • Display codes for process variables • Codes and abbreviations used in display menus • Menu maps for the transmitter display A.
Transmitter interface Figure A-1: A B C D E F G H A. Status LED B. Display (LCD panel) C. Process variable D. Scroll optical switch E. Optical switch indicator F. Select optical switch G. Unit of measure for process variable H. Current value of process variable A.
Optical switch indicator and optical switch states Table A-1: Optical switch indicator State of optical switches Solid red One optical switch is activated.
Tip If you do not know the correct value for Off-Line Password , wait 30 seconds. The password screen will time out automatically and you will be returned to the previous screen. 4. If Scroll flashes on the display, activate the Scroll optical switch, then the Select optical switch, and then the Scroll optical switch again.
1. Activate Select until the digit you want to change is active (flashing). Select moves the cursor one position to the left. From the leftmost position, Select moves the cursor to the rightmost digit. 2. Activate Scroll to change the value of the active digit.
- If the displayed value is not the same as the value in transmitter memory, SAVE/ YES? flashes on the display. Activate Scroll . Enter a floating-point value using exponential notation Exponential notation is used to enter values that are larger than 99999999 or smaller than − 9999999.
f. Activate Scroll until the desired character is displayed. g. Activate Select to move the cursor one digit to the left. h. Activate Scroll until the desired character is displayed. 4. Enter the sign. a. Activate Select to move the cursor one digit to the left.
Display codes for process variables (continued) Table A-2: Code Definition Comment or reference MTR_T Case temperature (T-Series sensors only) NET M Net mass flow rate Concentration measurement applic.
Codes and abbreviations used in display menus (continued) Table A-3: Code or abbrevi- ation Definition Comment or reference ACT Action ADDR Address AO 1 SRC Fixed to the process variable assigned to t.
Codes and abbreviations used in display menus (continued) Table A-3: Code or abbrevi- ation Definition Comment or reference ENABLE PASSW Enable password Enable or disable password protection for displ.
Codes and abbreviations used in display menus (continued) Table A-3: Code or abbrevi- ation Definition Comment or reference MSMT Measurement OFFLN Off-line OFF-LINE MAINT Off-line maintenance P/UNT Pulses/unit POLAR Polarity PRESS Pressure QUAD Quadrature r.
A.6 Menu maps for the transmitter display Offline menu – top level Figure A-2: Scroll and Select simultaneously for 4 seconds SWREV OFF-LINE MAINT Select SEE ALARM Scroll Scroll Scroll EXIT CONFG Sc.
Offline menu – version information Figure A-3: Scroll and Select simultaneously for 4 seconds SWREV Y es Version info* Scroll Select Y es ETO info* Scroll Scroll SENSOR VERFY* Scroll EXIT OFF-LINE MAINT Select Scroll * Displayed only if the corresponding ET O or application is installed on the transmitter.
Offline menu – configuration: units and I/O Figure A-4: OFF-LINE MAINT Scroll and Select simultaneously for 4 seconds Scroll Select Select Scroll CONFG MASS UNITS VOL/GSV DENS TEMP Select Scroll Scr.
Offline menu – configuration: meter factor, display, and digital communications Figure A-5: OFF-LINE MAINT Scroll and Select simultaneously for 4 seconds Scroll Select Select Scroll CONFG UNITS MASS.
Offline menu – alarms Figure A-6: SEE ALARM Scroll and Select simultaneously for 4 seconds ACK ALL* Y es EXIT Select No Alarm code Scroll ACK Y es Select No Active/ unacknowledged alarms? No Y es Se.
Offline menu – meter verification: top level Figure A-7: Scroll and Select simultaneously for 4 seconds ENTER METER VERFY Scroll RUN VERFY RESUL TS READ SCHEDULE VERFY Select EXIT Scroll Scroll Scro.
Offline menu – meter verification test Figure A-9: OUTPUTS ARE YOU SURE/YES? . . . . . . . . . . . . . . . x % P ASS VERFY ABORTED VERFY CAUTION VERFY Fail Abort RERUN/YES? Y es No Correct condition.
Offline menu – meter verification results Figure A-10: RESUL TS READ Select xx L STF% RUNCOUNT x Select xx HOURS Select P ASS Select xx R STF% Select RESUL TS MORE? Select Scroll Pass Select Scroll .
Offline menu – totalizers and inventories Figure A-11: RESET (3) Select Scroll STOP/ST ART (2) RESET YES? Process variable display STOP/ST ART YES? Scroll Mass total V olume total Scroll Select Y es.
Offline menu – Simulation (loop testing) Figure A-12: Scroll and Select simultaneously for 4 seconds Y es Scroll Select AO SIM FO SIM DO SIM Scroll Select SET x MA* Y es Select** SET y KHZ**** Select SET OFF SET ON Select EXIT Scroll Scroll Select*** .
Offline menu – Zero Figure A-13: …………………. OFF-LINE MAINT Scroll and Select simultaneously for 4 seconds Scroll Select Select CAL ZERO Troubleshoot ZERO/YES? CAL P ASS CAL F AIL RESTORE.
Appendix B Using the Chinese-language display Topics covered in this appendix: • Components of the transmitter interface • Use the optical switches • Access and use the display menu system • Menu maps for the transmitter display B.
Display feature shortcut keys Figure B-2: A B C D E A. Returns to the process variable view B. Change the language display: English or Chinese C. Access to show or hide the Offline menu D. Unlock or lock the display E. Activate the optical switches in the shown combinations to perform the specific task B.
Optical switch indicator and optical switch states Table B-1: Optical switch indicator State of optical switches Solid red One optical switch is activated.
b. Repeat this process for the second, third, and fourth digits. Tip If you do not know the correct value for Offline Password , wait 30 seconds. The password screen will time out automatically and you will be returned to the previous screen.
Procedure • To change the value: 1. Activate Select until the digit you want to change is active (flashing). Select moves the cursor one position to the left. From the leftmost position, Select moves the cursor to the rightmost digit. 2. Activate Up/Down to change the value of the active digit.
Exponential values entered via the display must be in the following form: SX.XXXEYY . In this string: • S = Sign. A minus sign ( − ) indicates a negative number. A blank indicates a positive number. • X.XXX = The 4-digit mantissa. • E = The exponent indicator.
b. Activate Up/Down until the desired character is displayed. For positive numbers, select a blank space. 5. To save the displayed value to transmitter memory, activate Down and Select simultaneously and hold until the display changes.
B.4 Menu maps for the transmitter display Offline menu – top level Figure B-3: Software V ersion Offline Maintain Select Alarm Down Down Exit Configuration Down Simulation T otalizer Mgmt Down Down .
Offline menu – version information Figure B-4: Software V ersion Transmitter and Core V ersion Information (Read Only) Select Y es ETO (CEQ) info* Down Y es Meter V erify** Down Down Exit Offline Maintain Up Down *The option is displayed only if the corresponding CEQ/ETO or application is installed on the transmitter.
Offline menu – configuration: units and I/O Figure B-5: Offline Maintain Select Select Down Select Configuration Mass Flow Rate Units V olume Flow Rate* Density T emperature Select Down Down Down mA.
Offline menu – configuration: meter factor and display Figure B-6: …(continued) Mass Flow Rate Meter Factor V olume Flow Rate Select Down Down LD Optimization Exit Down Down Down Reset T otals Dis.
Offline menu – configuration: sensor calibration, low flow cutoff, and damping Figure B-7: …(continued) Down Calibrate Sensor Select Flow Cal Factor Density Cal Factor T emperature Cal Factor Exit.
Offline menu – alarms Figure B-8: Acknowledge All* Y es Exit Select No Down Select *This screen is displayed only if the Acknowledge All function is enabled and there are unacknowledged alarms.
Offline menu – meter verification: top level Figure B-9: Run V erify Read Results Schedule Verify Exit Down Down Down Down Select Select Select Select *This option is displayed only if the transmitter is connected to an enhanced core processor (V3.6 or higher) and the meter verification software is installed on the transmitter.
Offline menu – meter verification test Figure B-11: Stop?/Y es . . . . . . . . . . . . . . . x % Pass V erify Abort V erify Caution V erify Fail Abort Sensor Rerun? Y es No Correct condition Run V e.
Offline menu – meter verification results Figure B-12: Read Results Select xx L STF% Run Count x Select Hours Left xx Select Pass V erify Up xx R STF% Up Select Down Pass Result type Fail Abort Hour.
Offline menu – totalizers and inventories Figure B-13: Offline Maintain Select Select Down Select T otalizer Mgmt Event 2 T otal* Event 1 T otal* Start T otals** Reset T otal Down Down Down Down Exit Process variable display Up Select Stop T otals** Down *This option displays only when Event X is enabled.
Offline menu – Simulation (loop testing) Figure B-14: Y es Select Milliamp Output Frequency Output* Discrete Output* Down Select x mA (1) Y es y KHZ (4) Select Off On Select Exit Down Down Select (3) . . . . . . . . . . . . . . . . Exit Y es Down . .
Offline menu – Zero Figure B-15: …………………. Select Calibration Zero Troubleshoot Zero? Calibration Result Pass Calibration Result Fail Zero Result Current Zero Standard Deviation* Select.
Appendix C Using ProLink II with the transmitter Topics covered in this appendix: • Basic information about ProLink II • Connect with ProLink II • Menu maps for ProLink II C.1 Basic information about ProLink II ProLink II is a software tool available from Micro Motion.
ProLink II messages As you use ProLink II with a Micro Motion transmitter, you will see a number of messages and notes. This manual does not document all of these messages and notes. Important The user is responsible for responding to messages and notes and complying with all safety messages.
C.2.2 Make a service port connection CAUTION! If the transmitter is in a hazardous area, do not use a service port connection. Service port connections require opening the wiring compartment, and opening the wiring compartment while the transmitter is powered up could cause an explosion.
Connection to service port Figure C-1: A C D E B A. PC B. Signal converter C. Service port terminal 7 (RS-485/A) D. Service port terminal 8 (RS-485/B) E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
CAUTION! If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals. Connecting directly to the transmitter terminals requires opening the wiring compartment, and opening the wiring compartment while the transmitter is powered up could cause an explosion.
Connection to transmitter terminals Figure C-2: A C D B A. PC B. Signal converter C. 250–600 Ω resistance D. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection. USB connections are also supported.
Connection over local loop Figure C-3: A C D E R1 R3 R2 B A. PC B. Signal converter C. Any combination of resistors R1, R2, and R3 as necessary to meet HART communication resistance requirements D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Connection over multidrop network Figure C-4: B A C D A. Signal converter B. 250–600 Ω resistance C. Devices on the network D. Master device 5. Start ProLink II. 6. Choose Connection > Connect to Device . 7. Set Protocol to HART Bell 202 . Tip HART/Bell 202 connections use standard connection parameters.
Option Description Primary Use this setting if no other host is on the network. The Field Communicator is not a host. 12. Click Connect . Need help? If an error message appears: • Verify the HART address of the transmitter. • Ensure that you have specified the correct COM port.
Tip HART connections are not polarity-sensitive. It does not matter which lead you attach to which terminal. Connection to transmitter terminals Figure C-5: A C B A. PC B. Signal converter C. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Connection over network Figure C-6: A C E D B A. PC B. Signal converter C. 120- Ω , 1/2-watt resistors at both ends of the segment, if necessary D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Option Description Secondary Use this setting if another HART host such as a DCS is on the network. Primary Use this setting if no other host is on the network. The Field Communicator is not a host. 9. Click Connect . Need help? If an error message appears: • Verify the HART address of the transmitter.
Tip Usually, but not always, the black lead is RS-485/A and the red lead is RS-485/B. Connection to transmitter terminals Figure C-7: A C B A. PC B. Signal converter C. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Connection over network Figure C-8: A C E D B A. PC B. Signal converter C. 120- Ω , 1/2-watt resistors at both ends of the segment, if necessary D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Need help? If an error message appears: • Verify the Modbus address of the transmitter. • Ensure that you have specified the correct COM port. • Check the physical connection between the PC and the transmitter. • Increase or decrease resistance.
Main menu (continued) Figure C-10: Data Logging* Enable/Disable Custody T ransfer Gas Unit Configurator Meter V erification Entrained Gas Analyzer Commissioning Wizard Proving Wizard Marine Bunker T r.
Configuration menu Figure C-11: Flow • Flow Direction • Flow Damp • Flow Cal • Mass Flow Cutoff • Mass Flow units • Mass Factor • Dens Factor • V ol Factor • Flow Switch V ariable .
Configuration menu (continued) Figure C-12: T emperature • T emp Units • T emp Cal Factor • T emp Damping • External T emperature • External RTD Frequency/Discrete Output • Frequency • T.
Configuration menu (continued) Figure C-13: ProLink > Configuration Device • Model • Manufacturer • Hardware Rev • Distributor • Software Rev • ETO • CP Software Rev • CP ETO • Op.
Configuration menu (continued) Figure C-14: ProLink > Configuration Polled V ariables Polled V ariable 1/2 • Polling Control • External T ag • V ariable T ype • Current V alue Discrete Even.
Configuration menu (continued) Figure C-15: ProLink > Configuration Special Units • Base Mass Unit • Base Mass Time • Mass Flow Conv Fact • Mass Flow T ext • Mass T otal T ext • Base V .
Configuration menu (continued) Figure C-16: ProLink > Configuration Sensor Simulation • Enable/disable • Mass flow • Wave form • Fixed value • Period • Minimum • Maximum • Density .
Appendix D Using ProLink III with the transmitter Topics covered in this appendix: • Basic information about ProLink III • Connect with ProLink III • Menu maps for ProLink III D.1 Basic information about ProLink III ProLink III is a configuration and service tool available from Micro Motion.
ProLink III messages As you use ProLink III with a Micro Motion transmitter, you will see a number of messages and notes. This manual does not document all of these messages and notes. Important The user is responsible for responding to messages and notes and complying with all safety messages.
D.2.2 Make a service port connection CAUTION! If the transmitter is in a hazardous area, do not use a service port connection. Service port connections require opening the wiring compartment, and opening the wiring compartment while the transmitter is powered up could cause an explosion.
Connection to service port Figure D-1: A C D E B A. PC B. Signal converter C. Service port terminal 7 (RS-485/A) D. Service port terminal 8 (RS-485/B) E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
CAUTION! If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals. Connecting directly to the transmitter terminals requires opening the wiring compartment, and opening the wiring compartment while the transmitter is powered up could cause an explosion.
Connection to transmitter terminals Figure D-2: A C D B A. PC B. Signal converter C. 250–600 Ω resistance D. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection. USB connections are also supported.
Connection over local loop Figure D-3: A C D E R1 R3 R2 B A. PC B. Signal converter C. Any combination of resistors R1, R2, and R3 as necessary to meet HART communication resistance requirements D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Connection over multidrop network Figure D-4: B A C D A. Signal converter B. 250–600 Ω resistance C. Devices on the network D. Master device 5. Start ProLink III. 6. Choose Connect to Physical Device . 7. Set Protocol to HART Bell 202 . Tip HART/Bell 202 connections use standard connection parameters.
Option Description Primary Use this setting if no other host is on the network. The Field Communicator is not a host. 12. Click Connect . Need help? If an error message appears: • Verify the HART address of the transmitter. • Ensure that you have specified the correct COM port.
Tip HART connections are not polarity-sensitive. It does not matter which lead you attach to which terminal. Connection to transmitter terminals Figure D-5: A C B A. PC B. Signal converter C. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Connection over network Figure D-6: A C E D B A. PC B. Adapter, if necessary C. Signal converter D. 120- Ω , 1/2-watt resistors at both ends of the segment, if necessary E. DCS or PLC F. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
8. Set Master as appropriate. Option Description Secondary Use this setting if another HART host such as a DCS is on the network. Primary Use this setting if no other host is on the network. The Field Communicator is not a host. 9. Click Connect . Need help? If an error message appears: • Verify the HART address of the transmitter.
b. Connect the leads from the signal converter to terminals 5 (RS-485/A) and 6 (RS-485/B). Tip Usually, but not always, the black lead is RS-485/A and the red lead is RS-485/B. Connection to transmitter terminals Figure D-7: A C B A. PC B. Signal converter C.
Connection over network Figure D-8: A C E D B A. PC B. Signal converter C. 120- Ω , 1/2-watt resistors at both ends of the segment, if necessary D. DCS or PLC E. Transmitter, with wiring compartment and power supply compartment opened Note This figure shows a serial port connection.
Need help? If an error message appears: • Verify the Modbus address of the transmitter. • Ensure that you have specified the correct COM port. • Check the physical connection between the PC and the transmitter. • Increase or decrease resistance.
Configuration: Process Measurement Figure D-10: Configuration: I/O Figure D-11: Using ProLink III with the transmitter 296 Micro Motion ® Model 1700 Transmitters with Analog Outputs.
Configuration: Events Figure D-12: Configuration: Communications Figure D-13: Using ProLink III with the transmitter Configuration and Use Manual 297.
Configuration: Informational Parameters Figure D-14: Device Tools: Calibration Figure D-15: Using ProLink III with the transmitter 298 Micro Motion ® Model 1700 Transmitters with Analog Outputs.
Calibration: Density Calibration Figure D-16: Calibration: Temperature Calibration Figure D-17: Using ProLink III with the transmitter Configuration and Use Manual 299.
Device Tools: Configuration Transfer Figure D-18: Diagnostics: Testing Figure D-19: Using ProLink III with the transmitter 300 Micro Motion ® Model 1700 Transmitters with Analog Outputs.
Diagnostics: Meter Verification Figure D-20: Device Tools: Trending Figure D-21: Using ProLink III with the transmitter Configuration and Use Manual 301.
Appendix E Using the Field Communicator with the transmitter Topics covered in this appendix: • Basic information about the Field Communicator • Connect with the Field Communicator • Menu maps for the Field Communicator E.
If Micro Motion is not listed, or you do not see the required device description, use the Field Communicator Easy Upgrade Utility to install the device description, or contact Micro Motion. Field Communicator menus and messages Many of the menus in this manual start with the On-Line menu.
Field Communicator connection to transmitter terminals Figure E-1: A B C A. Field Communicator B. 250–600 Ω resistance C. Transmitter, with wiring compartment and power supply compartment opened 2. To connect to a point in the local HART loop, attach the leads from the Field Communicator to any point in the loop and add resistance as necessary.
Field Communicator connection to multidrop network Figure E-3: A B C D A. Field Communicator B. 250–600 Ω resistance C. Devices on the network D. Master device 4. Turn on the Field Communicator and wait until the main menu is displayed. 5. If you are connecting across a multidrop network: a.
E.3 Menu maps for the Field Communicator On-Line menu Figure E-4: Configure 1 Manual Setup 2 Alert Setup Service T ools 1 Alerts 2 V ariables 3 T rends 4 Maintenance 5 Simulate 2 3 Overview 1 Check St.
Overview menu Figure E-5: Identification 1 T ag 2 Model 3 Xmtr Serial Num 4 Sensor Serial Num 5 Date 6 Descriptor 7 Message 1 Revisions 1 Universal 2 Field Device 3 DD Revision 4 T ransmitter Software 5 CP Software 6 ETO Number Mat. of Construction 1 T ube Wetted Mat.
Configure menu Figure E-6: Manual Setup 1 Characterize 2 Measurements 3 Display 4 Inputs/Outputs 5 Info Parameters 2 1 Alert Setup 1 I/O Fault Actions 2 Alert Severity 3 Discrete Events On-Line Menu &.
Manual Setup menu Figure E-7: Characterize 1 Sensor T ype 2 Sensor T ag Parameters Measurements 1 Flow 2 Density 3 T emperature 4 Update Rate 5 LD Optimization 6 Special Units 7 External Pressure/T em.
Manual Setup menu: Characterize Figure E-8: On-Line Menu > 2 Configure > 1 Manual Setup > 1 Characterize 2 1 2 1 Sensor T ype Straight T ube Curved T ube Density Parameters 1 D1 2 D2 3 DT 4 D.
Manual Setup menu: Measurements Figure E-9: * Displayed only if V olume Flow T ype = Liquid. Menu numbers are adjusted as required. On-Line Menu > 2 Configure > 1 Manual Setup > 2 Measurement.
Manual Setup menu: Display Figure E-10: On-Line Menu > 2 Configure > 1 Manual Setup > 3 Display Language English German French Spanish Display V ariable Menu Features 1 T otalizer Reset 2 Sta.
Manual Setup menu: I/O Figure E-11: On-Line Menu > 2 Configure > 1 Manual Setup > 4 Inputs/Outputs mA Output 1 Primary V ariable 2 mA Output Settings 3 mA Fault Settings Frequency Output 1 FO.
Manual Setup menu: I/O (continued) Figure E-12: Discrete Output 1 DO Assignment 2 DO Polarity 3 DO Fault Action 4 Flow Switch Source 5 Flow Switch Setpoint 6 Hysteresis (0.
Alert Setup menu Figure E-13: On-Line Menu > 2 Configure > 2 Alert Setup I/O Fault Actions 1 mAO Fault Action 2 mAO Fault Level 3 FO Fault Action 4 FO Fault Level 5 Comm Fault Action Alert Sever.
Service Tools menu Figure E-14: On-Line Menu > 3 Service T ools Alerts 1 Refresh Alerts Alert Name Additional Information for Above V ariables 1 V ariable Summary 2 Process V ariables 3 Mapped V ar.
Service Tools menu: Variables Figure E-15: * If V olume Flow T ype = GSV , GSV variables are displayed. On-Line Menu > 3 Service T ools > 2 V ariables Process V ariables 1 Mass Flow Rate 2 V olu.
Service Tools menu: Maintenance Figure E-16: On-Line Menu > 3 Service T ools > 4 Maintenance Routine Maintenance 1 T rim mA Output 2 Meter V erification * 1 Zero Calibration 1 Mass Flow Rate 2 V.
Service Tools menu: Simulate Figure E-17: On-Line Menu > 3 Service T ools > 5 Simulate 1 Simulate Outputs 1 mA Output Loop T est 2 Frequency Output T est/ Discrete Output T est * * Options vary depending on Channel settings.
Appendix F Default values and ranges F.1 Default values and ranges The default values and ranges represent the typical factory transmitter configuration. Depending on how the transmitter was ordered, certain values may have been configured at the factory and are not represented in the default values and ranges.
Transmitter default values and ranges (continued) Table F-1: Type Parameter Default Range Comments Density units g/cm 3 Density cutoff 0.2 g/cm 3 0.0 – 0.5 g/cm 3 D1 0 g/cm 3 D2 1 g/cm 3 K1 1000 µsec 1000 – 50,000 µsec K2 50,000 µsec 1000 – 50,000 µsec FD 0 Temp Coefficient 4.
Transmitter default values and ranges (continued) Table F-1: Type Parameter Default Range Comments Base volume time sec Volume flow conversion factor 1 Variable map- ping Primary variable Mass flow Secondary variable Density Tertiary variable Mass flow Quaternary variable Volume flow mA output 1 Primary variable Mass flow LRV –200.
Transmitter default values and ranges (continued) Table F-1: Type Parameter Default Range Comments Fault action Downscale AO fault level – downscale 2.0 mA 1.0 – 3.6 mA AO fault level – upscale 22 mA 21.0 – 24.0 mA Last measured value timeout 0.
Transmitter default values and ranges (continued) Table F-1: Type Parameter Default Range Comments Polarity Active low Display Backlight on/off On Backlight intensity 63 0 – 63 Refresh rate 200 mill.
Appendix G Transmitter components and installation wiring Topics covered in this appendix: • Installation types • Power supply terminals and ground • Input/output (I/O) wiring terminals G.1 Installation types Model 1700 and Model 2700 transmitters can be installed five different ways, only one of which applies to your specific installation.
High-temperature flexible conduit installation Figure G-2: High-temperature flexible conduit installations use the same installation instructions as 4-wire remote installations, except that the distance between the sensor and the electronics is limited by the length of the flexible conduit.
4-wire remote installation – stainless steel housing Figure G-4: Sensor Core processor Transmitter 4-wire cable • 9-wire remote – The transmitter and core processor are combined in a single unit that is installed remotely from the sensor.
9-wire remote installation type Figure G-5: Transmitter Junction box Sensor 9-wire cable • Remote core processor with remote sensor – A remote core process with remote sensor installation separates all three components – transmitter, core processor, and sensor – all of which are installed separately.
Remote core processor with remote sensor installation type Figure G-6: Core processor Transmitter 4-wire cable 9-wire cable Sensor Junction box G.2 Power supply terminals and ground Power supply wiring terminals Figure G-7: A B C A. Warning flap B. Equipment ground C.
G.3 Input/output (I/O) wiring terminals I/O wiring terminals Figure G-8: A B C A. mA/HART B. Frequency output or discrete output C. RS-485 Transmitter components and installation wiring 330 Micro Moti.
Appendix H NE 53 history H.1 NE 53 history Date Version Type Change Operating in- struction 08/2000 1.x Expansion Added writing of the device tag using Modbus 3600204 A Adjustment Improved communication handling with the HART Tri-Loop product Feature Indication of outputs option board type appears on display at power-up 05/2001 2.
Date Version Type Change Operating in- struction The display start/stop totalizers function can be enabled or disabled Petroleum measurement application improve- ments Live zero available as display v.
Date Version Type Change Operating in- struction 09/2006 5.x Expansion Discrete output assignable as a flow switch 20001715 B Discrete output fault indication configurability Discrete input support fo.
Date Version Type Change Operating in- struction Adjustment The following combinations are not allowed: • mA Output Fault Action = None and Digital Communications Fault Action = NAN • Frequency Ou.
Date Version Type Change Operating in- struction Pressing and holding the Up or Down optical switch allows continuous scrolling of the current screen in the Chinese-language display Auto-detection of .
Index A Added Damping 85 Additional Communications Response Delay 107 address HART address 102, 106 Modbus address 107 air calibration , See calibration, density alarm menu , See display alarms alarm .
customer service contacting ii cutoffs AO cutoff 84 density 49 interaction between AO Cutoff and process variable cutoffs 84 mass flow 25 troubleshooting 206 volume flow 31 D damping Added Damping 85 .
alarm password 66 off-line password 66 decimal notation 221 enabling or disabling operator actions acknowledging all alarms 66 resetting totalizers 65 starting and stopping totalizers 64 exponential n.
measurement units configuring 34 options 34 standard density 33 volume flow type 33 ground 329 grounding troubleshooting 193 GSV , See gas standard volume flow measurement H HART address 102, 106, 204.
measurement units density configuring 44, 47 options 45 gas standard volume flow rate configuring 34 options 34 special unit 36 mass flow rate configuring 21 options 22 special unit 23 pressure , See .
ProLink III connecting HART/Bell 202 284 HART/RS-485 289 Modbus/RS-485 292 service port 283 startup connection 7 connection types 282 connnecting to the transmitter 282 menu maps 295 overview 281, 282.
measurement units configuring 50 options 50 troubleshooting 189 tertiary variable (TV) 105 testing loop testing using ProLink II 197 using ProLink III 198 using the display 194, 195 using the Field Co.
Z zero procedure using ProLink II 155 using ProLink III 156 using the Field Communicator 157 restore factory zero using ProLink II 155 using ProLink III 156 using the Field Communicator 157 restore pr.
*MMI-20021712* MMI-20021712 Rev A B 201 3 Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459 www.micromotion.com Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 www.
Een belangrijk punt na aankoop van elk apparaat Emerson Model 1700 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Emerson Model 1700 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Emerson Model 1700 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Emerson Model 1700 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Emerson Model 1700 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Emerson Model 1700 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Emerson Model 1700 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Emerson Model 1700 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.