Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 www .rosemount.com Section 3 Inst allation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . .
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-2 W arnings Explosions could result in death or serious injury: • Do not remove the transmitter cover in explosive atmospheres when the circuit is alive.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-3 Rosemount 2088 and 2090 Figure 3-1. Installation Flowchart. Check for Leaks (Process Connections) Zero T rim T ransmitter for Mounting Effect s .
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-4 GENERAL CONSIDERATIONS The accuracy of the pressure measurement depends on proper installation of the transmitter and impulse piping. The piping between the process and transmitter must accurately transmit pr essure to the transmitter .
Reference Manual 00809-0100-4690, Rev EA March 2007 3-5 Rosemount 2088 and 2090 MECHANICAL CONSIDERATIONS Mounting Rosemount 2088 The Rosemount 2088 Smart T ransmitter weighs approximately 2.44 lb. (1,1 1 kg). The 2088 Analog T ransmitter weighs approximately 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-6 Impulse Piping Impulse piping configurations depend on specific measurement conditions. Use the following information and Figur e 3-3 as a guideline when installing impulse piping.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-7 Rosemount 2088 and 2090 Access Requirement s When choosing a mounting location and pos ition, take into account the need for access to the transmitter . Make wiring terminations through the conduit openings at the top of the electronics housing.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-8 Nameplate 3.9 (100) 2X 1 / 4 –20 UNC–2BX 0.60 Deep Mounting Bracket Holes 4.7 (140) T erminal Connections T ransmitter Circuitry Side Optional Meter Cover 5.0 (125) W eld Spud 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-9 Rosemount 2088 and 2090 Rosemount 2090P Installing the Rosemount 2090P transmitter involves att aching a weld spud to the tapped process vessel, att aching t he transmitter to the weld spud, and making electrical connections.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-10 3. Hand tighten the transmitter using the knurled retaining ring, then snug an additional 1 / 8 turn with adjustable pliers. IMPORT ANT Do not over-tighten the retaining ring.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-1 1 Rosemount 2088 and 2090 Rosemount 2090F The Rosemount 2090F sanitary pressu re transmitter is designed to be installed directly to a sanit ary fitting. T he transmitter is available with either a 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-12 Figure 3-9. T ransmitter Load Limitations Field Wiring All power to the transmitter is supplie d over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-13 Rosemount 2088 and 2090 Figure 3-10. Rosemount 2088 Smart Signal Wiring T erminals. FAILURE MODE AND SECURITY JUMPERS Failure Mode As part of normal operation, the Rosemount 2088/2090 Smart Pressure T ransmitter continuously monitors its own operation.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-14 With a meter inst alled The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transm itter housing and is labeled ALARM (See Figure 3-1 1).
Reference Manual 00809-0100-4690, Rev EA March 2007 3-15 Rosemount 2088 and 2090 NOTE If either the alarm or security jumper is dislodged or removed from its position the transmitter reverts to defaul.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-16 Disabling the Zero and Sp an Adjustment s After you rerange the transmitter usi ng the sp an and zero adjustments, you may wish to disable the adjustments to prevent further reranging.
Een belangrijk punt na aankoop van elk apparaat Emerson Process Management 2090 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Emerson Process Management 2090 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Emerson Process Management 2090 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Emerson Process Management 2090 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Emerson Process Management 2090 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Emerson Process Management 2090 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Emerson Process Management 2090 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Emerson Process Management 2090 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.