Gebruiksaanwijzing /service van het product 644H van de fabrikant Emerson Process Management
Ga naar pagina of 32
Quick Start Guide 00825-0100-4728, Rev BD May 2014 R osemount ® 644H and 644R Smar t T emperature T ransmitt ers.
May 2014 2 Quick Start Guide NO TICE This installation guide pr ovides basic guidelines f or the Rosemount 644. It does not pro vide instruc tions for detailed configuration, diagnostics, maintenance , serv ice , troubleshooting, or installation. R efe r to the 644 Re fere nce M anual (document n umber 00809-0100-4728) for more instruction.
Quick Start Guide 3 May 2014 Step 1: Configure (bench calib ration) The 644 commu nicates using the fiel d communicator (comm unication require s a loop resistance be tween 250 and 1100 ohms. Do no t operate when po wer is below 12 Vdc at the t ransmitter terminal) .
May 2014 4 Quick Start Guide Step 2: V erif y co nfiguration The tradit ional interface F ast Key sequences in Ta b l e 1 and Device Dashboard Fast Key Sequences in Ta b l e 2 may be us ed for transmitter con figuration and sta rtup.
Quick Start Guide 5 May 2014 T able 1. T raditional Interface F ast Ke y Sequences Function Fas t K ey s Function Fas t Key s Active Calibra tor 1, 2, 2, 1, 3 Open Sensor Hold off 1, 3, 5, 3 Alarm/Sat.
May 2014 6 Quick Start Guide Input/ve rif y Callendar V an-Duse n constants If sensor matching is being used with this combinat ion of a transmitter and sensor, verify the constants input. 1. At the Home screen, selec t 1 Devic e Setup , 3 Configuration , 2 Sensor C onfig , 1 Senso r 1, 3 Cal V an-Dusen .
Quick Start Guide 7 May 2014 Input/ve rif y Ca llend ar V an-D use n c onstants If sensor matching is bei ng used with this combin ation of a transmitter and sensor, verify the constants i nput. 1. From the Home scre en, s elect 2 Con figure , 2 Manual Setup , 1 Senso r .
May 2014 8 Quick Start Guide St ep 4: Mount the transmitter Mount the tra nsmitter at a h igh point in the conduit ru n to prevent moisture from draining into th e transmitter hous ing. T ypical c onnection head installation Head moun t transmitter with D IN plate st yle senso r 1.
Quick Start Guide 9 May 2014 T ypical univ ersal he ad installation Head mount transmitter with threaded sensor 1. Attach the thermowell to the pipe or process c ontainer wall. Install a nd tighten thermowells bef ore applyi ng process pressure . 2. Att ach necessary ex tension nipples and adapte rs to the th ermowell.
May 2014 10 Quick Start Guide Rail mount transmitte r and sensor 1. Attach the transmitter to a suitable rail or panel. 2. Att ach the thermowe ll to the pipe or process c ontainer wall. Install and tighten the thermowell, according to plan t standards, before applying pressure .
Quick Start Guide 11 May 2014 Rail mount transmitt er with thre aded sensor 1. Attach the transmitter to a suitable rail or panel. 2. Att ach the thermowe ll to the pipe or process container wall. Install and tighten the thermowe ll before applying pressure .
May 2014 12 Quick Start Guide Step 5: Wire and apply power Wire the transmitte r Wiring diagrams are located inside the terminal block co ver . Figure 4. Sensor Connections Diagr am Pow er the transm itte r 1. An ex ternal power supply is requi red to operate the transmit ter .
Quick Start Guide 13 May 2014 Ground the transmitter Ungrounded thermocouple, mV , and RTD/Ohm inputs Each process in stallation has di fferent requirements for ground ing. Use the grounding options recommended b y the faci lity for the specific sensor type, or begin with grounding option 1 (the most common).
May 2014 14 Quick Start Guide Option 3 1. Ground sensor wiring shield at the sensor , if possible. 2. In sure that the sensor wiring and signal wiring shields are electrically isolated from the trans mitte r housing . 3. D o not connect the signal wiring shield to the sensor wiring shield.
Quick Start Guide 15 May 2014 St ep 6: Perform a loop test The Loop Test co mmand verifies transmit ter output, loop i ntegrity, and operat ion of any recorders or similar de vices installe d in the loop. T radition al inte r fac e Initiate a loop t est 1.
May 2014 16 Quick Start Guide Produc t Cer tifications Appro v ed Manuf acturing L ocations Ro semoun t Inc. - Ch anh ass en, Mi nneso ta, U SA Ro semount T emperature GmbH – Ge rmany Emerson Proces.
Quick Start Guide 17 May 2014 Special C onditions for Safe Us e (X): 1. When no en closure option is s elected, the Model 644 T emperature T ransmitter shall be installed in a final enc losure meeting type of protection IP20 and meeting the requirements of AN SI/ISA 61010-1 and ANSI/ISA 60079-0 2.
May 2014 18 Quick Start Guide I1 AT E X I n t r i n s i c S a f e t y Certificate : Baseef a03A TE X0499X [Headmount Fieldbus/Pro fibus]; BAS00A TE X1033X [Railmount HART]; Ba seefa12A TEX0 101X [Head.
Quick Start Guide 19 May 2014 Inte rnation al E7 IECEx Flame proof Certificate: IE CEx FMG 12.0022X Standar ds Used: IE C 60079-0:2011, IEC 60079-1:2007-04, IEC 60079-31:2008 Marking s: Ex d IIC T6….
May 2014 20 Quick Start Guide NK IECEx Du st Certificate : IECEx FMG 12.0022X Standards U sed: IE C 600 79-0:2011, IEC 60079-1:2007-04, IE C 60079-31:2008 Markings : Ex d IIC T6…T1 Gb, T6(-50 °C .
Quick Start Guide 21 May 2014 China E3 China Flameproo f Certificate: GYJ111385 Standar ds Used: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000 Markings: Ex d IIC T6 Special C onditions for Safe Us e (X): 1. T emperature Assembly using te mperature se nsor t ype 65, 68 , 75, 183, 185 are cer ti fi ed.
May 2014 22 Quick Start Guide I3 China Intrinsic Sa fety Certificate : GYJ111384X Standards U sed: GB3836.1-2000, GB3836.4-2000 Markings : Ex ia IIC T4/T5/T6 Special Conditions for Sa fe Use (X): 1. The ambient te mperature range is: When Options do not se lec t Enhance P erformance When Options select Enhanced Performanc e 2.
Quick Start Guide 23 May 2014 When Options select Enhanc ed Performance T erminals of pow er supply (+, -) T erminals of s ensor (1,2,3,4) 3. This product com plies t o the req uire ment s for FISC O field de vice s spec ified in IEC60079-27: 2008.
May 2014 24 Quick Start Guide N3 China T y pe n Certificate : GYJ101421 Standards U sed: GB3836.1-2000, GB3836.8-2003 Markings : Ex nA nL IIC T5/T6 Special C onditions for Safe Us e (X): 1.
Quick Start Guide 25 May 2014 Com bi nati o ns K1 combin ation of E1, I1, N1, NC, and ND K2 combi natio n of E 2 and I2 K5 combi natio n of E 5 and I5 K7 combin ation of E7, I7, N7, NG, and NK KA combina tion of K1 and K6 KB combina tion of K5 and K6 KC combi natio n of I5 and I 6 KD combin ation of E1, E5, K6, I1, I5, I6 Ta b l e s T able 3.
May 2014 26 Quick Start Guide Declar ation of Conformity.
Quick Start Guide 27 May 2014.
May 2014 28 Quick Start Guide.
Quick Start Guide 29 May 2014.
May 2014 30 Quick Start Guide.
Quick Start Guide 31 May 2014.
Rose mo unt In c. 8200 Mark et Boulev ard Chanha ssen , MN USA 55317 T (US) (8 00) 999-9307 T (Intnl) (952 ) 906-8888 F (952) 906-8889 Emerso n Process Management Asia Pacifi c Private Lim ited 1 Pandan Cr esce nt Singapor e 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743 Emerso n Process Management GmbH & Co.
Een belangrijk punt na aankoop van elk apparaat Emerson Process Management 644H (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Emerson Process Management 644H heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Emerson Process Management 644H vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Emerson Process Management 644H leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Emerson Process Management 644H krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Emerson Process Management 644H bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Emerson Process Management 644H kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Emerson Process Management 644H . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.