R-410A Models Service Manual 2010 HG-ServMan (4-10) SH15M30A SH20M30A Cool Only H a z a r d o u s D u t y R o o m A i r C o n d i t i o n e r.
T able Of Contents Important Safety Information ..................................................................................................................... 2-4 Introduction ....................................................................
IMPORT ANT SAFETY INFORMA TION The information contained in this manual is intended for use by a qualied service technician who is familiar with the safety procedures required for installation and repair , and who is equipped with the proper tools and test instruments required to service this product.
Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, • and sleeve on the room side of the air conditioning unit while cleaning.
PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specied amperage rating. • Connect to a properly grounded outlet only .
Serial Number Decade Manufactured L=0 C=3 F=6 J=9 A=1 D=4 G=7 B=2 E=5 H=8 A K A R 00001 Production Run Number Y ear Manufactured A=1 D=4 G=7 K=0 B=2 E=5 H=8 C=3 F=6 J=9 Product Line R = RAC Month Manu.
UL L i st ed f or u s e in Cla s s I, Division 2, G rou ps A, B, C an d D h a z a r do us lo c ati o ns . Ha za r dg ar d is sp eci c al ly d esi gne d to c ool l ivin g q uar te r s, st ora g e a .
SPEC IF IC A TIONS AND PERFORMANCE DA T A Coolin g P er forman ce Data EV APORA TOR AIR TEMP . DEG. F CONDENSER TEMPERA TURE DEG. F Discharge T emp Suction T emp Super Heat Sub- Cooling OPERA TING PRESSURES ELECTRICAL RA TINGS R-410A REF . V oltage BREAKER FUSE Discharge Air T emp.
ELECTRICAL D A T A ELECTRICAL REQUIR EME NTS ELECTRIC SHOCK HAZARD W ARNING T urn off electric power before service or installation. All el ec tri ca l conn e cti o ns an d wir in g MUS T be in st al le d by a qu al i ed e l e ct ri c ia n an d con for m to the National Electr ic al Code and all local co des which have jurisdic tion.
Permanent Split-Capacitor , totally enclosed fan motor to assure efcient operation even under adverse electrical conditions. Motor has a special stainless steel shaft to resist corrosion and a hermetically sealed overload for arc-free operation. High capacity compressor with internal hermetically sealed overload.
COMPONENT DEFINITIONS A. Mechanical components B. Electrical components C. Hermetic components Plenum assembly Diffuser with directional louvers used to direct the conditioned airow .
F AN MOTOR SWITCH, ON-OFF Line side SOLID ST A TE RELA Y Load side LED indicates contacts closed when lit F AN MOTOR A 230 volt single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A running capacitor is wired across the start and run terminals of the motor .
RANGE: Thermostat (Part No. 618-225-02) 60 ° F ( ± 2 ° ) to 90 ° F( ± 4 ° ) SENSING BULB LOCA TION THERMOST A T A cross ambient thermostat is used to maintain the desired comfort level. The thermostat reacts only to a change in temperature at the bulb location.
• R-410A pressure is approximately 60% higher than R-22 pressure. • R-410A cylinders must not be allowed to exceed 125 F , they may leak or rupture.
Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or efciency . Accordingly , the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged.
3. Install a process tube to sealed system. 4. Make necessary repairs to system. 5. Evacuate system to 200 microns or less. 6. Weigh in refrigerant with the proper quantity of R-410A refrigerant. 7. Start unit, and verify performance. 8. Crimp the process tube and solder the end shut.
Underchar ged R efrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
R estricted R efrigerant System T roubleshooting a restricted refrigerant system can be difcult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
Lock ed Rotor V olta ge (L.R.V .) T est Locked rotor voltage (L.R.V .) is the actual voltage available at the compressor under a stalled condition. Single Phase Connections Disconnect power from unit.
Many compressor failures are caused by the following conditions: 1. Improper air ow over the evaporator . 2. Overcharged refrigerant system causing liquid to be returned to the compressor . 3. Restricted refrigerant system. 4. Lack of lubrication. 5.
3. After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor . Be certain to have both suction and discharge process tubes open to atmosphere. 4. Carefully pour a small amount of oil from the suction stub of the defective compressor into a clean container .
R OUTINE MAINTENANCE AIR FIL TER Clean the unit air intake lter at least every 300 to 350 hours of operation. Clean the lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.
R OUTINE MAINTENANCE (Continued) Do not drill holes in the bottom of the drain pan or the underside of the unit. Not following this notice could result in damage to the unit or condensate water leaking inappropriately which could cause water damage to surrounding property .
ROOM AIR CONDITIONER UNIT PERFORMANCE TEST D A T A SHEET DA TE: _______________ MODEL:_______________ SERIAL:________________ YES NO IS THERE A FRIEDRICH SLEEVE INST ALLED? ____ ____ IS THERE A FRIEDR.
TROUBLESHOO TING Problem Possible Cause Possible Solution Possible Solution Possible Solution Possible Solution Possible Solution Unit does not run Power disconnected. Check power source. Branch circuit fuse blown or circuit breaker tripped. Replace fuse, reset breaker .
Problem Possible Cause Possible Solution Possible Solution Possible Solution Compressor attempts to start, or runs for short periods only . Cycles on overload. Compressor attempts to start before system pressures are equalized. Allow a minimum of 3 minutes to allow pressures to equalize before attempting to start.
Problem Possible Cause Possible Solution Possible Solution Possible Solution Possible Solution Fan motor does not run. Defective switch (On-Off) Check continuity across terminals 2 and 3. Fan capacitor open. T est with capacitor analyzer . Replace if bad.
ELECTR OMECHANICAL CONTR OL COOL ONL Y MODELS: SH15M30-A SH20M30-A 27.
Friedrich Air Conditioning Company P .O. Box 1540 San Antonio, TX 78295 210.357.4400 www .friedrich.com HAZARDGARD ® ROOM AIR CONDITIONERS LIMITED W ARRANTY LIMITED ONE YEAR P ARTS W ARRANTY 1.
FRIEDRICH AIR CONDITIONING CO . Post Ofce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · 877-599-5665 x 846 · F AX (210) 357-4490 Email: tac@friedrich.com www .friedrich.com Printed in the U.
.
HG-ServMan (4-10) FRIEDRICH AIR CONDITIONING CO . Post Ofce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4490 www .
Een belangrijk punt na aankoop van elk apparaat Friedrich R-410A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Friedrich R-410A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Friedrich R-410A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Friedrich R-410A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Friedrich R-410A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Friedrich R-410A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Friedrich R-410A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Friedrich R-410A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.