Gebruiksaanwijzing /service van het product DORFC-1 van de fabrikant AMABILIA
Ga naar pagina of 30
Manual 2100-518B Page 1 of 30 W ARNING: After ushing is complete, but prior to pump motor start-up, loosen the lar ge screw in the center of the pump motor(s) to allow air to escape.
Manual 2100-518B Page 2 of 30 CONTENTS Getting Other Informations and Publications ......... 3 General Information Flow Center Nomenclature ....................................... 4 Application Description .............................................
Manual 2100-518B Page 3 of 30 GettinG Other infOrma tiOn and Publica tiOns These publications can help you install the air conditioner or heat pump. Y ou can usually nd these at your local library or purchase them directly from the publisher . Be sure to consult current edition of each standard.
Manual 2100-518B Page 4 of 30 GeOthermal flOw centers nOmencla ture flOw center descriPtiOn The DORFC Series Flow Centers are a compact, easy to mount polystyrene cabinet that contains 3-way valves and pump(s) with connections for ushing, lling and pumping uids for geothermal closed loop systems.
Manual 2100-518B Page 5 of 30 Manual 2100-518A Page 5 of 30 0 10 20 30 40 50 60 70 0 5 10 15 20 25 30 35 Flow ( GPM) Head (Feet) FIGURE 1B PERFORMANCE MODEL DORFC-2 FLOW CENTER 0 5 10 15 20 25 30 35 0.
Manual 2100-518B Page 6 of 30 G F B D H MIS- 2658 11 .4 31 .5 5 .1 6 .7 12 .7 19 .1 A B C D E F G H I NCH ES 13 .5 10 .3 7 .5 12 .4 2 .0 2 .6 5 .0 4 .7 CM 34 .
Manual 2100-518B Page 7 of 30 nOtice The Flow Center must be mounted with the pump shaft in the horizontal position. In other words, it should always be mounted in a vertical position (not on its back or mounted to the ceiling).
Manual 2100-518B Page 8 of 30 OK HOR IZONT AL OK IM PE LLER S HAFT HOR IZONT AL IM PE LLER S HAFT MIS- 2659 NO IM PE LLER S HAFT CAN N OT BE VE RTIC AL fiGure 3 PumP hOrizOnt al aPPlica tiOns.
Manual 2100-518B Page 9 of 30 1/4" T AP CON S CR E WS MIS- 2660 1/4" LAG B OL TS DIRECT L Y I NTO S T UD fiGure 4 mOuntinG FIGURE 4A Studded W all Mounting FIGURE 4B Masonry W all Mounting.
Manual 2100-518B Page 10 of 30 The Flow Center features Double O-Ring ttings for installation exibility and ease of installation – maintaining a reliable connection. T able 1 illustrates the connection options available for Flow Centers. Pressure drop in piping systems should be calculated to ensure adequate ow through the unit.
Manual 2100-518B Page 1 1 of 30 1" swivel X double O-ring dOrfP1-s 1" copper sweat X double O-ring with 1/4" fPt Port & Pressure/t emperature t est Plugs dOrs1-s elbow , 1" hos.
Manual 2100-518B Page 12 of 30 mul tiPle unit tO sinGle lOOP cOnnectiOn In instances where multiple units are connected to a singular loop, our recommendation is to apply a ow center to each individual system with full-port balancing valves installed on each unit.
Manual 2100-518B Page 13 of 30 fiGure 5b flOw center cOnnectiOn tO Gt series mOdel NOTE: APPLY PETROLEUM JELLY TO O-RINGS TO PREVENT DAMAGE AND AID IN INSERTION WATER IN WATER OUT GOUND LOOP PIPE FROM.
Manual 2100-518B Page 14 of 30 fiGure 5c flOw center cOnnectiOn tO Qw series mOdel NOTE: Apply petroleum jelly to o-rings to prevent damage and aid in insertion MIS-2748 A FLEXIBLE HOSE for Model No.
Manual 2100-518B Page 15 of 30 GROUND FULL PORT BALL VALVE FOR BALANCING LOOP 4. All units must include P/T ports for flow rate measure and balancing. FIELD SUPPLIED MIS-2664 NOTES: 1. Piping is shown schematically. Actual pipe diameter and layout must be determined before installation.
Manual 2100-518B Page 16 of 30 Power wiring to the Flow Center should conform to all applicable codes. Figure 7 shows the required wiring between the geothermal heat pump and the ow center . Note : the ow center is only available in 208/230 V olt, 60 Hz, 1-phase.
Manual 2100-518B Page 17 of 30 L2 L1 3 PU SH 3 PU SH T er mi na l Blo ck FLOW CENT ER CO NN ECTI ON FLOW CENT ER ELECTRIC AL ENTRA NCE MIS- 2665 38 Circui t B rea k ers R ed 37 Bl a ck 2 fiGure 7 elec.
Manual 2100-518B Page 18 of 30 All Flushing of earth loops should be performed using a 1.5 HP or lar ger pump (as specied by IGSHP A). Flushing can be accomplished using three different methods. The rst ushing method applies a one-step installation of the loop, unit and inside piping.
Manual 2100-518B Page 19 of 30 SU PP LY RET URN MIS- 2661 flushinG & charGinG (cOntinued) fiGure 8 cOnnectinG flush cart tO flOw center.
Manual 2100-518B Page 20 of 30 MIS- 2662 FLUSH L OO P ON LY FLUSH L OO P& UN IT T OG ETH ER flushinG & charGinG (cOntinued) fiGures 9a & 9b flOw center V al Ve POsitiOninG.
Manual 2100-518B Page 21 of 30 FLUSH UN IT O NLY O PE RATI ON MIS- 2663 flushinG & charGinG (cOntinued) fiGures 9c & 9d flOw center V al Ve POsitiOninG.
Manual 2100-518B Page 22 of 30 flushinG & fillinG earth lOOP and unit(s) tOGether All air and debris must be removed from the earth loop piping system before operation. Flush the loop with a high volume of water at a high velocity (2 fps in all piping in accordance with IGSHP A guidelines).
Manual 2100-518B Page 23 of 30 flushinG unit Onl y (alsO used when rePlacinG unit , cOaXial cOil, hOse kit Or PumP) 1. Connect unit to ow center . 2. Rotate 3-way valve to position shown in Figure 9C. 3. Remove access port caps and plugs and connect either ush cart or Bard DORGHMT tting (service only - not intended for primary ush).
Manual 2100-518B Page 24 of 30 1. Check to make sure the loop and unit isolation valves are completely open and the ush ports are closed and sealed (see Figure 9D).
Manual 2100-518B Page 25 of 30 10 120 110 100 90 80 70 60 50 40 30 20 0 Retaining cap, hand tighten only Pete's test plug Test plug cap Barbed 90° adapter MIS-2622 A NOTE: Slide retaining cap back to expose double o-rings.
Manual 2100-518B Page 26 of 30 t able 3b Gt series cOil Pressure drOP t able 3c Qw series cOil Pressure drOP model GPm Gtc36s1 Gtc48s1 Gtc60s1 Psid ft. hd. Psid ft. hd. Psid ft. hd. 3 0.1 0.23 4 0.5 1.15 0.9 2.08 5 1.2 2.77 1.4 3.23 6 1.7 3.92 2.3 5.31 7 2.
Manual 2100-518B Page 27 of 30 Problem Possible causes checks & corrections W ater Drips Out Condensation Insulate piping, check for insulation gaps. W ater Leak Inspect/tighten ttings. Low Flow / No Flow Power Loss Check power supply from the heat pump.
Manual 2100-518B Page 28 of 30 Selection of antifreeze solutions for ground loop applications requires consideration of many important factors, which may have long-term implications in regards to performance and system component life. Each area of concern leads to a different antifreeze solution.
Manual 2100-518B Page 29 of 30 Propylene Glycol – Non-toxic, non-corrosive, expensive, hard to handle when cold, poorest heat transfer , has formed “slime-type” coatings inside system piping. Propylene Glycol is acceptable in systems anticipating loop temperatures no colder than 40°F (4.
Manual 2100-518B Page 30 of 30 antifreeze Verifica tiOn Both Glycol and Alcohol based antifreeze solutions can be veried to the specic percentage of volume within the ground loop system.
Een belangrijk punt na aankoop van elk apparaat AMABILIA DORFC-1 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen AMABILIA DORFC-1 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens AMABILIA DORFC-1 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding AMABILIA DORFC-1 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over AMABILIA DORFC-1 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van AMABILIA DORFC-1 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de AMABILIA DORFC-1 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met AMABILIA DORFC-1 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.