Gebruiksaanwijzing /service van het product 25/30kW van de fabrikant Generac
Ga naar pagina of 136
This manual should remain with the unit. 1.6L 25/30kW Models EP A Cer tified Owner's Manual Stationar y Emergency Generator Cover191 Re v . A 04/10 Part No.
SECTION P AGE INTRODUCTION ........................................................... 1-1 Read this Manual Thoroughly ....................................................... 1-1 Operation and Maintenance ..............................................
INTRODUCTION Thank you for purchasing this model of the stationar y emergency generator product line. Ever y effor t was expended to make sure that the infor mation and instr uctions in this manual were both accurate and current at the time the manual was written.
SAFETY RULES Study these SAFETY RULES carefully before installing, operating or ser vicing this equipment. Become familiar with this Owner ’s Manual and with the unit. The generator can operate safely , effi- ciently and reliably only if it is properly installed, operated and maintained.
If personnel must stand on metal or concrete while installing, • operating, ser vicing, adjusting or repairing this equipment, place insulative mats over a dr y wooden platform.
IDENTIFICA TION RECORD DA T A L ABEL Ever y generator set has a DA T A L ABEL that contains impor tant information per tinent to the generator . The data label, which can be found attached to the gene.
EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur rent Stationar y Emergency Generator . It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units.
ENGINE PROTECTIVE DEVICES The Stationar y Emergency Generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant temperature, oil pressure or rpm.
FUEL SYSTEM FUEL REQUIREMENTS The Stationar y Emergency Generator may be equipped with one of the following fuel systems: • Natural gas fuel system • Propane vapor (LPV) fuel system Recommended fuels should have a Btu content of at least 1,000 Btu's per cubic foot for natural gas; or at least 2,520 Btu's per cubic foot for LP gas.
SPECIFICA TIONS ST ANDB Y EMERGENC Y GENERA TOR T ype...................................................................... Synchronous Rotor Insulation ............................................................. Class H Stator Insulation ..........
WEA THER AND MAINTENANCE KITS T o keep the generator r unning at its peak, the following kits are offered: • Cold Weather Kit ~ Recommended for climates with temperatures below 32° F . • Extreme Cold Weather Kit ~ Recommended Block Heater Kit for protection in tempera- tures below 32° F .
AL TERNA TOR AC LEAD CONNECTIONS The electrical wires in the unit’s AC connection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. The voltage and phase are described on the generator data label.
Figure 7.4 — Stator P ower Winding Connections - 3-phase, 120/208V (6 Lead) E3 E2 00 (NEUTRAL) INTERNAL CONNECTIONS E1 L-L L-N S1 S1 S4 S4 S6 S6 S3 S3 S5 S5 S2 S2 Figure 7.5 — Stator P ower Winding Connections - 3-phase, 120/208V (12 Lead) E3 E2 E1 L-L L-N S7 S1 S10 S4 S12 S6 S9 S3 S5 S11 S2 S8 Figure 7.
CONTROL P ANEL INTERF ACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO , the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source voltage drops below a preset level or during the normal exercise cycle.
8-2 CntrlNexus001 Rev . E 12/11 Control P anel ACTIVA TION CHART CHOOSE LANGUAGE TROUBLESHOOTING Display Reads: Use ARROW keys to scroll to desired lan- guage. Press ENTER to select. If the wrong language is chosen, it can be changed later using the “edit” menu.
INST ALLA TION ASSIST ANT Interconnect System Self T est Feature (follow the on-screen prompts). Upon power up, this controller will go through a system self test which will check for the presence of utility voltage on the DC circuits.
SEQUENCE OF AUTOMA TIC OPERA TION Initial Conditions: Generator in Auto ready to r un, load being sup- plied by the Utility Source through the transfer switch. 1. When the utility voltage fails (falls below 60% of nominal), a 10-30 second (programmable) “line interr upt” delay timer is star ted.
CHECK ENGINE MESSAGE The control system has detected an emissions related fault. This fault cannot be cleared using the control panel inter face. The unit will continue to operate in automatic mode.
OVERVOL T AGE AL ARM If the generator voltage rises above 110% for >3 seconds, an alarm will be issued. If the generator voltage rises above 130% for >0.2 seconds, an alarm will be issued. INTERNAL F AILURE SHUTDOWN ALARM Any internal failure that can be detected such as cor r upted firmware will cause this shutdown alar m.
8-7 Control P anel ACTIV A TION RUN LOG ALARM LOG HISTOR Y STA TUS COMMAND S TAT E VERSIONS DISPLA Y GENERA TOR FREQUENCY ENGINE HOURS ENGINE RPM BA TTERY VO LTA G E DEBUG INPUTS OUTPUTS DISPLA YS EDIT LANGU AGE TIME/DA TE EXERCISE TIME/SPEED ESC Press the “ESCAPE” key to jump back up through the menu levels.
ST A TIONARY EMERGENCY GENERA TOR CONTROL AND OPERA TION Refer to the appropriate control panel operator’s manual for this unit. OPERA TING UNIT WITH MANUAL TRANSFER SWITCH If the Stationar y Emergency Generator was installed in conjunction with a transfer switch capable of manual operation only , the fol- lowing procedure applies.
GENERAL MAINTENANCE Before working on the Stationary Emergency Generator , ensure the following: The AUTO/OFF/MANUAL switch is in the OFF position. • The control panel fuse has been removed from the control • box. The 120VAC supply to the battery charger is switched OFF .
ENGINE COOLANT Check coolant level in coolant recover y bottle. See the Specifications and Ser vice Schedule sections. Add recommended coolant mixture as necessar y . • P eriodically remove radiator pressure cap (only when engine • has cooled down) to make sure the coolant recover y system is functioning properly .
Figure 10.3 – Engine Air Filter AIR FIL TER SP ARK PLUGS Reset the spark plug gap or replace the spark plugs as neces- sar y . 1. Clean the area around the base of the spark plugs to keep dir t and debris out of the engine. Clean by scraping or washing using a wire br ush and commercial solvent.
SERVICE SCHEDULE System / Component Frequency Procedure Weekly - W Monthly - M Y early - Y Inspect Change Clean Fuel Fuel Lines & Connections M X Lubrication Oil Level M X* Oil Y X** Oil Filter Y .
T roubleshooting TROUBLESHOOTING GUIDE PROBLEM CAUSE CORRECTION Engine won’t crank. 1. Control panel 7.5 amp fuse blown. 1. R eplace fuse.* 2. Loose or corroded or defective 2. Tighten, clean or replace batter y cables. batter y cables as necessar y .
13-1 EmsnWrnty001 Rev . D 09/11 United States Environmental Protection Agency W arranty Statement (Stationary Emergency Spark -Ignited Generators) W arranty Rights, Obligations and Coverage The United States Environmental Protection Agency (EP A) and Generac Power Systems, Inc.
13-2 EmsnWrnty001 Rev . D 09/11 United States Environmental Protection Agency Compliance Requirements (Stationary Emergency Spark -Ignited Generators) Purchaser's/Owner's Recordkeeping Responsibilities The United States Environmental Protection Agency (EP A) and Generac Power Systems, Inc.
Notes.
.
1 0G4827 1 ASSY RTR 104 KD1 HI EFF ( 18KW) 0G2927 1 RTR- 102-20.0AD1 CP L (2006) (20KW) 0G2827 1 ASS Y RTR 25KW 2P ( 2006) (25KW) 0G3451 1 ASS Y RTR 30KW 2P 10"(2006) 2 0G0 820A 1 HOUS ING BLOWER LG PILOT 3 0G4452 1 BLOW ER HOUSING S CREEN 4 02074 6 4 S CREW PPHM M5- 0.
.
.
.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-1182-J Page 4 of 8 DATE: 12/16/11 ITEM PART# QTY. DESCR I PTION 1 0H6795 1 CONBOX BACK/SIDES C1 CPL 2 0H6796 1 CONBOX TOP C1 CPL (4)3 0H67330ST0R 1 BRACKET GIMBAL CONTROL PNL RAW 4 0H7115 2 KNOB M6-1.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-1182-J Page 5 of 8 DATE: 12/16/11 ITEM PART# QTY. DESCR I PTION M 022129 6 WASHER LOCK M 8-5/16 N 022145 4 WASHER FLAT 5/16-M 8 ZINC P 045771 2 NUT HEX M8-1 .25 G8 CLEAR ZINC R 058306 2 SCRE W SHC M8- 1.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-1182-J Page 6 of 8 DATE: 12/16/11 ITEM PART# QTY. DESCR I PTION UL CIRCUIT BRE AKER (CC 2P) A 0H4745 REF CB 0.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-1182-J Page 7 of 8 DATE: 12/16/11 ITEM PART# QTY. DESCR I PTION UL CIRCUIT BRE AKER (BQ 2P) A 0D5543 REF CB 0.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-1182-J Page 8 of 8 DATE: 12/16/11 THIS PAGE LEFT INTENTIONALLY BLANK.
.
1 0G3418 1 RADIATOR SUP PORT LH SIDE 1.6L 2 0G3421 1 VENTURI 1. 6L 3 0G3419 1 RADIATOR SUP PORT RH SIDE 1.6L 4 0E9837B 1 RA DIATOR 1.6L CHY 5 0G3553 1 FAN COOL 450MM DIA 7 BLADE 6 0 E3257 2 S CREW HWHTF M6 -1.0 X 16 7 0G4080 1 HOSE LOWER RADIATOR 1.6L 8 099502 6 CLAMP HOSE #24 B1.
.
EXPLODED VIEW: MO UNTING BASE 1.6L DRAWING #: 0G3531 GROUP C APPLICABLE TO: REVISION: H-5975-B Page 2 of 2 DATE: 2/5/10 ITEM PART# QTY. DESCR I PTION 1 0G3343 1 MOUNTING BASE 1 .6L 2007 C1 2 027 482 1 WASHER SHAKEPROOF EXT 5/16 STL 3 070 936 2 DAMPENER VIBRATION 4 070936C 2 VIB.
.
1 0F3408C 1 BATTE RY TRAY, C1 & C2 2 0F3411 1 STRAP BATTERY RETAINMENT 3 02550 7 1 WASHER SHAKEPR OO F EXT 7/16 STL 4 05998 0 1 SCREW HHC M10-1.5 X 25 G10.
.
EXPLODED VIEW: E NGINE COMMON PARTS 1.6L DRAWING #: 0H7219 GROUP D APPLICABLE TO: REVISION: H-8414-C Page 2 of 2 DATE: 3/1/11 ITEM PART# QTY. DESCR I PTION 1 0H1734 R EF ENGINE GENERAC 1.6L G11 CERT 2 0G0834A 1 ENGINE PLATE 1 .6L 6MM (TO BE USED W ITH PLATE SPACER P/N 0G2070A.
.
EXPLODED VIEW: FUE LSYS NG/LPV 1.6L CPL DRAWING #: 0H6671 GROUP E APPLICABLE TO: REVISION: H-9610-B Page 2 of 2 DATE: 9/9/11 ITEM PART# QTY. DESCR I PTION 1 037 561 1 NUT W ING 1/4-20 NYL K 2 0A 5547 .
.
EXPLODED VIEW: E V ENCLOSURE C1 CPL DRAWING #: 0G3534 GROUP F ITEM PART# QT Y. DESCRIPTION REVISION: -A- Page 2 of 2 DATE: 11/14/11 (2) 1 0G33370AL0R 1 ROOF 1.
.
1 0F7 366 1 MUFFLER C1 2 0F7 647 1 MUFFLER SADDLE 3 0F8 095 1 PIPE EX HAUST OUTLET 4 0G3576 1 EXHAUS T PIPE LOWER 1.6L 5 0E3257 4 SCREW HW HTF M6-1.0 X 1 6 6 0F7 644 2 MUFFLER STRAP 7 0C611 9 1 BOLT U 5 /16- 18 X 2-1/4 8 036434 3 BO LT U 5/16-18 X 2.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
BackPg001 Re v . A 04/07.
This manual should remain with the unit. 1.6L 25/30kW Models EP A Cer tified Owner's Manual Stationar y Emergency Generator Cover191 Re v . A 04/10 P ar t No .
SECTION P AGE INTRODUCTION ........................................................... 1-1 Read this Manual Thoroughly ....................................................... 1-1 Operation and Maintenance ..............................................
INTRODUCTION Thank you for purchasing this model of the stationar y emergency generator product line. Ever y effor t was expended to make sure that the infor mation and instr uctions in this manual were both accurate and current at the time the manual was written.
SAFETY RULES Study these SAFETY RULES carefully before installing, operating or ser vicing this equipment. Become familiar with this Owner ’s Manual and with the unit. The generator can operate safely , effi- ciently and reliably only if it is properly installed, operated and maintained.
If personnel must stand on metal or concrete while installing, • operating, ser vicing, adjusting or repairing this equipment, place insulative mats over a dr y wooden platform.
IDENTIFICA TION RECORD DA T A L ABEL Ever y generator set has a DA T A L ABEL that contains impor tant information per tinent to the generator . The data label, which can be found attached to the gene.
EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur rent Stationar y Emergency Generator . It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units.
ENGINE PROTECTIVE DEVICES The Stationar y Emergency Generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant temperature, oil pressure or rpm.
FUEL SYSTEM FUEL REQUIREMENTS The Stationar y Emergency Generator may be equipped with one of the following fuel systems: • Natural gas fuel system • Propane vapor (LPV) fuel system Recommended fuels should have a Btu content of at least 1,000 Btu's per cubic foot for natural gas; or at least 2,520 Btu's per cubic foot for LP gas.
SPECIFICA TIONS ST ANDB Y EMERGENC Y GENERA TOR T ype...................................................................... Synchronous Rotor Insulation ............................................................. Class H Stator Insulation ..........
WEA THER AND MAINTENANCE KITS T o keep the generator r unning at its peak, the following kits are offered: • Cold Weather Kit ~ Recommended for climates with temperatures below 32° F . • Extreme Cold Weather Kit ~ Recommended Block Heater Kit for protection in tempera- tures below 32° F .
AL TERNA TOR AC LEAD CONNECTIONS The electrical wires in the unit’s AC connection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. The voltage and phase are described on the generator data label.
Figure 7.4 — Stator P ower Winding Connections - 3-phase, 120/208V (6 Lead) E3 E2 00 (NEUTRAL) INTERNAL CONNECTIONS E1 L-L L-N S1 S1 S4 S4 S6 S6 S3 S3 S5 S5 S2 S2 Figure 7.5 — Stator P ower Winding Connections - 3-phase, 120/208V (12 Lead) E3 E2 E1 L-L L-N S7 S1 S10 S4 S12 S6 S9 S3 S5 S11 S2 S8 Figure 7.
CONTROL P ANEL INTERF ACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO , the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source voltage drops below a preset level or during the normal exercise cycle.
8-2 CntrlNexus001 Rev . E 12/11 Control P anel ACTIVA TION CHART CHOOSE LANGUAGE TROUBLESHOOTING Display Reads: Use ARROW keys to scroll to desired lan- guage. Press ENTER to select. If the wrong language is chosen, it can be changed later using the “edit” menu.
INST ALLA TION ASSIST ANT Interconnect System Self T est Feature (follow the on-screen prompts). Upon power up, this controller will go through a system self test which will check for the presence of utility voltage on the DC circuits.
SEQUENCE OF AUTOMA TIC OPERA TION Initial Conditions: Generator in Auto ready to r un, load being sup- plied by the Utility Source through the transfer switch. 1. When the utility voltage fails (falls below 60% of nominal), a 10-30 second (programmable) “line interr upt” delay timer is star ted.
CHECK ENGINE MESSAGE The control system has detected an emissions related fault. This fault cannot be cleared using the control panel inter face. The unit will continue to operate in automatic mode.
OVERVOL T AGE AL ARM If the generator voltage rises above 110% for >3 seconds, an alarm will be issued. If the generator voltage rises above 130% for >0.2 seconds, an alarm will be issued. INTERNAL F AILURE SHUTDOWN ALARM Any internal failure that can be detected such as cor r upted firmware will cause this shutdown alar m.
8-7 Control P anel ACTIV A TION RUN LOG ALARM LOG HISTOR Y STA TUS COMMAND S TAT E VERSIONS DISPLA Y GENERA TOR FREQUENCY ENGINE HOURS ENGINE RPM BA TTERY VO LTA G E DEBUG INPUTS OUTPUTS DISPLA YS EDIT LANGU AGE TIME/DA TE EXERCISE TIME/SPEED ESC Press the “ESCAPE” key to jump back up through the menu levels.
ST A TIONARY EMERGENCY GENERA TOR CONTROL AND OPERA TION Refer to the appropriate control panel operator’s manual for this unit. OPERA TING UNIT WITH MANUAL TRANSFER SWITCH If the Stationar y Emergency Generator was installed in conjunction with a transfer switch capable of manual operation only , the fol- lowing procedure applies.
GENERAL MAINTENANCE Before working on the Stationary Emergency Generator , ensure the following: The AUTO/OFF/MANUAL switch is in the OFF position. • The control panel fuse has been removed from the control • box. The 120VAC supply to the battery charger is switched OFF .
ENGINE COOLANT Check coolant level in coolant recover y bottle. See the Specifications and Ser vice Schedule sections. Add recommended coolant mixture as necessar y . • P eriodically remove radiator pressure cap (only when engine • has cooled down) to make sure the coolant recover y system is functioning properly .
Figure 10.3 – Engine Air Filter AIR FIL TER SP ARK PLUGS Reset the spark plug gap or replace the spark plugs as neces- sar y . 1. Clean the area around the base of the spark plugs to keep dir t and debris out of the engine. Clean by scraping or washing using a wire br ush and commercial solvent.
SERVICE SCHEDULE System / Component Frequency Procedure Weekly - W Monthly - M Y early - Y Inspect Change Clean Fuel Fuel Lines & Connections M X Lubrication Oil Level M X* Oil Y X** Oil Filter Y .
T roubleshooting TROUBLESHOOTING GUIDE PROBLEM CAUSE CORRECTION Engine won’t crank. 1. Control panel 7.5 amp fuse blown. 1. R eplace fuse.* 2. Loose or corroded or defective 2. Tighten, clean or replace batter y cables. batter y cables as necessar y .
13-1 EmsnWrnty001 Rev . D 09/11 United States Environmental Protection Agency W arranty Statement (Stationary Emergency Spark -Ignited Generators) W arranty Rights, Obligations and Coverage The United States Environmental Protection Agency (EP A) and Generac Power Systems, Inc.
13-2 EmsnWrnty001 Rev . D 09/11 United States Environmental Protection Agency Compliance Requirements (Stationary Emergency Spark -Ignited Generators) Purchaser's/Owner's Recordkeeping Responsibilities The United States Environmental Protection Agency (EP A) and Generac Power Systems, Inc.
Notes.
.
1 0G 4 827 1 A SSY RT R 10 4 K D1 H I EF F ( 1 8KW ) 0G 2 927 1 R T R- 1 02 - 20. 0A D 1 C PL ( 20 06 ) (2 0K W ) 0G 2 827 1 A SS Y RT R 25 K W 2 P ( 2006 ) ( 25 K W) 0G 3 451 1 A SS Y RT R 30 K W 2 P 10" ( 20 06 ) 2 0G 0 820 A 1 H O U SI N G BL OWE R L G PIL O T 3 0G 4 452 1 BLO WER HOUSI N G S CR E E N 4 02074 6 4 SC REW PPH M M 5-0 .
.
.
.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-6101-L Page 4 of 8 DATE: 8/12/13 ITEM PART# QTY. DESCR I PTION 1 0H6795 1 CONBOX BACK/SIDES C1 CPL 2 0H6796 1 CONBOX TOP C1 CPL (4)3 0H67330ST0R 1 BRACKET GIMBAL CONTROL PNL RAW 4 0H7115 2 KNOB M6-1.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-6101-L Page 5 of 8 DATE: 8/12/13 ITEM PART# QTY. DESCR I PTION M 022129 6 WASHER LOCK M 8-5/16 N 022145 4 WASHER FLAT 5/16-M 8 ZINC P 045771 2 NUT HEX M8-1 .25 G8 CLEAR ZINC R 058306 2 SCRE W SHC M8- 1.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-6101-L Page 6 of 8 DATE: 8/12/13 ITEM PART# QTY. DESCR I PTION UL CIRCUIT BRE AKER (CC 2P) A 0H4745 REF CB 01.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-6101-L Page 7 of 8 DATE: 8/12/13 ITEM PART# QTY. DESCR I PTION UL CIRCUIT BRE AKER (BQ 2P) A 0D5543 REF CB 00.
EXPLODED VIEW: CO NNECTION BOX C1 CPL DRAWING #: 0H7234 GROUP A APPLICABLE TO: REVISION: J-6101-L Page 8 of 8 DATE: 8/12/13 ITEM PART# QTY. DESCR I PTION G 0J 78230 AS0R 1 SHIELD CB HANDLE CONBOX H 029289 1 TAPE ELEC 1/2 FOAM J 036261 4 RIVET POP .125 X .
.
1 0G3418 1 RADIATOR SUP PORT LH SIDE 1.6L 2 0G3421 1 VENTURI 1. 6L 3 0G3419 1 RADIATOR SUP PORT RH SIDE 1.6L 4 0E9837B 1 RA DIATOR 1.6L CHY 5 0G3553 1 FAN COOL 450MM DIA 7 BLADE 6 0 E3257 2 S CREW HWHTF M6 -1.0 X 16 7 0G4080 1 HOSE LOWER RADIATOR 1.6L 8 099502 6 CLAMP HOSE #24 B1.
.
EXPLODED VIEW: MO UNTING BASE 1.6L DRAWING #: 0G3531 GROUP C APPLICABLE TO: REVISION: H-5975-B Page 2 of 2 DATE: 2/5/10 ITEM PART# QTY. DESCR I PTION 1 0G3343 1 MOUNTING BASE 1 .6L 2007 C1 2 027 482 1 WASHER SHAKEPROOF EXT 5/16 STL 3 070 936 2 DAMPENER VIBRATION 4 070936C 2 VIB.
.
1 0F3408C 1 BATTE RY TRAY, C1 & C2 2 0F3411 1 STRAP BATTERY RETAINMENT 3 02550 7 1 WASHER SHAKEPR OO F EXT 7/16 STL 4 05998 0 1 SCREW HHC M10-1.5 X 25 G10.
.
EXPLODED VIEW: E NGINE COMMON PARTS 1.6L DRAWING #: 0H7219 GROUP D APPLICABLE TO: REVISION: H-8414-C Page 2 of 2 DATE: 3/1/11 ITEM PART# QTY. DESCR I PTION 1 0H1734 R EF ENGINE GENERAC 1.6L G11 CERT 2 0G0834A 1 ENGINE PLATE 1 .6L 6MM (TO BE USED W ITH PLATE SPACER P/N 0G2070A.
.
EXPLODED VIEW: FUE LSYS NG/LPV 1.6L CPL DRAWING #: 0H6671 GROUP E APPLICABLE TO: REVISION: -A- Page 2 of 2 DATE: 1/21/10 ITEM PART# QTY. DESCR I PTION 1 037 561 1 NUT W ING 1/4-20 NYL K 2 0A 5547 1 COVER AIR CLEANER 3 062 522 1 STUD TH 1/4-20 X 3 G2 ZNC FULL 4 022 127 1 NUT HEX 1/4-20 STEEL 5 059402 1 FILTE R ELEMENT 6 091 526 4 SCREW PPHM M5-0.
.
EXPLODED VIEW: E V ENCLOSURE C1 CPL DRAWING #: 0G3534 GROUP F ITEM PART# QT Y. DESCRIPTION REVISION: J-1720-K Page 2 of 2 DATE: 3/23/12 (2) 1 0G33370AL0R 1 ROOF 1.
.
1 0F7 366 1 MUFFLER C1 2 0F7 647 1 MUFFLER SADDLE 3 0F8 095 1 PIPE EX HAUST OUTLET 4 0G3576 1 EXHAUS T PIPE LOWER 1.6L 5 0E3257 4 SCREW HW HTF M6-1.0 X 1 6 6 0F7 644 2 MUFFLER STRAP 7 0C611 9 1 BOLT U 5 /16- 18 X 2-1/4 8 036434 3 BO LT U 5/16-18 X 2.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
BackPg001 Re v . A 04/07.
Een belangrijk punt na aankoop van elk apparaat Generac 25/30kW (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Generac 25/30kW heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Generac 25/30kW vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Generac 25/30kW leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Generac 25/30kW krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Generac 25/30kW bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Generac 25/30kW kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Generac 25/30kW . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.