GSZ/VSZ 13 SEER S plit System Heat Pump s • Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WA RNI NG WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 GSZ/VSZ13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. Select GSZ13 models are available in 208/230 and 460 volt 3-phase applications. These models use R-410A refrigerant.
PRODUCT DESIGN 5 Mo d el D i m en si o n s - W x D x H G / V SZ 130181A * 26 x 26 x 32 ¼ G / V S Z 130241A * 26 x 26 x 32 ¼ G / V S Z 130241B* 26 x 26 x 32 ½ G / V SZ 130301A * 26 x 26 x 32 ¼ G / .
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
9 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L : G /V S Z 130181A * / A R * F 182416 ** EXPA ND ED PER FOR M ANC E D ATA COOL I NG O PE RA T I ON O utdoor Am bien t Te m pe r ature 65 75 85 95 1.
10 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L: G /V S Z 130181A * / A R * F 182416* * EXPAN DED PER FORM AN CE DA T A COOL I NG OP E RA T I ON O utdoor Am bi e nt Te m pe r a tur e 65 75 85 95.
11 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L: G /V S Z 130241A * / A R* F 182416** EX PANDED P ERF O RM ANCE DAT A C O O L IN G O P E R A T IO N O utdoo r Am bi e nt Te m pe r at ur e 65 75 8.
12 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L : G /VSZ 13024 1A * / A R * F 1 82416 * * EX PAN DE D PERF OR M ANCE D AT A COOL I NG OP E RA T I ON O utdoor Am bi e nt Te m per a ture 65 75 85 .
13 COOLING PERFORMANCE DA T A EXPAN DED PE RFORM AN CE DATA MODE L : G/ V S Z130241B*/ AR*F18 2416* * C OOLI NG OPE RA TI ON O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W e t B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 22 .
14 COOLING PERFORMANCE DA T A G/VSZ130241B* EXPAN DED PE RFORM AN CE DATA MODE L : G/ V S Z 130241B*/ AR*F18 2416* * C OOLI NG OP E RA T I ON O ut door Am bie nt Te m pe r atur e 6 5 75 8 5 9 5 105 11 5 E nte r ing Indoor W e t B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 23.
15 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L : G /V S Z 1303 01A * / A R * F 30 301* * E XPA NDED P E RF ORM AN CE DA T A COOL I NG OP ER A TI ON O utd o or Am bie nt T e m p e r atur e 65 75.
16 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L : G /V S Z 13030 1A * / A R * F 303 01* * EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OPE RA TI ON O utdoor Am bi e nt Te m pe r ature 65 75 85 9.
17 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L : G /V S Z130361A * / A R * F 36 42 16 * * EX PANDED P ERF O RM ANCE DAT A C OOL I N G OPE R ATIO N O utdoor Am bi e nt Te m pe r a tur e 65 75 85.
18 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L: G / VSZ130361A * / A R * F 3 64216 * * EXPA NDED PERFOR M AN CE DA T A C OOL IN G OP E R AT ION O utd oor Am bi e n t Te m pe r atur e 65 75 85 9.
19 COOLING PERFORMANCE DA T A G/VSZ130361B* EXPAN DED PE RFORM AN CE DATA M ODEL: G/ V S Z 1303 61B* / AR*F 364216 * * C OOLI NG OPE RA TI ON O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W et B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 34.
20 COOLING PERFORMANCE DA T A G/VSZ130361B* EXPAN DED PE RFORM AN CE DATA M ODEL: G/ V S Z 1303 61B* / AR*F 364216 * * C OOLI NG OP ER ATION O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W et B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 35.
21 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130363A* / AR*F 3642 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 33.
22 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130363A* / AR*F 3642 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 34.
23 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L : G /V SZ 130421A * / A R * F 36421* * EX PANDED PERF ORM ANCE DATA COOL I NG OP ERA T I ON O utdoo r Am bie nt Te m pe r ature 65 75 85 95 105 11.
24 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L : G /VSZ 130421 A * / A R * F 36421* * EXP ANDED PERF ORM ANCE DAT A CO OLI N G OPE RA T I ON O utdoo r Am bie nt Te m pe r atur e 65 7 5 85 95 10.
25 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /V S Z 130481A * /A R * F 48601** EXPAND ED PER F O RM ANC E DATA COOL I NG OP ERA T I ON O utdoor Am bi e nt Te m pe rat ur e 65 75 85 95 105.
26 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /V S Z 130481A * /A R * F 48601* * EXPAND ED PER F O RM ANC E DATA COOL I NG OP ERA T I ON O utdoor Am bi e nt Te m pe r at ur e 65 75 85 95 1.
27 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130483A* / AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.
28 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130483A* / AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.
29 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130484A* / AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.
30 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130484A* / AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.
31 COOLING PERFORMANCE DA T A G/VSZ130601A* M O D E L : G /V S Z 130601A * / A R* F 48601** EXPAN DED PER F O RM AN CE DA T A C OOL I N G OP E R ATI ON O utdoor Am bi e nt Te m pe rat ur e 65 75 85 95.
32 COOLING PERFORMANCE DA T A G/VSZ130601A* EX PANDED P ERF O RM ANCE DAT A C OOL I N G OP E R AT I ON M ODEL: GS Z 130601A * / AR*F 48601** O utdoor Am bi e n t Te m pe rat ur e 65 75 85 95 105 115 E nt e r i ng Indoor Wet B ulb Te m pe rature ID B A ir flo w 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 7 1 59 63 67 71 M Bh 55.
33 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130603A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.
34 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130603A* /AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.
35 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130604A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.
36 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130604A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.
37 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p.+ f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on.
38 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p. + f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on.
39 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p. + f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on.
40 SPLIT SYSTEM HEA TING PERFORMANCE EXPA N DED PER FOR M A N CE DA T A M ODEL: GS Z 130483A* / A R*F486016 ** H E A T IN G OP E RAT IO N O utd oor Am bie nt Te m pe r atur e 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 - 5 - 10 M Bh 55.3 52.4 49.3 46.
41 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
HIGH VOL T AGE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLIN G THIS UNIT . MUL T IPL E POWER SO URCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJURY OR DEA TH. WIRING DIAGRAMS 42 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HI GH VO L T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLING THIS UNIT . MUL T IPL E POWER SOUR CES MA Y BE PR ESENT . F AILURE T O DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL I NJURY OR DE A TH . WIRING DIAGRAMS 43 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Een belangrijk punt na aankoop van elk apparaat Goodman Mfg GSZ/VSZ 13 SEER (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Goodman Mfg GSZ/VSZ 13 SEER heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Goodman Mfg GSZ/VSZ 13 SEER vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Goodman Mfg GSZ/VSZ 13 SEER leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Goodman Mfg GSZ/VSZ 13 SEER krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Goodman Mfg GSZ/VSZ 13 SEER bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Goodman Mfg GSZ/VSZ 13 SEER kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Goodman Mfg GSZ/VSZ 13 SEER . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.