SSZ 14 SEER S plit System Heat Pump s • Refer to Service Manual RS6200005 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet.
HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
7 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PE RFORM ANCE DA T A C OOL I N G OP E R A TION M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800** - 1 O ut door Am bi e nt Te m per at u.
8 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PERF O RM ANCE DA T A C OOL I N G OP E R ATION M O DE L : S S Z 1 40181A* / CA*F 3131* 6A* + T X V / M BR8 00**-1 O ut door Am bi e nt Tem pe ra tu.
9 COOLING PERFORMANCE DA T A SSZ140241A* EXPANDED PERF O RM ANCE DA T A C OOL I N G OP E R ATIO N M O DE L : S S Z 14 0241A* / CA*F3 636*6A*+ T X V / M B R800**-1 O utdoor Am bi e nt Te m pe r ature 6.
10 COOLING PERFORMANCE DA T A SSZ140241A* EX PANDED P ERF ORM ANCE DAT A C OOL IN G OP E R ATION M ODEL: S S Z 140241A* / CA*F3636*6A*+ T X V / M BR800**-1 O utdoor Am bi e nt Tem pe r ature 65 75 85 .
11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFO RM ANC E DA T A C OOLI N G OP E R ATI O N M O D EL: S S Z 140301A* / CA*F 3642*6A*+T X V / M BR1600**- 1 O utdoo r Am bi e nt Te m pe ra ture .
12 COOLING PERFORMANCE DA T A SSZ140301A* EX PANDED PERF O RM ANCE DAT A C O O L IN G O P E R A T IO N M O D EL: S S Z 140301A* / CA*F 3642*6A*+ TX V / M BR1600**-1 O utdoo r Am bi e nt T e m pe ra tu.
13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA N DED PER FORM AN CE D ATA M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoo r Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m pe r at u r e ID B Air flo w 5 9 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 33.
14 COOLING PERFORMANCE DA T A SSZ140361A* EX PANDED PE RF O RM ANCE DATA C OOL IN G OP E R AT ION M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r a tur e 65 .
15 COOLING PERFORMANCE DA T A SSZ140421A* EXPAN DED PERFORMAN CE DATA M ODEL : S S Z140421A* / CA*F 4860*6 A*+ T X V / M BR 2000**-1 O utdoor Am bi e n t Te m p e rature 65 75 85 95 105 115 E nte r ing I ndoo r We t B ulb Te m pe r atur e ID B A ir flo w 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 6 7 71 59 63 67 71 M Bh 39.
16 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PER F O RM AN CE DA TA C OOL I N G OP E R AT I ON M O DE L : S S Z140421A* / CA*F 4860*6 A*+ TX V / M BR2000* *- 1 O u tdoor Am bi e n t Te m pe r a.
17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OP E R ATIO N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR20 00**-1 O u tdoor Am bi e n t Te m pe ratu.
18 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FO RM AN CE D ATA C OOLIN G OP E R AT I O N M O DEL: S S Z 14 0481A* / CA*F 4860* 6A*+ T X V / M BR2000* *-1 O utdoor Am bi e n t Te m pe ratur.
19 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF O RM A NCE DATA C OOL I N G OP E R ATION M O DE L: S S Z 140601 A* / CA*F4860*6 A*+ T X V / M BE2 000**- 1 O utdoor A m bi e nt Te m pe r a t.
20 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF ORM ANCE DAT A C OOL I N G OP E R ATION M ODEL: S S Z 140601A* / CA*F4860*6A *+ TX V / M BE 2000**- 1 O utd oor Am bi e nt Te m pe ra ture 65.
21 PERFORMANCE DA T A Out door Temp. ° F . Total Btuh Sensible Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35.
22 EXPA NDED PERFORM A NCE DATA M ODEL: SSZ140361A * / CA*F4860C6A *+TXV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 2 0 17 15 10 5 0 -5 -10 MBh 4 3.5 41.2 38.8 36.2 34.6 33.5 31 .1 28.7 28.8 26.6 24.
23 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TXV / MBR2000**-1 HEA T ING OPERATION Outdoor Ambie nt Temperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 - 5 -10 MBh 57.8 5 4.7 5 1.5 48. 2 46.0 4 4.6 41.4 38.2 36 .6 33.8 31.
24 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19. 2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.
25 HEA TING SPECIFICA TIONS capaci t y btuh c. o. p. 4 .8 9.6 14. 4 19. 2 65 51.5 4 4 .44 67 .92 84. 30 100. 68 117. 07 60 48.7 9 4 .28 65 .17 8 1. 55 97. 94 114. 32 55 45.9 2 4 .11 62 .30 7 8. 68 95. 07 111. 45 50 42.9 3 3 .92 59 .31 7 5. 69 92. 07 108.
26 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 27 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS 28 HIGH VOL T A GE! DISCO NNECT A LL POWE R BEFORE SERVICI NG OR INS T A LLIN G THIS UNIT . M UL T IPLE POW ER SOURCES MA Y BE PRESENT .
Een belangrijk punt na aankoop van elk apparaat Goodman Mfg SSZ 14 SEER (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Goodman Mfg SSZ 14 SEER heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Goodman Mfg SSZ 14 SEER vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Goodman Mfg SSZ 14 SEER leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Goodman Mfg SSZ 14 SEER krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Goodman Mfg SSZ 14 SEER bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Goodman Mfg SSZ 14 SEER kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Goodman Mfg SSZ 14 SEER . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.