V ektor -CD Dir ect or Belt Drive The V ektor -CD fan is a side inlet centrifugal blower with a high plume dilution nozzle designed for laboratory exhaust systems.
Remove any accumulations of dirt, water , ice or snow and wipe dry before moving to indoor storage. T o avoid “sweating” of metal parts allow cold parts to reach r oom temperature. T o dry parts and packages use a portable electric heater to get rid of any moisture build up.
3 V ektor -CD Centrifugal Laboratory Exhaust ® REMOVING FROM ST ORAGE As fans are r emoved from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.
4 V ektor -CD Centrifugal Laboratory Exhaust ® Curb Installations Greenheck supplies gasketing material for all multi- section curbs and/or plenums. Install gasketing prior to bolting split curbs and or plenums together .
5 V ektor -CD Centrifugal Laboratory Exhaust ® Riser Installation Check curb or structural supports for levelness. Both must be level to ensure pr oper drainage from plenum and fan(s). For side inlet fans, remove panel at end of plenum. This opening is the designed connection spot for user connected ductwork from building.
6 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum Installation The figures depicted illustrate thr ee common methods used to install V ektor -CD bypass plenums. Methods used to attach a V ektor unit are dependent on local codes, roof construction design and r oof construction materials.
7 V ektor -CD Centrifugal Laboratory Exhaust ® Fan Installation Fan Housing Installation If the windband is shipped attached to the fan housing or if the windband is secured to the fan housing prior to mounting to the plenum, the fan / windband assembly should be lifted by the lifting lugs located on the fan housing.
8 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum and Fan Drainage Piping and T rap Detail (by others) There ar e multiple locations for pipe connections, one on each plenum section, and another on each tubular fan housing located at the bottom of the scroll.
9 V ektor -CD Centrifugal Laboratory Exhaust ® Disconnect is mounted to fan housing. T ransformer is mounted to bypass air plenum near isolation damper actuator motor . For systems that ship un-assembled because of physical size, this connection at disconnect from transformer must be field installed.
10 V ektor -CD Centrifugal Laboratory Exhaust ® Unit Start-Up 1. Disconnect and lock-out all power switches to fan. 2. Check for bearing alignment and lubrication. 3. Check the V -belt drive for proper alignment and tension (belt drive). 4. Check rigid coupling for proper alignment and connect between motor shaft and fan shaft (direct drive).
11 V ektor -CD Centrifugal Laboratory Exhaust ® Serviceable Components Windband Bypass Air Plenum Bypass Damper Weatherhood Isolation Damper Nozzle Fan Assembly Roof Curb or Structural Support Fan Operation All fans should be run every thirty (30) days, or at least “bumped” every thirty days.
12 V ektor -CD Centrifugal Laboratory Exhaust ® Motors Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only . Removing dust and grease buildup on the motor housing assists proper motor cooling.
13 V ektor -CD Centrifugal Laboratory Exhaust ® Bearing Replacement Both drive bearings are accessible fr om the ground on all V ektor -CD fans. Whether direct or belt driven, the bearings, along with other serviceable drive components (belts, motors, sheaves) are accessible by removing the motor cover panel.
14 V ektor -CD Centrifugal Laboratory Exhaust ® Problem Cause Corrective Action Excessive noise Wheel rubbing inlet Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft. V -belt drive Tighten sheaves on motor/fan shaft. Adjust belt tension.
15 V ektor -CD Centrifugal Laboratory Exhaust ® Date __________________ Time _____________ AM/PM Notes:___________________________________________ _________________________________________________ __.
16 471555 • Model V ektor -CD IOM, Rev. 1, February 2008 Copyright 2008 © Greenheck Fan Corp. Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of thr ee years from the pur chase date.
Een belangrijk punt na aankoop van elk apparaat Greenheck Fan 47555 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Greenheck Fan 47555 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Greenheck Fan 47555 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Greenheck Fan 47555 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Greenheck Fan 47555 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Greenheck Fan 47555 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Greenheck Fan 47555 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Greenheck Fan 47555 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.