990-1055A, 08/01 User’s Manual English APC Smart-UPS ® 2200VA /3000VA 3U Rack M ount Uninterr uptible Pow er Supply 230VA C/120VA C.
.
1 1: S AF E T Y I NFORMA TION Am erican Power Conversion Corporation (APC) is the leading n ational and international manu fac- turer of sta te-of-the -art uninterr upti ble p ower sup plie s, re dunda nt switches, p ower management so ft- w are, and related equi pment.
2 anesthesia ven tilators, infusion pumps, an d any other device designated as “critical” by the U.S.F.D.A. Hospital grade w iring dev ices and leakage cu rrent may be ordered as options on man y APC UPS system s, APC does not claim that units w ith this m odification are certified or listed as Hospital Grade by A PC or any oth er organization.
3 B ATTERY S AFETY This equipm ent contains potentially hazardou s voltages that m ay cause pers onal injury if handled incorrectly. This equipm ent m ust be installed and serviced only by qualified electrical service personnel. n This equipm ent contains poten tially hazardous voltages.
4 2: I NST A LLA TION The UPS has a “rack” des ign so it can be m ounted in a 19-inch (46.5 cm ) equipm ent rack. Hardw are is provi ded. U NPACKING 1. Inspect the UPS upon receipt. APC design ed robust packag ing for y our product. How ever, acci- dents an d damage m ay occu r during sh ipment.
5 5. Connect th e battery and attach th e front bezel. 6. Connect th e equipmen t and power to th e UPS. 7. Turn on th e UPS. I NSTALLIN G THE M OUNTING R AILS I N THE R ACK Install the m ounting rails in th e rack. Directions are included w ith the rail kit.
6 3. Locate the battery m odule handle at the top of the battery f ace plate . 4. Be careful during th is step—the battery module is heavy . Pull the battery m odule handle toward y ou to slide the battery m odule out of the UPS. DO NOT pull on the battery cables or the wh ite cord.
7 C ONNECTING THE B AT TERY AND A TTACHING THE F RONT B EZEL 1. Facing the f ront of the UPS, locate the battery cables and the UPS battery connector jack to the right of th e battery m odule. 2. To connect the battery connector plug to the battery jack, push the plu g into the jack so the metal pieces inside each part are touch ing.
8 4. Turn on all conn ected equipmen t (loads). To use the UPS as a m aster ON/OFF sw itch, be sure all connected loads are switched on. The loads will n ot be p owered un til the UPS is turned on. 5. Add any optional accessories. See th e documen tation accompany ing th e accessory f or details.
9 3: O PER A TION I NDICATORS A ND C ONTROLS ON THE S MART -U PS The APC Un interru ptible Pow er Supply (UPS) is des igned to prev ent blackou ts, brow nouts , sags an d surges from reaching y our computer an d other valuable electronic equipmen t.
10 S ELF -T EST Automatic Self-Test The UPS performs a s elf-test au tomatically when turned on, and ev ery tw o week s thereafter (by def ault). Refer to the User Configurati on Items for details on changing the default interval. Autom atic self-test eases m aintenance requiremen ts by elimin ating the need for periodic manual self -tests.
11 Voltage Trim This LED illumin ates to indicate the UPS is co mpensatin g for a high util- ity v oltage. Voltage Boost This LED illumin ates to indicate the UPS is co mpensatin g for a low utility volta ge.
12 S MAR T -UPS R EAR P ANEL The rear panel has the input and output conn ectors, computer interface port, and default setting bu t- tons for the low battery w arning level an d voltage sensitivity in dicator.
13 To red uce UPS sensitivity , press the voltag e sensitivity button. Use a pointed object (su ch as a pen) to do so. Press th e button once to set sensitivity to reduced . Press it again to set sensitivity to low . Press the button a third time to reset normal sensitivity.
14 O N -B A TTERY O PERATION The Smart-UP S switches to battery oper ation auto matically if the utility power fails. W hile running on-battery , an internal alarm sounds (periodic beeps). Pre ss the button (f ront panel) to silen ce the UPS alarm (for th e current alarm only).
15 4: U SER C ONFIGU RA TION I TEMS N OTE : S ET TING T HESE ITEMS REQU IRES SOFTWA RE OR O PTIONA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABL E C HOICES D ESCRIPTION Autom atic Self- .
16 N OTE : S ET TING T HESE ITEMS REQU IRES SOFTWA RE OR O PTIONA L HA RDWA RE . F UNCTION F ACTORY D EFAULT U SER S ELECTABL E C HOICES D ESCRIPTION High Transfer Point 120V Models 132 VAC 230V Model.
17 5: S T ORAGE A ND M A INTENA NCE S TORAG E S TORAGE C ONDITIONS Store the UPS covered and flat (rack mou nt orientation) in a cool, dry location, with its batteries fully charged. Disconnect any cables connected to the computer interface port to avoid unnecessary bat- tery dr aina ge.
18 6: T RA NSPORTING Y OUR S MA RT -UPS R EMOVING THE UPS FROM THE R AC K Always DIS CONNECT T HE BATTE RY before ship ping the UPS to avoi d dam age durin g transport. (U.S. Federal Regulation requires that batteries are disconnected during shipment.
19 7: T ROUBLESHOOTING Use the chart below to solve m inor UPS installation prob lems. A lso refer to the APC web site. Con- tact APC for ass istance w ith complex UPS problem s. P ROBLEM A ND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON ON button not pushe d.
20 P ROBLEM A ND P OSSIBLE C AUS E S OLUTION A LL INDICATORS ARE L IT AND THE UPS EMITS A CONSTANT BEEPING Int ernal UPS fault. Do not at tempt to use t he UPS.
21 S ERVICE If the un it requires service, do not return it to the dealer. Instead, follow these steps: 1. Review th e problems di scussed i n the Troubl eshooting section of this m anual to eliminate com - mon problems . 2. Verify that no circuit breakers are tripped.
22 8: C ONT A CT , R EGULA TOR Y , A ND W A RRA NTY I NFORMA T ION C ONTACTING AP C Refer to the inform ation provided at the APC Internet site: ht t p :/ / www. a p c. c o m/ s u pport/contact R EGULATORY A GENCY A PPROVALS 230V M ODEL S This is a Class A product.
23 D ECLARA TION OF C ONFORMITY L IMITED W ARRA NTY Am erica n Po we r Convers ion (APC) w arrants its products to be f ree f rom def ects in m ateri als and w orkma nship for a period of tw o yea rs from the date of purchase .
Een belangrijk punt na aankoop van elk apparaat American Power Conversion 3000VA 3U (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen American Power Conversion 3000VA 3U heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens American Power Conversion 3000VA 3U vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding American Power Conversion 3000VA 3U leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over American Power Conversion 3000VA 3U krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van American Power Conversion 3000VA 3U bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de American Power Conversion 3000VA 3U kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met American Power Conversion 3000VA 3U . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.