MX06 50 MX06 100 -48 VDC POWER SYSTEMS User’s Manual (Document # 990-9 131B).
MX06 Power Plant User’s Manual Page ii Table of Contents 1 Safety First! 1 1.1. W ARNING S YMBOLS .........................................................................................................1 1.2. G ENERAL P RECAUTIONS : ...............
MX06 Power Plant User’s Manual Page iii User Ou tputs................................................................................................................... ......18 User I nputs ..........................................................
MX06 Power Plant User’s Manual Page iv Revision History Revision Date By Preliminary 15 FEB, 2000 SCG PML-0216A 07 APR, 2000 SCG PML-0216B 05 MAY, 2000 SCG PML-0216C 26 JUN, 2000 DRD PML-0216D 27 OC.
MX06 Power Plant User’s Manual Page 1 1 Safety First! It is very important to follow all safety procedures when unpacki ng, installing and operating any sort of power equipment.
MX06 Power Plant User’s Manual Page 2 2 Introduction 2.1. General Information DC Power Plants from APC have unique features that make them easy to in stall, maintain, and upgrade. The rectifier units are modular and tr uly “hot-pluggable” into the shelf assembly without any separate AC wiring.
MX06 Power Plant User’s Manual Page 3 AC DC Control AC DC Control AC DC Control AC DC Control AC DC Control J3 USER ALARM INPU TS J2 ALARM RELAY OUTPUTS J5 MOTORIZED BREAKER CONTROLS J4 TEMPERATURE .
MX06 Power Plant User’s Manual Page 4 2.2. How to Use This Manual Each section of this manual ca n be read in any order and provi des a complete explanation of the subject described by the title. However, the sequence of the sections is designed to provide a typical step-by-step process fo r successful use of the equipment.
MX06 Power Plant User’s Manual Page 5 3 Installation 3.1. Unpacking Equipment Remove equipment from packing material and inspect for shipping damage or missing items. It is important to report damage or material shortages to the shipping carrier while a representative is on site.
MX06 Power Plant User’s Manual Page 6 Ventilation The rectifier modules for this system have fans t hat provide front-to-rear airflow for internal cooling. The power system housing should be moun ted such that there is free airflow to the front and back of the unit.
MX06 Power Plant User’s Manual Page 7 3.4. Battery Connections WARNING : Hazardous energy levels are present on bare conductors in the -48VDC distribution connec tion area of the plant. Accidental shorting of distribution conductors can cause ar cing and high currents that can cause serious burns or other physical harm.
MX06 Power Plant User’s Manual Page 8 Figure 3.4-1 Battery Cable Connection Locatio ns Battery LVD Connection The MX06 provides control for a motorized circ uit breaker on the –48 V battery string. This motorized circuit breaker is mounted on the ba ck of the MX06.
MX06 Power Plant User’s Manual Page 9 CM NO NC Yellow Yellow Brow n Orange 1 1 Batt Alm 2 2 Brown 3 3 Black 4 4 Orange 5 5 +BAT 6 6 Blue Black Orange Red Blue MX06 Breaker Side Motor Side J5 Battery.
MX06 Power Plant User’s Manual Page 10 Battery Temperature Probe Installation The 15 Ft (4.5m) temperature probe is used to m onitor the battery string temperature. To get the most representative temperat ure measurement, the probe should be placed in contact with a battery cell that is centrally loca ted.
MX06 Power Plant User’s Manual Page 11 3.6. Load Protection Installation Circuit Breaker Installation Standard circuit breaker output boar ds are available with two 30 Amp break ers or one 60 Amp breaker. Output boards are instal led at the factory and are not fiel d replaceable un its.
MX06 Power Plant User’s Manual Page 12 3.7. Load Connections Cable Size Considerations The DC load cable(s) should be sized to limit the voltage drop fr om the DC power plant to the loads per system design requirements. The cable( s) must also carry the full load current during battery operation.
MX06 Power Plant User’s Manual Page 13 GMT Fuse protected Load Connections Connections for ¼ to 15 Amp DC loads require a ring terminal with a 0.170 in (4.3 mm) clearance hole and are located at the rear of the unit. Load Connections should be made as shown in Figure 3.
MX06 Power Plant User’s Manual Page 14 RELAY OUTPUT J2 CONNECTOR DESIGNATIONS OUTPUT RELAY NOTES NC 1 MAJOR C 2 NO 3 NC 4 MINOR C 5 NO 6 NC 7 VERY LOW V C 8 NO 9 Figure 3.8-1 Output Relay Connections External Alarm Input Connections Four user-defined alarm inputs are provided on connector J3.
MX06 Power Plant User’s Manual Page 15 3.9. Rectifier Module Installation WARNING : Rectifier DC output ci rcuits will be damaged if battery is installed incorrectly.
MX06 Power Plant User’s Manual Page 16 5) Use a Digital voltmeter to measure t he system voltage using the “RTN” (+) and ”-NEG V” (-) test points on the fr ont panel. The volt age is set at the factory for –54.0 V dc. Use the “V ADJ” potent iometer to set th e voltage to the desired level.
MX06 Power Plant User’s Manual Page 17 4 T echnical Description The various MX06 models are modular stand-alon e –48 V dc power plants. Each can be configured to support most typi cal applications within their specified current capacity without special application eng ineering or assistance.
MX06 Power Plant User’s Manual Page 18 4.2. System Management A single plug-in circuit card provides the contro l, display and user interface functions for the MX06. Features include the following: Control Functions a) The Control Module is “hot-pluggable”.
MX06 Power Plant User’s Manual Page 19 User Inputs t) Temperature Probe: Provides input for battery voltage tem perature compensation. This feature operates only when the probe is attached. u) User Alar m Inputs: Four inputs are provided for user alarm inputs.
MX06 Power Plant User’s Manual Page 20 Battery Low Voltage Disconnect In order to prevent damage to the battery due to deep discharge, the DC power system has hardware support for a battery Low Voltage Disconnect (LVD). A battery LVD has the lo ads attached to the rectifiers and the battery is di sconnected from the system.
MX06 Power Plant User’s Manual Page 21 5 Operation 5.1. Description The MX06 is designed for years of operation with no user input. T he power system is pre-set at the factory with all parameters needed for normal operation. The front panel LEDs and the alarm output relays, indicate the general health of the unit.
MX06 Power Plant User’s Manual Page 22 MX06 External Alarm Input Configuration The MX06-50 and the MX06-100 alarm input circuitry is the same for both controllers.
MX06 Power Plant User’s Manual Page 23 MX06-50 Rectifier Configuration The system Controller Board must know if a rectifier is present for eac h of the five slots. This is done by the properly setting the dipswitch S2 (“R ECT PRESENT”) on the Co ntroller Board.
MX06 Power Plant User’s Manual Page 24 MX06-50 Temperature Probe Selection Temperature compensation can be configured for either a Fahrenheit or Celsius probe by the use of configuration jumpers on pin header J4 shown in Figure 5. 3-1. The MX06-50 is factory set for Fahrenheit operation, with jumpers on all position of J4.
MX06 Power Plant User’s Manual Page 25 MX06-100 Programmable Alarms The GMT alarm, and the battery circuit breaker alarm can each be programmed to either MAJOR or MINOR alarm priority. A three-pin jumper header is used for each alarm in the manner shown in Figure 13.
MX06 Power Plant User’s Manual Page 26 6 Specifications The overall system specifications can vary, depending upon the number of rectifier modules. Note that some specification items are provided on a “ per rectif ier” basis and must be combined or totaled for a given system configuration.
MX06 Power Plant User’s Manual Page 27 MX06 100 Power System Nominal Input Voltage 90, 115, 208, 230 VAC Input Voltage Range 85 – 264 VAC AC Frequency Range 47 – 63 Hz Apparent Power Factor 99% Typical, 98% Minimum Input Current 55 Amps @ 115 Volts AC 37 Amps @ 230 Volts AC 6.
MX06 Power Plant User’s Manual Page 28 MX06 50 Power System Output Voltage (factory programmed) 54.0 VDC Operating Voltage Range 47 – 57 VDC Rated Output Current 52.5 A Efficiency 85% Typical Over Voltage Protection 59.5 Volts DC Output Current 45 Amps Minimu m Continuous at 115 VAC Input 52.
MX06 Power Plant User’s Manual Page 29 6.3. Controls and Indicators TWF0500H5401 Rectifier FAIL LED DC output voltage below (-) 39.5 Volts DC or above (-) 59.5 Volts DC. MX06 Controller Voltage Good LED (Green) On when vo ltage is between 50 and 57 Volts.
MX06 Power Plant User’s Manual Page 30 Magnum VS 50 Power System Dimensions 5-1/4 in (13.3 cm) high x 17-1/4 in (43.8 cm) wide x 12.5 in (32 cm) deep Weight 12 lbs. (5.5 Kg) Color Grey Front, Yellow zinc sides and back Mounting 19” Rack Mounting (23” Optional) Magnum VS 100 Power System Dimensions 10-1/2 in (26.
MX06 Power Plant User’s Manual Page 31 6.6. Compliance NEBS NEBS Level 3 Safety UL 1950 / CE EMC FCC Part 15, Subpart J, Class A EN50081-1, EN50082.
MX06 Power Plant User’s Manual Page 32 7 APC W orldwide Customer Support Customer Support for this or any other APC product is available at no charge.
MX06 Power Plant User’s Manual Page 33 8 Limited Pr oduct W arranty The limited warranty pro vided by American Power Co nversion Corporation ("APC") in this Statement of Limited Factory Warranty applies only to Produc ts Buyer purchases for your commerc ial or industrial use in the ordinary course of Buyer's business.
Een belangrijk punt na aankoop van elk apparaat American Power Conversion MX06 100 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen American Power Conversion MX06 100 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens American Power Conversion MX06 100 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding American Power Conversion MX06 100 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over American Power Conversion MX06 100 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van American Power Conversion MX06 100 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de American Power Conversion MX06 100 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met American Power Conversion MX06 100 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.