Doc # PML-0209 Revision Level: A DC POWER PLANT PRODUCT MANUAL MODEL MX28B American Power Conversion 11035 Switzer Avenue Dallas, TX 75238 214-342-5000 December, 1999.
ii MX28B REVISION HISTORY Revision Date By Description A 12/16/99 BGL Initial release..
MX28B iii TABLE OF CONTENTS 1. GENERAL INFORMATI ON ................................................................................................................. 1 1.1 I NTRODUCTION .................................................................
iv MX28B 5.7.1 DC Circuit Breakers and Fuses ............................................................................................. 16 5.7.2 Installation of Circuit Breakers and Fuses ............................................................
MX28B 1 1. GENERAL INFORMATION 1.1 Introduction DC Power Systems from APC have unique features that make them easy to install, maintain, and upgrade. The rectifier units are modular and truly “hot-pluggable” into the shelf assembly without any separate ac wiring.
2 MX28B If damage has occurred or the quantity of items is not correct, then: 1) Make a descriptive notation on the delivery receipt before signing. 2) File a damage or shortage report with the carrier that delivered the shipment.
MX28B 3 2. CUSTOMER SERVICE AND SUPPORT APC manufactures a line power plants and provides customers with complete product and systems support and service. APC has an international network of factory trained service technicians. The service organization is on call 24 hours a day, 365 days a year.
4 MX28B 3. WARRANTY PROVISIONS 3.1 General Provisions APC warrants the power equipment and components it manufactures or sells against defective materials and workmanship for a period of TWO (2) YEARS from the date of shipment.
MX28B 5 4. Advance Power, Inc. assumes no responsibility for any work accomplished or expenses incurred except with expressed written consent from Advance Power, Inc.
6 MX28B 4. PRODUCT OVERVIEW AND TECHNICAL DESCRIPTION 4.1 Description The Advance Power, Inc. Model MX28B is a modular stand-alone -48V dc power plant.
MX28B 7 Figure 4.1 - 2 . MX28B BLOCK DIAGRAM.
8 MX28B 4.2 Power Output Capacity The power plant has two basic configurations: The first supplies a maximum of 200 amps or 150 amps with N+1 redundancy. The housing for this configuration provides space for one rectifier shelf that can hold up to four rectifiers, a control unit, and one tier of up to 24 distribution circuit breakers.
MX28B 9 • Control of either a battery or a load LVD 4.5 AC Input Power Each rectifier requires 208/220/240V ac, single-phase, 50/60 Hz, supplied through an external 20-amp two-pole breaker.
10 MX28B 4.7 DC Distribution A standard 24-position plug-in circuit breaker tier provides -48V distribution. The breaker tier is connected at its center to the -48V dc bus, and each side has an ampacity of 300A.
MX28B 11 4.10 Mechanical Dimensions: 15.75” high x 23” wide x 17.5” deep (200 amp unit) 22.75” high x 23” wide x 17.5” deep (400 amp unit ) Weight: Housing - 85 lbs.
12 MX28B 5. INSTALLATION PROCEDURES 5.1 Preparation 5.1.1 Recommended Tools • Standard selection of insulated hand tools. • Proper tools for crimping the selected cable lugs.
MX28B 13 5.1.6 Mounting Both front mounting on standard 23-inch rails and optional wall mounting are available. 5.1.7 Ventilation The rectifiers have fans that provide front to rear airflow for internal cooling. The MX28B housing should mounted such that there is free airflow to the front, top, and bottom of the unit.
14 MX28B cable(s) must also carry the full load current during battery operation. If assistance is required to determine the necessary cables for the application, contact your sales representative or Advance Power, Inc. 5.3.3 Connecting the Cables The battery cable connections are located at the top rear of the unit as shown in Figure 4.
MX28B 15 Table 5.6 - 1 . External Alarm Input Definition Table 5.6 - 2 shows the external alarm input connection designations. Connector J4 is located on the interface card mounted in the top left side of the unit. Systems are shipped with jumper wires connecting each NC and corresponding C contact.
16 MX28B ALARM OUTPUT TERMINAL DESIGNATION NO-NC-C USER ALARM NOTES RELAY #1 RELAY #2 RELAY #3 RELAY #4 RELAY #5 RELAY #6 MINOR MAJOR J1 NO1-NC1-C1 NO2-NC2-C2 NO3-NC3-C3 NO4-NC4-C4 J2 NO5-NC5-C5 NO6-N.
MX28B 17 30 A FFA-0019 * -1: adapter has #10 studs on 5/8” centers for two-hole cable lug -2: adapter has #10 studs on ¾” centers for two-hole cable lug -3: adapter has ¼” studs on 1” centers for two-hole cable lug Table 5.7 - 1 . Plug-in Circuit Breakers A list of GMT type fuses available from Advance Power, Inc.
18 MX28B NOTE: Circuit breaker alarm contacts close when the circuit breaker is tripped but not when it is turned OFF. ***** CAUTION ***** During circuit breaker installation, carefully align the breaker alarm terminals with the alarm terminal board to avoid breaker terminal damage.
MX28B 19 as seen in Figure 5.7 - 1 . The return bus provides 24 sets of threaded #10-32 holes on 5/8” centers and four sets of threaded ¼”-20 holes on ¾” centers for connection of two-hole lugs on load return wires.
20 MX28B MX28B + S TATUS ALARMS SYSTEM MODULES BATT PIN OEM Figure 5.9 - 1 5.9.2 System Parameters Verification/Adjustment The MX28B system control unit is delivered with pre-programmed parameter default settings.
MX28B 21 6. SETUP, ADJUSTMENTS, AND OPERATION 6.1 User Interface The MX28B control unit provides a user interface designed with a hierarchical menu that can be viewed on the 32-character display by “navigating” with the “ ï ” (left), “ ð ” (right), “ ñ ” (up), and “ ò ” (down) arrow keys located on the front panel.
22 MX28B 6.3 Alarm Output Relays There are eight alarm output relays designated Relay 1 through Relay 6, Minor, and Major, respectively. Various system parameters may be programmed to activate any of these alarm relays when set thresholds are exceeded or specific conditions occur.
MX28B 23 Table 6.4 - 1 . Parameter Locations, Descriptions, and Default Values PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS SYSTEM SETUP Password Entry PIN Entry [PIN] Screen for entry of the active password (PIN).
24 MX28B ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Display Type [SYSTEM/SETUP] Type number for the control unit display. Display Type + 000255 D ate/Time Setup Date {1} [SYSTEM/DATE] Internal system calendar date.
MX28B 25 ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS System Low Temperature {1} [SYSTEM/SET-ALM] The control unit temperature is below the low temperature threshold.
26 MX28B ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS • • • • • • • • • Test Relay 6 {1} [SYSTEM/DIAG] Setting this parameter to “ON” energizes Relay 6 and turns on the “ALM6” LED on the control unit front panel.
MX28B 27 ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS High Voltage Alarm {1} [BATT/SET-ALM] An alarm that is generated if the magnitude of the battery voltage rises above the high voltage threshold.
28 MX28B ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS RFA Alarm {1} [MODULES/RECT/SET-ALM] This alarm indicates that a rectifier output has failed.
MX28B 29 ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS INPUT RELAY SETUP Input Relay 1 Alias {1} [SYSTEM/IN-RLY/ALIAS] An alternate name (alias) can be assigned to the relay if desired.
30 MX28B ( Table 6.4 -1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Output Relay Alarms Output Relay 1 {1} [SYSTEM/OUT-RLY/RLY-MAP] Output Relay 1 alarm can be “mapped” to activate other output relays (“Ignore” activates no additional relays).
MX28B 31 Figure 6.4 - 1 . Control Unit Menu Structure MX28B + STATUS Sys Voltage Sys Current Sys Temp Batt Current Batt Temp ALARMS Alarm Item 1 Alarm Item 2 Alarm Item 3 Alarm Item 4 Alarm Item 5 Ala.
32 MX28B (Figure 6.4 -1. Control Unit Menu Structure) Address 3 Model Fahrenheit Cntrl Rev FW Version Display Type DATE Date Time OUT-RLY RLY-MAP Out-Rly 1 Alm Out-Rly 2 Alm Out-Rly 3 Alm Out-Rly 4 Al.
MX28B 33 (Figure 6.4 -1. Control Unit Menu Structure) Test Relay 1 Test Relay 2 Test Relay 3 Test Relay 4 Test Relay 5 Test Relay 6 Test Min Rly Test Maj Rly MODULES RECT SET-ALM Rect CL Alm Rect Stdb.
34 MX28B (Figure 6.4 -1. Control Unit Menu Structure) Cir Bkr 21 Alm Cir Bkr 22 Alm Cir Bkr 23 Alm Cir Bkr 24 Alm ALIAS Cir Bkr 1 Cir Bkr 2 Cir Bkr 3 Cir Bkr 4 Cir Bkr 5 Cir Bkr 6 Cir Bkr 7 Cir Bkr 8 .
MX28B 35 (Figure 6.4 -1. Control Unit Menu Structure) GMT 8 LVD SET-ALM LVD Option LVD Open Alm PARAM LVD Trip LVD Reset BATT SET-ALM Batt Disc Thr Batt Disc Alm Batt HV Thr Batt HV Alm Batt LV Thr Ba.
Een belangrijk punt na aankoop van elk apparaat American Power Conversion MX28B (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen American Power Conversion MX28B heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens American Power Conversion MX28B vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding American Power Conversion MX28B leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over American Power Conversion MX28B krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van American Power Conversion MX28B bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de American Power Conversion MX28B kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met American Power Conversion MX28B . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.