Gebruiksaanwijzing /service van het product XS 450 -48 van de fabrikant American Power Conversion
Ga naar pagina of 48
Magnum XS 450 -48 Vdc Power System User’s Manual.
Magnum XS 450 Power System –48 VDC User’s Manual Page ii Table of Contents 1 SAFETY FIRST! ................. ............... .................... ................ ................... ................ .......... 1 1.1. W ARNING S YMBOLS ...........
Magnum XS 450 Power System –48 VDC User’s Manual Page iii Relay Output Connections ............................. ................ ................ ................... ................ 27 External Alar m Input Connections ..................... ....
Magnum XS 450 Power System –48 VDC User’s Manual Page iv System Temperature Test ......................... ................ .................... ............... ................ .... 38 Battery Current Test ....... ................... ............
Magnum XS 450 Power System –48 VDC User’s Manual Page v Revision History Revisi on Da te By Descri pti on 990-1557 Revision 1 20 Oct, 2003 JPF Initial Re lease 990-1557 A Revision 2 30 MAR 2004 BET Update to inclu de Battery Cabinet Table of Figures FIGURE 2.
Magnum XS 450 Power System –48 VDC User’s Manual Page 1 1 Safety First! It is very import ant to follow all safety p rocedures when unpacking, installing and operating any sort of power equipment.
Magnum XS 450 Power System –48 VDC User’s Manual Page 2 2 Introduction 2.1. General Informatio n DC Power Plants fr om APC have unique features tha t make them easy to install, maintain , and upgrade. The rectifier units are mo dular and truly “hot-pluggabl e” into the shelf assembly witho ut any separate ac wiring.
Magnum XS 450 Power System –48 VDC User’s Manual Page 3 Figure 2.1-2 Power System Block Diagram.
Magnum XS 450 Power System –48 VDC User’s Manual Page 4 How to Use This Manual Each section of this manu al can be re ad in any order and should provide a compl ete explanation of the subject described by the title. However, the sequence of the sections is designed to provide a typical step-by-step p rocess for successful use of the equipment.
Magnum XS 450 Power System –48 VDC User’s Manual Page 5 3 Installation 3.1. Unpacking Equipment Remove equipment from packing material and inspect for shipp ing damage or miss ing items. It is important to report damage or m aterial shortages to the shippin g carrier while a rep resen tative is o n site .
Magnum XS 450 Power System –48 VDC User’s Manual Page 6 Figure 3.2-1 Door Clearance Dimensions.
Magnum XS 450 Power System –48 VDC User’s Manual Page 7 Mounting The unit is self-s upporting, but designed to be bolted to the floor of the housing structure. Figure 3.2-2 shows the f ootprint of the box frame and the mounting p oints with dimensions.
Magnum XS 450 Power System –48 VDC User’s Manual Page 8 3.3. AC Power Connections WARNING : Ensure that all of the external dc and ac circuit break ers are in the OFF position prior to connectin g service to the power plant. Confirm that all voltages have been removed includin g any battery sources before proceeding .
Magnum XS 450 Power System –48 VDC User’s Manual Page 9 powered from the terminal bl ock labeled L2. The rig ht rectifier in each shelf is powered from the ter min al bl ock la bele d L3. AC Line 1 AC Line 2 AC Line 3 AC Neutral Earth Ground DC AC DC AC DC AC DC AC DC AC DC AC DC AC DC AC DC AC L1 L2 L3 Neut.
Magnum XS 450 Power System –48 VDC User’s Manual Page 10 Neutral Input Wire Size (AWG) Wire Size (mm 2 ) Max Torque (in-lb) Max Torque (N-m) 350 kcmil – 2 Cu 185 – 35 Cu 275 31.75 L1, L2, and L3 Input Wire Size (AWG) Wire Size (mm 2 ) Max Torque (in-lb) Max Torque (N-m) 2/0 – 6 Cu 70-16 Cu 125 13.
Magnum XS 450 Power System –48 VDC User’s Manual Page 11 AC Line 1 AC Neutral 1 AC Line 2 AC Neutral 2 AC Line 3 AC Neutral 3 AC Line 4 AC Neutral 4 AC Line 5 AC Neutral 5 AC Line 6 AC Neutral 6 A.
Magnum XS 450 Power System –48 VDC User’s Manual Page 12 Rectifier Shelf Serial Communications Program the binary address of each rectifier in the shelf using S1 on the rectifier interface card. These are located at the b ack of each rect ifier slot.
Magnum XS 450 Power System –48 VDC User’s Manual Page 13 Rectifier Module Installation WARNING : Rectifier dc output circuits would be damaged if battery were installed incorrectly. Before rectifier install ation, ensure proper battery polarity. Rectifier modules are hot-swappable.
Magnum XS 450 Power System –48 VDC User’s Manual Page 14 Merlin Gerin 28 Circuit Breaker Module Installation WARNING : Hazardous energy levels are present on bare conduc tors in the -48Vdc distribution connection ar ea of the plant.
Magnum XS 450 Power System –48 VDC User’s Manual Page 15 Merlin Gerin 12 Circuit Breaker Module Installation WARNING : Hazardous energy levels are present on bare conduc tors in the -48Vdc distribution connection ar ea of the plant.
Magnum XS 450 Power System –48 VDC User’s Manual Page 16 Figure 3.5-2 12 Circuit Breake rs Module CIRCUIT BREAKER R ATING ORDERING NUMBER Merlin Gerin C60HC 4 A 0M-3318 Merlin Gerin C 60HC 10 A 0M.
Magnum XS 450 Power System –48 VDC User’s Manual Page 17 dc bus. Use M8 hardware to secure the buses together. Use M5 har dware to secure the front lip to the powe r system frame. Use M6 ha rdware to secure the rear of the module to the power system frame.
Magnum XS 450 Power System –48 VDC User’s Manual Page 18 Hooking the lo ad cables to a module us ed as a battery retu rn will cause erroneous batt ery curren t reading s. The dc load cable(s) should be sized to limit the voltage drop from the Magnum XS 450 Power System to the loads per system design requirements.
Magnum XS 450 Power System –48 VDC User’s Manual Page 19 Installing circuit breakers in a 28 Circuit Breaker Mo dule on the DIN rail Figure 3.7-2 Merlin Gerin 28 CB Module Insta llation Detail Ins.
Magnum XS 450 Power System –48 VDC User’s Manual Page 20 C60 28 26 25 23 22 20 19 17 16 14 C120 0 1 2 3 4 5 6 7 8 9 Total 28 27 27 26 26 25 25 24 24 23 C60 13 11 10 8 7 5 4 2 1 0 C120 10 11 12 13 14 15 16 17 18 19 Total 23 22 22 21 21 20 20 19 19 19 Table 3.
Magnum XS 450 Power System –48 VDC User’s Manual Page 21 Figure 3.7-4 CB Alarm Interface Board (28 circuit breaker module) Figure 3.7-5 CB Alarm Expansion Board (12 circuit breaker module).
Magnum XS 450 Power System –48 VDC User’s Manual Page 22 Installing a fuse in the NH2 Fuse Module Insert the fuse into the fuse module until the tangs on each end of the fuse bottom out in the socket.
Magnum XS 450 Power System –48 VDC User’s Manual Page 23 Figure 3.7-7 Large Load a nd Small Load Return Module DC Lo ad Re turn cabl e con nec tio ns The battery return module has a shunt ins talled and t he load return modules do not. The small return has 40 pairs of M5 threade d holes on 1.
Magnum XS 450 Power System –48 VDC User’s Manual Page 24 Connect t he LVD pow er wiring to the po wer bus observ ing proper polarity. Connect the LVD control cable to the customer interface bus. The alarm signal of each i ndividual Batt ery Disconnect Swit ch is connec ted to the blade terminals of the switch (C and N/C).
Magnum XS 450 Power System –48 VDC User’s Manual Page 25 Battery Return Module Insta llation The battery return mo dule is typically installed in the top return modul e position. To install the battery return module, loosen the 4 M5 X 8 Phillips head screws on the back of the unit.
Magnum XS 450 Power System –48 VDC User’s Manual Page 26 positioning the probe o n the selected battery cell. Rem ove the adhesive prote ction strip from the probe body and press the adhesiv e side of the probe on the batt ery cell cover. Figure 3.
Magnum XS 450 Power System –48 VDC User’s Manual Page 27 is possible by DB-9 cable on t he Console Port of the module and v ia RJ-45 (Ethernet) cable on the 10/100 Base-T port on the Network Ma nagement Card.
Magnum XS 450 Power System –48 VDC User’s Manual Page 28 External Alarm Input Connections Four external alarm inputs with assignable priority l evels are available. These a larm inputs respond to external dry contact closures between nor mally open (N/O) and common ( C) or contact openings between normally cl osed (N/C) and C.
Magnum XS 450 Power System –48 VDC User’s Manual Page 29 4 Commissioning 4.1 Pre-Commissioning Inspection Environment 1. Ensure the dc system environment is suitable for operation. 2. Ensure that there is sufficient clearance around the system for service.
Magnum XS 450 Power System –48 VDC User’s Manual Page 30 10. Che ck th e tor que of all batt ery i nter - ce ll connector in accordance with the battery manufacturer’s specificati ons. 4.2 Commissioning Initial Set-up 1. Remove all rectifiers. 2.
Magnum XS 450 Power System –48 VDC User’s Manual Page 31 1. Monitor battery current an d verify that it is +/- 0.1 A. 2. Set battery maximum recharge setting by determi ning the entire battery string capacity and dividing by 10 hours. This setting will recharge the battery in 10 hours.
Magnum XS 450 Power System –48 VDC User’s Manual Page 32 3. Verify that the system voltage is above the float voltage if the battery tempe rature is below 25 degrees C and below the float voltage if the battery temperature is above 25 degree s C. 4.
Magnum XS 450 Power System –48 VDC User’s Manual Page 33 5 Operation 5.1 Technical Description The Magnum XS 450 Power System is designed to supply safe –54 Vdc primary power through the use of up to nine rectifi er modules. If installed with an interna l battery string, it will supply backup power as well.
Magnum XS 450 Power System –48 VDC User’s Manual Page 34 5.3 DC Distr ibutio n DC Distribution Module The main function of the dc distribution module is to provide a means of connect ing and protecting cables that will be con nected to powe r dc loads.
Magnum XS 450 Power System –48 VDC User’s Manual Page 35 5.5 C ustomer Interface Board Alarm Outputs (Output Relay s) There are eight a larm output relays desi gnated Relay 1 through Relay 6, Minor, and Maj or, respectively.
Magnum XS 450 Power System –48 VDC User’s Manual Page 36 6 Preventive Maintenance Preventive Maintenance is typically perfor med on a quarterly basis. 6.1 Equipment 1. 4 Digit Voltmeter. 2. Clamp-on ampere meter. 3. Standard In sulated tools. 6.2 I nspecti on Environmental Ins pection 1.
Magnum XS 450 Power System –48 VDC User’s Manual Page 37 2. Check the mechanical integr ity of the battery framing, racking, or cabinet. Tighten wher e nec essa ry. 3. If there is a battery disconnect device fitted, ens ure that it is properly connected and protected.
Magnum XS 450 Power System –48 VDC User’s Manual Page 38 5. After the fan has completely stopped spinnin g, insert a plastic pen or plastic screwdriver into t he fan blade of one of the rectifiers a nd reinsert both rectifier s 6. Verify that you get the fan f ail alarm on controller and the customer remote alarm panel.
Magnum XS 450 Power System –48 VDC User’s Manual Page 39 Battery Preventive Mainten ance Procedure The purpose of the preventive ma intenance is to ensure that the battery is in good, worki ng condition. The observations, measureme nts, and tests performed are designed to determi ne the “state of health” of the battery.
Magnum XS 450 Power System –48 VDC User’s Manual Page 40 7 Specifications The overall system specifications can vary, depe nding upon the number of rectifier modules. Note that some sp ecification it ems are provid ed on a “per r ectifier” basi s and must be combined or totaled for a give system configuration.
Magnum XS 450 Power System –48 VDC User’s Manual Page 41 7.4 Compliance Safety IEC 60950, 3 rd Edition CE Marked to Low Volt age Directive (EN60950, 3 rd Edition) EMC FCC Part 15 Class A EN55022 C.
Magnum XS 450 Power System –48 VDC User’s Manual Page 42 8 APC W orldwide Customer Support Customer Support for this or any other APC product is available at no charg e.
Magnum XS 450 Power System –48 VDC User’s Manual Page 43 9 Limited Product W arranty The limit ed warra nty provi ded by Americ an Pow er Conversi on Corporat ion ("APC") in this St atem.
Een belangrijk punt na aankoop van elk apparaat American Power Conversion XS 450 -48 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen American Power Conversion XS 450 -48 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens American Power Conversion XS 450 -48 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding American Power Conversion XS 450 -48 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over American Power Conversion XS 450 -48 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van American Power Conversion XS 450 -48 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de American Power Conversion XS 450 -48 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met American Power Conversion XS 450 -48 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.