Gebruiksaanwijzing /service van het product HDG48 van de fabrikant Heat Controller
Ga naar pagina of 27
Heat Controller , Inc. • 1900 Wellworth A ve. • Jackson, MI 49203 • (517)787-2100 • www .heatcontroller .com INST ALLA TION INSTR UCTIONS Air Handler HDG Series 1.
HDG Series Air Handler INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 1 1.0 NOMENCLA TURE ............................................................................................................... 2 2.0 SAFETY ...............................
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 2 These instructions are intended as an aid to qualied licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 3 This document is customer property and is to remain with this unit. These instructions do not cover all the different variations systems nor does it provide for every pos - sible contingency to be met in connection with installtion.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 4 The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. PROPOSITION 65: This appliance contains berglass insulation.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 5 Do not install this unit in manufactured (mobile) homes. Improper installation is more likely in manufactured housing due to ductwork material, size, location and arrangement.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 6 3.0 General The unit can be positioned for bottom return air in the upow position, left and right return in the horizon - tal position, top return in downow position.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 7 Model Size Dimensions Unit Weight lbs. [kg] Unit Height in. [mm] Unit Weight in.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 8 1-9/16 2-15/16 5/16 2-15/16 1-3/ 8 1-1/ 4 5/16 2-13/16 Fig.2 Coil Connection Dimensions 4.0 Applications 4.1 V ertical Upow • V ertical Upow conguration is the factory set on all models (see Fig 1).
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 9 • Using a screwdriver or pencil, lift blue plastic tab with hole away from breaker until breaker releas - es from mounting opening.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 10 Fig.4 INDOOR COI L AND DRAIN P AN SET- UP A 1:4 A RAILS RAILS DETA IL A ENSURE THE RETA INING CHANNEL IS FULLY ENGAGED WITH THE COIL RAIL.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 1 1 Horizontal units must be congured for right hand air supply or left hand air supply . Horizontal drain pan must be located under indoor coil. Failure to use the drain pan can result in property damage.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 12 5.2 CONTROL WIRING IMPORT ANT : Class 2 low voltage control wiring should not be run in conduit with main power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 13 Model V oltage HP RPM SPEEDS CIRCUIT AMPS. MINIMUM CIRCUIT AMP ACITY MAXIMUM CIRCUIT PROTECTOR HDG18 208/230-1-60 1/8 580 3 0.68 1 15(A) HDG24 208/230-1-60 1/5 701 3 0.95 1.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 14 6.0 Airow Performance Airow performance data is based on cooling performance with a coil and no lter in place. Select perfor - mance table for appropriate unit size.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 15 Model Number Motor Speed CFM (W atts) External Static Pressure-Inches W .C. [kPa] 0 [0] 0.1 [.02] 0.16 [.04] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 16 Terminal Fan speed M edium High Low Fan M1 M2 Red Blue B lack Black Blue Red Blue R ed Black Fan speed switch congurations: 1. All motors are shipped from the factory at medium speed as default.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 17 7.0 DUCTWORK Field ductwork must comply with the National Fire Protection Association NFP A 90A, NFP A 90B and any applicable local ordinance.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 18 8.0 REFRIGERANT CONNECTIONS Keep the coil connections sealed until refrigerant connections are made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 19 • The drain line should be insulated where necessary to prevent sweating and damage due to conden - sate forming on the outside surface of the line. • Make provisions for disconnecting and cleaning of the primary drain line should it become neces - sary .
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 20 Scroll Heat Pump Applications* Air Handler: Heat Pumps Piston Size HDG18FB-1A HRG18S-1D 0.052 inch HDG24FB-1A HRG24S-1D 0.058 inch HDG30FB-1A HRG30S-1D 0.065 inch HDG36FB-1A HRG36S-1D 0.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 21 9.0 AIR FIL TER (not factory-installed) • External lter or other means of ltration is required. Units should be sized for a maximum of 300 feet/ min. air velocity or what is recommended for the type lter installed.
Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 22 10.0 FIL TER INST ALLA TION DIMENSIONS AIR FIL TER REMOV AL 1.Remove bolts manually , remove air lter recover , see in Fig 7; 2. Hold the edge of the air lter and extract out .
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 23 1 1.0 Wiring Diagram 1. T o avoid the electrical shock, connect the air conditioner with the ground lug. The main power plug in the air conditioner has been joined with the ground wiring, please don’t alter it.
Fig. 10: Indoor Unit Wiring Diagram for A/C Systems and H/P Systems Heat Contr oller , Inc. INST ALLA TION INS TRUCTIONS HDG Series Air Handler 24.
HDG Series Air Handler INST ALLA TION INS TRUCTIONS Heat Contr oller , Inc. 25 0 1 2 6 4 8 2 6 4 8 0 1 12 GA 1015 600V 105 C F IE L D W I R I N G P ER L O C A L CO D E 6 N C PCB 1 L 2 L 1 L 2 L 0 1 2 .
04/2009 05/201 1.
Een belangrijk punt na aankoop van elk apparaat Heat Controller HDG48 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Heat Controller HDG48 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Heat Controller HDG48 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Heat Controller HDG48 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Heat Controller HDG48 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Heat Controller HDG48 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Heat Controller HDG48 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Heat Controller HDG48 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.