Gebruiksaanwijzing /service van het product DB/DW-720-1810 van de fabrikant A.O. Smith
Ga naar pagina of 44
1 WITH ELECTRONIC INTERMITTENT PILOT IGNITION AND INST ALLA TIONS W ARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. — Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
2 FOREWORD CA UTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE USING APPLIANCE. Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested.
3 W ARNING AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILA TION. Minimum Clearances T o Combustibles Water Blank T op Side Side Rear V ent Front All Models 12" (305mm) 18" (457mm) 6" (155mm) 6" (155mm) 6" (155mm) Alcove CAUTION Label all wires prior to disconnection when servicing controls.
4 W ARNING Y our Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than 100 ° F (38 ° C). Colder inlet water temperatures will result in significant condensation developing on the heat exchanger .
5 FEA TURES IMPORT ANT Only qualified personnel shall perform the initial firing of the heater . At this time the user should not hesitate to ask the individual any questions regarding the operation and maintenance of the unit. Lighting and Operating instructions are included at the rear of this manual.
6 AUT OMA TIC RESET HIGH TEMPERA TURE LIMIT CONTROL CAUTION LIMIT CONTROLS ARE NOT TO BE USED AS THERMOST A TS. ALL MODELS - This limit is a safety device wired in series with the ignition system. Set the limit control dial to a minimum of 10 ° F (6 ° C) above the maximum designed system temperature.
7 INST ALLA TION INSTRUCTIONS REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS BOILER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING, AIR SUPPL Y , VENTING, GAS SUPPL Y AND ELECTRICAL WORK ARE REQUIRED.
8 If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner , shall be provided.
9 W ARNING F AILURE TO CORRECT BACK DRAFTS MA Y CAUSE AIR CONT AMINA TION AND UNSAFE CONDITIONS. V ent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
10 T ABLE 5 Multipliers T o Be Used W ith T able 1 When Applying The Gravity Factor T o Other Than .60 Specific Gravity Specific Specific Gravity Multiplier Gravity Multiplier .35 1.31 1.00 .78 .40 1.23 1.10 .74 .45 1.16 1.20 .71 .50 1.10 1.30 .68 .55 1.
11 Applications of the gravity factor converts the figures given in table 1 to capacities with another gas of different specific gravity . Such application is accomplished by multiplying the capacities given in table 1 by the multipliers shown in table 5.
12 IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105 ° C WIRE OR ITS EQUIV ALENT , EXCEPT FOR THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250 ° C. SERVICING WIRING AND/OR CONTROL CAUTION Label all wires prior to disconnection when servicing controls.
13 The flow switch shall be mounted in the top opening of the reducing tee and provide adequate paddle length in the flow stream. For example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For 2" or 3" pipe use the paddle segments as supplied.
14 Thereafter , during the heating season, lubricate the three oil cups at least once every four months. Combination heating/cooling systems or water heating (Cer-temp) systems should be lubricated every four months year-round. Use 2 or 3 teaspoonfuls in bearing oil cups, fig.
15 A system bypass should be installed as shown in fig. 10 to prevent boiler circulation starvation when the system zones call for reduced flow . This bypass may also be used with multiple boilers manifolded for reverse-return flow . The system bypass would be installed from boiler outlet to suction side of pump.
16 NOTES: 1. BUILDING TEMPERA TURE CONTROLS SUPPLY ELECTRIC POWER T O BUILDING CIRCULA T OR. 2. MAIN FLOW SWITCH PROVES MAIN W A TER FLOW BEFORE ENERGIZING, SEQUENCING AND RESETTING CONTROLS. 3. OUTDOOR THERMOST A T REQUIRED IF BUILDING CONTROLS DO NOT PROVIDE AUTOMA TIC SHUT-DOWN OF RESET CONTROLS DURING W ARM WEA THER.
17 BYP ASS BALANCING With systems where water temperature can be expected to drop appreciably due to long standby periods, or heavy draw down, a bypass pipe of at least 1" size with a balancing cock should be installed between the boiler inlet and outlet (see fig.
18 generator type boilers establish temperature rises. The deciding factor in choice of boiler temperature rise relates to the boiler inlet temperature.
19 FIGURE 14 NO . SUGGESTED ITEMS FOR INST ALLA TION 1. SHORT PIPE NIPPLE AND P AIR OF BOILER LOOP TEES IN PIPING BETWEEN SYSTEM SUPPL Y AND RETURN - ONE SET PER EACH BOILER 2. BOILER PIPE LOOP (See Piping Sizing Data T able 3.) 3. BOILER CIRCULA TING PUMP (See Piping Sizing Data T able 3.
20 USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED. USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED.
21 DURA-MAX - PUMP MOUNT - SINGLE ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
22 DURA-MAX - PUMP MOUNT - DUAL ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
23 DURA-MAX - PUMP MOUNTED - MODULA TING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
24 DURA-MAX - SINGLE ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
25 DURA-MAX - DUAL ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
26 DURA-MAX - MODULA TED FIRING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
27 HOT W A TER SUPPL Y APPLICA TIONS Cer-T emp 80 Recovery Systems W A TER LINE CONNECTIONS This section provides detailed installation diagrams for typical methods of application for the unit using a Cer-T emp 80 Recovery System (for one temperature water).
28 ONE DURA-MAX (MODEL DW) COMMERCIAL BOILER WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT SAFETY FLOW SWITCH AS SHOWN TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULA TOR F AILURE.
29 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH VERTICAL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) SEE P AGE 31 FOR ADDITIONAL PIPING INFORMA TION. CAUTION PUMP MUST BE RA TED FOR SYSTEM OPERA TING TEMPERA TURE AND PRESSURE .
30 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF W A TER SERVICE INTERRUPTION OR CIRCULA TO R F AILURE.
31 FIGURE 24 MANIFOLDING OF MODEL TJV-120M & TJV-200M T ANKS NOTE: PIPE SIZES BETWEEN MANIFOLDS AND BOILER(S) TO BE SELECTED FROM THE CER-TEMP 80 DIAGRAM FOR THE HEA TER MODEL TO BE INST ALLED. ALL PIPING FROM TEES TO BE EQUIDIST ANT TO T ANKS. INST ALL IN ACCORDANCE WITH ALL LOCAL CODES.
32 ST ART-UP AND OPERA TING INSTRUCTIONS W ARNING After placing boiler into operation, the ignition system safety shutoff device must be tested by the following test method. 1. Reset Manual High T emperature Safety Limit Control (High Limit) to the lowest setting.
33 LIGHTING AND OPERA TING INSTRUCTIONS WARNING: HOT W A TER CAN PRODUCE 3rd DEGREE BURNS IN 6 SECONDS A T 140 ° F . (60 ° C). IN CASE OF POWER F AILURE DO NOT A TTEMPT TO OPERA TE BOILER. IMPROPER INST ALLA TION, ADJUSTMENT , AL TERA TION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
34 INTERNAL CONT AMINANTS The system must be internally cleaned and flushed after a new or replacement unit has been installed to remove contaminants that may have accumulated during installation. This is doubly important when a replacement unit is installed into an existing system where Stop Leak or other boiler additives have been used.
35 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign matter . 3. Clean burners with bristle brush and/or vacuum cleaner 3/4" DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Making sure front and rear of burners are installed correctly in burner support brackets.
36 CHECKING HONEYWELL S8600H OR S8610M (NA T . GAS) INTERMITTENT IGNITION CONTROLS NO SP ARK A T PILOT BURNER NO Replace ignition module Is voltage (24 V ac) across the 24 V terrminals on module durin.
37 SP ARK A T PILOT BURNER BUT PILOT WILL NOT LIGHT Ensure all manual shutoff valves are fully open; All filters are clean; All gas connections are gas tight; Pilot tubing is not damaged, obstructed or kinked; and pilot orifice is unclogged. Check for air in gas line, purge (bleed) line if necessary .
38 PILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHT Correct the situation by consulting N O the installation or user ’ s manual Does the pilot flame cover 3/8 ° to 1/2" on how to adjust pilot flame. (10 mm to 12 mm) of igniter/sensor rod? YES Replace ignition NO NO module.
39 CAUTION DO NOT USE A NYLON BRUSH OR OTHER ST A TIC CREA TING MA TERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM HEA TING SURFACES AND VENT . SUCH DEPOSITS ARE FLAMMABLE AND MA Y BE IGNITED BY ST A TIC ELECTRICITY . USE A MET AL BRUSH TO MINIMIZE THE DANGER OF EXPLOSION 1.
40 The time between cleaning will vary from two to six months depending upon water conditions and usage. A change of approximately 5 ° F in the normal temperature rise through the boiler is usually an indication that scale should be removed.
41 DURA-MAX LIMITED W ARRANTY A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this hydronic boiler: 1. If within TEN years after initial installation of.
42.
43.
44 REPLACEMENT P ARTS 5621 W . 1 15TH STREET , ALSIP , IL 60803 PHONE: 800-433-2545 F AX: 800-433-2515 ww w .hotwater .com E-Mail: parts@hotwater .com.
Een belangrijk punt na aankoop van elk apparaat A.O. Smith DB/DW-720-1810 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen A.O. Smith DB/DW-720-1810 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens A.O. Smith DB/DW-720-1810 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding A.O. Smith DB/DW-720-1810 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over A.O. Smith DB/DW-720-1810 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van A.O. Smith DB/DW-720-1810 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de A.O. Smith DB/DW-720-1810 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met A.O. Smith DB/DW-720-1810 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.