Gebruiksaanwijzing /service van het product R8182J van de fabrikant Honeywell
Ga naar pagina of 20
PRODUCT DATA 68- 0105- 2 ® U.S. Registered Trademark Copyright © 2002 Honeywe ll • All Rights Reserved R8182D,E,F,H,J Combination Protectorelay™ and Hydronic Heating Controls GENERAL The R8182 i.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 2 ORDERING INFORMATION When purchasing replacement and modernizatio n products from your TRADELINE® wholesaler or distributor , refer to the TRADELINE® Catalog o r price sheets for complete ordering number .
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 3 68-0105—2 Fig. 1. R8182D,E,F installati on dimensions in in. (mm). Thermostat Anticipator Setting: 0.2A for R8182, 0.4A for each R845A Switching R elay used. Maximum Ambient T emperature (at Element): 250°F (121°C).
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 4 Dial Stop: For restricting range, part no. 4074BRR for R8182D,F ,H . Optional Sp ecifications: R8182D,E,F: Case with l ong dimension horizon tal. R8182H,J: End mounted hinge.
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 5 68-0105—2 Fig. 7. Internal view of R8182H. Fig. 8. Internal view of R8182J. INSTALLATION WARNING Explosion Hazard. Can cause severe injury , death or property damage. This product is intended for use only in systems with a pressure relief va lve.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 6 NOTE: Do not make sharp bends in the tubing. A sh arp bend can break the tubi ng and cause a loss of fill. In models with an adjustable tu bing length, pul l the extra tubing out of the controller case.
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 7 68-0105—2 Fig. 9. Positioning the sensing bulb in the immersion well. WIRING IMPORT ANT Use Underwriters Laboratories Inc. listed connectors when making external circuit connections to the orange and white line voltage burner and ign ition leadwires of the R8182H,J.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 8 Fig. 10. Converting TRADELINE® R8182D ,H to replace other controls. M4526 USING THE TRADELINE® R8182D TO REPLACE R8182F: 1. REMOVE BLUE WIRE FROM THIS TERMINAL AND INSULATE END TO PREVENT CONTACT.
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 9 68-0105—2 Fig. 1 1. R8182D internal sc hematic and wiring di agram. Fig. 12. R8182E internal sch ematic and wiring diagram. M4519 L1 (HOT) L2 1 3 4 2 1 2 3 4 120 VAC POWER SUPPLY.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 10 Fig. 13. R81 82F internal sche matic and wiring diagra m. Fig. 14. R8182H internal schematic and wirin g diagram. M4528 L1 (HOT) L2 1 2 1 2 120 VAC POWER SUPPLY.
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 1 1 68-01 05—2 Fig. 15. R8 182J interna l schematic a nd wiring dia gram. Fig. 16. R8182D,E,F ,H and J in a typical zoning application us ing zone valves. M4529 L1 (HOT) L2 1 1 120 VAC POWER SUPPLY.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 12 Fig. 17. R8182D and R845A in a ty pical multiple circulator zon ing application. OPERATION R8182D A call for heat by the thermost at pulls in relay 1K, which energizes the safety switch circuit and relay 2K to turn on th e burner .
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 13 68-0105—2 R8182J The burner and circulator ope rate whenever the thermostat calls for heat. Relay 2K pulls in. When the cadmium sulfide flame detector sees flame, the sa fety switch heater circuit is bypassed, and 2K is held in throug h 2K1.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 14 Fig. 20. R8182F Aquastat ® limit switching. STARTUP AND CHECKOUT WARNING Explosion Hazard. Can cause severe injury , death or property damage. This product is intended for use only in systems wi th a pressure relief valve.
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 15 68-0105—2 Fig. 21. Setting stop i n position to restrict low limit setting to 180°F (82°C) or lower . Startup WARNING Explosion Hazard. Can cause severe injury , death or property damage.
R8182D,E,F ,H,J COMBINATION PROTECTO RELAY™ AND HYDRONI C HEATING CONTROLS 68-0105—2 16 Section 2. Composition, Information on Ingredients (Table 3). T able 2. Ingredien ts of Heat Conductive Compou nd a . a Additional Information: Part No. 120650 (0 .
R8182D,E,F ,H,J COMBINATION PROTECTO R ELAY™ AND HYDRONIC HEATING CONTROLS 17 68-0105—2 Section 8. Exposure Controls and Personal Protection Ventilation: No special ventilation is requi red when working with this product. Respiratory Protection: None required.
68-0105—2 18.
19 68-0105—2.
68-0105—2 G.R. Rev . 1-02 www .honeywell.com/building/components Automation and Control Solutions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 Printed in U.
Een belangrijk punt na aankoop van elk apparaat Honeywell R8182J (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell R8182J heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell R8182J vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell R8182J leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell R8182J krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell R8182J bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell R8182J kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell R8182J . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.