INSTALLATION INSTRUCTIONS 66- 1085- 3 ® U.S. Registered T rademark Copyright © 2002 Honeywell • All Rights Reserved RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES Relay Modules APPLICATION The Hon eywel.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 2 WARNING Fire or Ex plosion Haza rd. Can cause property dama ge, sev ere injury , or deat h. T o prevent possibl e hazardous burner operation, verify safety requirements each time a co ntrol is inst alled on a bur ner .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 3 66-1085—3 4. All wir ing mu st co mply with all appli cable electric al codes, ordina nces and regula tions . Wiring , where required, must com ply wit h NEC, Class 1 (Line V oltage) wiring.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 4 Fig. 1. Inte rnal block diagram of the RM780 0L/RM7840L (See Fig. 2, 3, 4 or 5 for individ ual deta iled wiri ng instructions ).
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 5 66-1085—3 T able 2. Recommended Groundi ng Practice s. T able 3. T ermina l Ratings. . a The re lay modu le mu st have a n earth ground providin g a co nnection betwe en the subbase and th e cont rol pan el or the equipm ent.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 6 T able 4. Combinat ions for T er minals 8, 9 , 10 and 21. T able 5. Explana tion of Eac h Combination .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 7 66-1085—3 Fig. 2. Wiring subbase and sequence for RM7800 E,L/RM7840E,L . M12261C G L2 3 4 4 5 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 12 LOCKOUT INTERLOCKS (INC.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 8 Fig. 3. W iring subbase and sequen ce for RM7800 G/RM7840 G. RM7800G/RM7840G POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL FIRING RATE MOTOR INITIATE (INITIAL POWERUP ONLY) POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER PFEP 10 SEC.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 9 66-1085—3 Fig. 4. Wiring subbase and sequen ce for RM780 0M/RM7840 M. M12262A G L2 3 4 5 6 7 8 9 10 F (L1) 13 14 15 16 17 18 19 20 21 22 .
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 10 Fig. 5. RM7800 /RM7840 R elay Module exploded vie w . SAFETY SHUTDOWN Safety Shutdown (Lockout) o ccurs if any of the following oc cur du ring the indicated period: 1. INITIA TE Period: a.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 1 1 66-1085— 3 g. Lockout In terloc k opens d uring PREPURGE (RM7840E,L). h. Ignition /pilot valve/i ntermi ttent pi lot valv e term inal is energiz ed. i. Main v alve term inal i s energiz ed.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 12 Ignition Trials 1. Pilo t F lame Es tabli shi ng Peri od ( PFEP ): a. With the firing rate mo tor at the l ow fire p ositio n: (1) The pilot valv e and igniti on transfo rmer , termina ls 8, 1 0 and 2 1, are ene rgized .
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 13 66-1085—3 Keyboard Disp lay Module (VFD) The Keyboard Display Module (see Fig. 5) is provided with the RM7800 R elay Module (but is not requir ed f or operatio n) and is an op tion fo r the RM7840 Rel ay Modu le.
RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES 66-1085—3 14 T able 7. Sit e Configurable J umper Optio ns. a Pilot V alv e /First Sta ge Oi l V alve (V alve/S tart) T erminal 21. b A 30 sec ond MFEP c an be a ccompl ished by addin g a ju mper wire be tween T erminals 19 and 5.
RM7800E,G ,L,M; RM78 40E,G,L,M 780 0 SERIES R ELAY MODULES 15 66-1085—3 T able 8. Static C heckout. Te s t No. RM780 0/ RM7840 Models Te s t Jumper s V oltmete r Normal Opera tion If Operation is Abnormal, Check the Items Listed Be low 1 All None 4-L2 Line volta ge at T erminal 4.
66-1085—3 G.R. Rev . 02-02 www .honeywell.com RM7800E,G ,L,M; RM7840E,G ,L,M 7800 SERIES RELAY MO DULES Autom ati on and Contr ol Solut ions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, M N 55422 Scarborough, Ont ario M1V 4Z9 Printed in U.
Een belangrijk punt na aankoop van elk apparaat Honeywell RM7800M (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell RM7800M heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell RM7800M vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell RM7800M leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell RM7800M krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell RM7800M bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell RM7800M kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell RM7800M . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.