Gebruiksaanwijzing /service van het product S8600 van de fabrikant Honeywell
Ga naar pagina of 20
TABLE 1—INTERMITTENT PILOT IGNITION MODULES. IGNITER- 100 SENSOR TYPE PREPURGE PERCENT LOCKOUT IGNITION MODEL TYPE OF GAS TIMING SHUTOFF TIMING SEQUENCE a S8600A, Separate Natural None No No Spark on until pilot S8610A lightoff or manual S8600F, Combination shutoff; pilot valve S8610F open until manual shutdown.
2 CORROSIVE CHEMICALS Corrosive chemicals can also attack the module and gas control and eventually cause a failure. Where chemicals may be used routinely for cleaning, make sure the cleaning solution cannot reach the controls.
We recommend mounting the module with the terminals down to protect them from dripping water and dust. It can also be mounted with the terminals on either side. DO NOT MOUNT with terminals pointing up. Fasten securely with four No. 6-32 machine or No.
4 Ground Control System The igniter, flame sensor and ignition module must share a common ground with the main burner. Use thermo- plastic insulated wire with a minimum rating of 105 ° C [221 ° F] for the ground wire; asbestos insulation is not accept- able.
5 69-0463 Fig. 3 — S8600A,B; S8610A,B connections in a heating system with an atmospheric burner. Fig. 2 — S8600F,H,M; S8610F,H with a vent damper plug in a heating system with an atmospheric burner and a D80D vent damper.
Fig. 5 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with power-assisted combustion. Fig. 4 — S8600A,B; S8610A,B with vent damper pl u g in an atmospheric burner heating system with a D80D vent damper. 6 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W VENT DAMPER PLUG SPARK 5 S8600A,B; S8610A,B POWER SUPPLY.
Fig. 6 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating system with a two-stage gas control and power-assisted combustion. 7 69-0463 5 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) .
Fig. 7 — S8600F,H,M; S8610F,H; S8660D; S8670D in a heating system with an atmospheric burner and a D80B vent damper. 8 LIMIT CONTROLLER 5 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 5 S8600F,H,M; S8610F,H; S8660D; S8670D 3 POWER SUPPLY.
Fig. 8 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a heating-cooling system with power-assisted combustion. 9 69-0463 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 5 S8600F,H,M; S8610F,H; S8660D; S8670D POWER SUPPLY.
Fig. 9 — S8600F,H,M; S8610F, H; S8660D; S8670D connections in a hydronic heating sytem with a D80D vent damper. 10 2 MV MV/PV PV GND (BURNER) 24V GND 24V TH-W (OPT) VENT DAMPER PLUG (OPT) SPARK 4 S8600F,H,M; S8610F,H; S8660D; S8670D POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 10 — S8600F,H,M; S8610F,H; S8660D; S8670D connections in a commercial water heater control system. 11 69-0463 CHECKOUT Check out the gas control system: • At initial installation of the appliance. • As part of regular maintenance procedures.
call for heat. ❏ Make sure pilot lights smoothly when gas reaches the pilot burner. ❏ Make sure main burner lights smoothly without flash- back. ❏ Make sure burner operates smoothly without floating, lifting, or flame rollout to the furnace vestibule or heat buildup in the vestibule.
13 69-0463 TRIAL FOR IGNITION Pilot Ignition Following prepurge timing (S8660, S8670), or on the call for heat (S8600, S8610), the module energizes the first main valve operator. The first main valve opens, which allows gas to flow to the pilot burner.
14 WARNING When performing the following steps, do not touch stripped end of jumper or SPARK terminal. The ignition circuit generates over 10,000 volts and electrical shock can result. ❏ Energize the module and immediately touch one end of the jumper firmly to the GND terminal on the module.
15 69-0463 • Make sure electrical connections are clean and tight. Replace damaged wire with moisture-resistant No. 18 wire rated for continuous duty up to 105 ° C [221 ° F]. • Check for cracked ceramic insulator, which can cause short to ground, and replace igniter-sensor if neces- sary.
Fig. 15 — S8660, S8670 troubleshooting guide. 16 Check continuity of ignition cable and ground wire. NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout. If checks are okay, replace module.
17 69-0463 Fig. 16 — Representative schematic for S8600F,H, M; S8610F,H. See Fig. 1 for hookup. S8660 and S8670 are similar except the timing circuit includes a purge timer.
Fig. 17 — Representative schematic for S8600A,B; S8610A,B. See Fig. 3 for hookup. 18 L1 (HOT) L2 1 24V TRANSFORMER LIMIT CONTROLLER ON-OFF SWITCH 24V 2 THERMOSTAT OR CONTROLLER 24V (GND) 1K1 1K2 3K2 2K2 3K1 GND (BUR- NER) MV/ PV MV PV IGNITER BURNER GROUND 1 2 POWER SUPPLY.
19 69-0463 EXHIBIT A RECOMMENDED PROCEDURE FOR SAFETY INSPECTION OF AN EXISTING APPLIANCE INSTALLATION AS A PRELIMINARY STEP TO APPLYING AN AUTOMATIC INTERMITTENT PILOT SYSTEM The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in a safe condition for continuing use.
EXHIBIT B PROCEDURE FOR INSTALLING AUTOMATIC INTERMITTENT PILOT SYSTEMS Prior to beginning this procedure, a preliminary ex- amination of the appliance and the automatic intermit- tent pilot system should be made to determine that the automatic intermittent pilot system can be properly applied to the appliance.
Een belangrijk punt na aankoop van elk apparaat Honeywell S8600 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell S8600 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell S8600 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell S8600 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell S8600 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell S8600 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell S8600 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell S8600 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.