1 68-0148—1 B.M. • Rev. 6-94 • ©Honeywell Inc. 1994 • Form Number 68-0148—1 T8131A,B,C; T8132A,B,C Pr ogrammable Thermostats The T8131 and T8132 Thermostats provide energy savings for single-stage heating and cool- ing applications while providing reliable, precise temperature control.
68-0148—1 2 T8131A,B,C; T8132A,B,C SPECIFICATIONS • ORDERING INFORMATION Ordering Information When purchasing replacement and modernization products form your TRADELINE ® wholesaler or your distributor, refer to the TRADELINE Catalog or price sheets for complete ordering information, or specify— 1.
3 68-0148—1 T8131A,B,C; T8132A,B,C SPECIFICATIONS • INSTALLATION Fig. 2—T8131 LED. CYCLES PER HOUR ADJUSTMENT: Heating: Field adjustable to 3, 6, or 9 cph ±10 percent. Cooling: Factory-set at 3 cph ±10 percent (not field adjustable). CALIBRATION: Thermostat and thermometer self-cali- brating to ±1.
68-0148—1 4 Fig. 3—Mounting thermostat mounting plate. T8131A,B,C; T8132A,B,C INSTALLATION WALL WIRES THROUGH WALL OPENING WALL ANCHORS (2) MOUNTING PLATE MOUNTING SCREWS (2) M1718 WIRING All wiring must comply with all applicable electrical codes, ordinances, and regulations.
5 68-0148—1 T8131A,B,C; T8132A,B,C INSTALLATION Fig. 8—2-wire heat-only application (jumper intact). Fig. 10—4-wire heat/cool application (jumper intact). R Rc W Y G B D A C 2-WIRE HEAT-ONLY (JUMPER INTACT) M1709B L1 (HOT) L2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
68-0148—1 6 ADJUST FAN OPERATION SWITCH, AS REQUIRED The thermostat fan operation switch, labeled FUEL SWITCH (see Fig. 12) is factory-set in the “F” position. This is the correct setting for most systems. If this system is an electric heat system, set the switch to “E.
7 68-0148—1 T8131A,B,C; T8132A,B,C INSTALLATION M1719C REMOVING BATTERY DOOR Fig. 14—Installing position for batteries. MOUNTING THE THERMOSTAT To mount the thermostat on the subbase, engage the tabs at the top of the thermostat and mounting plate (see Fig.
68-0148—1 8 T8131A,B,C; T8132A,B,C PROGRAMMING THE THERMOSTAT Pr ogramming the Thermostat T8131A AND T8132A MODELS Set Current Time/Day To set time, press and release Set Clock/Day once, then press Ahead or Back until the current time displays.
9 68-0148—1 T8131C AND T8132C MODELS Set Current Time/Day To set time, press and release Set Clock/Day once, then press Ahead or Back until current time displays. To set day, press and release Set Clock/Day again, and then press Ahead or Back until current day displays; then press Run Program .
68-0148—1 10 T8131A,B,C; T8132A,B,C CHECKOUT AND SETTINGS Checkout and Settings CHECKOUT After the thermostat is mounted on the subbase, check operation as follows: Model Heating A,C B For T8131 models only, first check that the green power LED is lit, indicating the thermostat is powered properly.
11 68-0148—1 T8131A,B,C; T8132A,B,C CHECKOUT AND SETTINGS • TROUBLESHOOTING SETTINGS AND ADJUSTMENTS Set the Fan and System Switches First set the fan switch FAN AUTO: Normal setting for most homes. A single-speed fan will turn on automatically with the air conditioner or furnace.
68-0148—1 12 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario M1P 2V9 Printed in U.
Een belangrijk punt na aankoop van elk apparaat Honeywell T8131C (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell T8131C heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell T8131C vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell T8131C leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell T8131C krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell T8131C bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell T8131C kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell T8131C . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.