PRODUCT DATA 63-2675-03 TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS APPLICATION The TB7100A1000 Mu ltiPRO™ Multispeed and Mu.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 ORDERING INFORMATION When purchasing replacement and modernizat io n products from your TRADELINE® whol esaler or distributor , refe r to the TRADELINE® Catalog or price sheets for complete ordering number .
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 3 63-2675—03 NOTE: Alkaline batteries keep calendar and time if lithium battery is no longer fun ctional. Resistance Characteristics of Remote Sensors: C7189U Remote Indoor Sensor: 10K ohm NTC.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 4 Fig. 4. C71 89U Indoor Sensor d imensions in in. (mm). MERCURY NOTICE If this control is replaci ng a control that contains mercury in a sealed tube, do not place your old control in the trash.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 5 63-2675—03 Fig. 7. Install wallplate. WIR ING CAUTION Electrical Shock Hazard. Can cause electrical shock or eq uipment damage. Disconnect power supply before connecting wiring. IMPORT ANT — All wiring must agree with applicabl e codes, ordinances and regulations.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 6 T able 5. T erminal Designation Description s. NOTES: 1. When used in a single-transformer system, leave metal jumper wire in place between Rc and R. If used on a two-transfo rmer system, remove met al jumper wire between Rc and R.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 7 63-2675—03 Fig. 13. T ypical hookup of heat-only sys tem. Fig. 14. T ypica l hookup of hea t-only system with fan . Fig. 15. T ypical ho okup of cool-onl y system. Heat Pump System Wiring Fig.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 8 Fan Coil System Wiring Fig. 18. T ypica l wiring of 4 pipe fan coi l. Fig. 19. T ypical wiring of 2 pipe fan coil wi th reheat. Fig. 20. T ypic al wiring of 2 pipe fan coil with out reheat.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 9 63-2675—03 Fig. 22. T ypical hoo kup of PT AC with HI and LO fan speed s (2H/1C). POWER THE THERMOSTAT Y ou can choose from three methods to power the thermostat: • Batteries only (AAA alkaline).
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 0 Wire Indoor Sensor CAUTION Electrical Interference (Noise) Hazard. Can cause erratic system operation. Keep wiring at least one foot away from large inductive loads such as motors, li ne starters, lighting ballasts and large power distribution panels.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 11 63-2675—03 Fig. 29. Setting calend ar when thermostat is first powered. Fig. 30. Setting time when thermostat is first powered. INSTALLER SETUP Advanced Settings The thermostat has advanced settings to match the HV AC system.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 2 INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND T ESTS (T ABLE 6) Use the Installer System T est to test the heatin g, cooling and fan. Refer to th e latter portion of T able 6.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 13 63-2675—03 0310 De adband 3°F (2°C) 2 (1.5)—2°F (1.5°C) 3 (2.0)—3°F (2.0°C) 4 (2.5)—4°F (2.5°C) 5 (3.0)—5°F (3.0°C) 6 (3.5)—6°F (3.5°C) 7 (4.0)—7°F (4.0°C) 8 (4.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 4 0 3 4 9 A u t o F a n R e s e t 0 0 — I n a c t i v e 1—Reset back to Auto after 2 hours 2—Reset back to Auto after 4 hours The timer will be set after the user selects the constant fan speed.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 15 63-2675—03 NOTE: Press the Done button to exit the Installer System T est. MAIN SCREEN Fig. 33. Main screen selections. Fig. 34. Main screen display . 0700 T emperature Display Offset 0 -3 (-1.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 6 PROGRAMMING T able 7 shows default program settings. T able 7. Energy-saving Default Program Settings. Fan Settings Auto: Fan runs only w hen heating/ cooling system is on.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 17 63-2675—03 OPERATION Fan Sequence Operations (ISU 347, 348, 349) If heat pump or conventional app lication modes a re enabled in ISU 170, then ISU 347 is not available for fan ramp algorithm.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 1 8 a If Installer Setup (0170) System T ype is set to 2 pipe Fan Coil (8) or 2 pipe Fan Coil w/Aux Heat (9), the Y terminal will be u sed for cooling and heating.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 19 63-2675—03 Special Programmabl e Mode Functions Installer Setup 160 allows the thermostat to be configured for either a mode with a programmable 7 d ay schedule or as a non-programmable thermostat.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 0 Replace the batteries as follows: 1. Remove the thermostat from the base by pulling it straight out. (See Fig. 39.) 2. Install two new AA alkaline batteries with proper polar- ization.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 21 63-2675—03 — Users cannot make changes to the temperature setpoint or any schedule, system, or fan settings. — The only features availabl e are HOLIDA Y and OVERRIDE. — T o unlock the screen, see Advanced Settings secti on.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 63-2675—03 2 2 Fig. 41. 20 K ohm sensor resistance versus temperature. TEMPERA TURE (DEGREES) o F 30 40 50 60 70 80 90 100 110 0 10 20 .
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT 23 63-2675—03 T ROUBLESHOOTING (T ABLE 12) T able 12. T rou bleshooting. Symptom Possible Cause Action Display does not come on. Thermostat is not being powered. Ch eck for 24 V ac between C and Rc.
Automation and Co ntrol Solutions Honeywell Internation al Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Dri ve North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT ® U.
Een belangrijk punt na aankoop van elk apparaat Honeywell TB7100A1000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell TB7100A1000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell TB7100A1000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell TB7100A1000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell TB7100A1000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell TB7100A1000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell TB7100A1000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell TB7100A1000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.