OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC BOOSTER HEATER ELECTRIC HEATER COMPANY BASE MODEL “ B ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: http://www.hubbellheaters.com/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory. WARNING / CAUTION 1.
3 TABLE OF CONTENTS SECTION TITLE PAG E # I GENERAL DESCRI P TI ON AND CONSTRUCTION 5 II INSTAL LATI ON 9 III S C H E D U LE D M A IN TE NANC E AND OPERATION 15 I V TROUBL ES HOOTI NG 17 V S E R V I C.
4.
5 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged electric booster heater that is ty pically used to provide 180 ° F sanitizing rinse water.
6 CONTROL THERMOS TAT The water heater is supplied with an immer sion thermostatic switch that is i nstalled and wired at t he factory. The thermostat can be adjusted through a range of 100° - 195° F and is adjustable with a flat tip screwdriver.
7 OPTIONS The following optional features may be included in y our water heater. Reference included drawing specific to y our heater for further details. Low Water Cut-Off Used as a safet y devi ce, the electroni c low water cut-off is used to detect a low water situation and disengage the operating coils in the magne tic contactor(s).
8 Pressure Reducing Valv e An optional pressure reducing valve with built-in by pass may be supplied. This valve is shipped separately for in-line installation. Stainless Ste el Outer Jacket An optional stainl ess steel outer jacket m ay replace t he standard galvaneel jacket.
9 SECTION II – INSTALLATION WARNING / CAUTION DO NOT TURN ON THE ELECTRI C POWER SUPPL Y to this equipment until heate r is completely filled with water and all air has been re leased. If the heater is NOT fille d with water when the power is turned on, the heating elements will burn out.
10 of water. To over come this condition, it is recommended that a 3/8” by -pass arrangement with a horizontal check valve be installed around the pressure regulator. This will prevent annoy ance caused by the relief valve dripping or blowing off. 3.
11 FINAL CHECKS 1. Check all connections for tightness. 2. Ensure that all the above steps are completed 3. After the wa ter is heated f or the first time, monitor the water te mperature as described in S e ct i o n III, Q u a rt e r l y In s p e c t i on.
12 1 – Terminal Block 2 – Magnetic Contactor 3 – Heating Element 4 – Low Water Cut-Off, if supplied 5 – Transformer, 480-Volt/240-Volt, installed on 480-Volt models with low water cut-off on.
13 1 – Terminal Block 2 – Magnetic Contactor 3 – Heating Element 4 – Low Water Cut-Off, if supplied 5 – Transformer, 480-Volt/240-Volt, installed on 480-Volt models with low water cut-off on.
14.
15 SECTION III - SCHEDULED MAINTE NANCE AND OPERATION WARNING / CAUTION Before performing any maintenance procedure, make certain power supply is OF F and cannot accidentally be turned on. MAINTENANCE AND OPERATION The water heater is automatic in its operation.
16 ANNUAL INSPECTION 1. Flush tank as follows a. Shut off power supply . b. Close valve on hot water outlet piping. c. Open valve on drain piping. d. Cold water inlet line pressure will be strong enough to flush sediment from the bottom of the tank out through the drain.
17 SECTION IV – TROUBLESHOOTING Symptom Probable Cause Corrective Action / Remedy Circuit breaker tripped at source. Reset circuit breaker. Blown fuse in transformer, if installed. Replace fuse. High limit switch tr ipped. Reset hig h limit switch. Loose wires.
18 Faulty thermostat. Che ck thermostat a djustment. Monitor thermostat as described i n S e c t i o n III, Q u a rt er l y I nspection. Replace if necessary .
19 SECTION V - SERVICING & REPLACEMENT OF PARTS WARNING / CAUTION Before servicing or replacing any part make sure to turn the power supply switch to the OF F position. SURFACE TEMPERATURE HIGH LIMIT CUT -OFF 1. Disconnect power from unit. 2. Remove access cover.
20 HEATING ELEM ENT 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Attach hose to drain connection. 4. Lift manual release lever on relief valve to let air into sy stem or break union on outgoing water line. 5. Drain water from tank.
21 IMMERSION THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Remove high limit c over screw and cover. Cover Cover Screw 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell.
22 MAGNETIC CONTACTOR 1. Disconnect power from unit. 2. Disconnect line and load wires to contactor. 3. Disconnect two (2) 14 gaug e control circuit wires. Control Wires Line Wires Load Wires 4. Loosen two (2) holding screws and remove contactor. Mounting Screws (Bottom screw not shown) 5.
23 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one. 6. Connect overflow piping.
24 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS ELEMENT CHA RT Power (kW) Resistance (Ohms) Element Part # 208V 240V 480V I mmersion L ength Hairpin 1 Φ 3 Φ DELTA 3 Φ WYE CH-FO 608 6 ---- ---- 13 3/8" 7.2 7.2 ---- ---- CH-FO 604 4.5 6 ---- 13 3/8" 9.
25 TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.
Een belangrijk punt na aankoop van elk apparaat Hubbell Electric Heater Company B (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hubbell Electric Heater Company B heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hubbell Electric Heater Company B vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hubbell Electric Heater Company B leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hubbell Electric Heater Company B krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hubbell Electric Heater Company B bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hubbell Electric Heater Company B kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hubbell Electric Heater Company B . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.