1 PRINTED IN U.S.A. 1212 P ART NO. 325370-000 MODELS BBCN375T754NV PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND NOTIFY OWNER T O KEEP FOR FUTURE REFERENCE.
2 FOREWORD The design of model BBCN375T754NV complies with the current edition of ANSI Z21.10.3/CSA 4.3 as automatic storage or automatic circulating tank type water heaters. Installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping necessary .
3 GENERAL SAFETY INFORMA TION PRECAUTIONS DO NOT USE THIS W A TER HEA TER IF ANY P ART HAS BEEN UNDER W A TER. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water .
4 INSULA TION BLANKETS Insul ation bl ankets available t o the gene ral publi c for exte rnal use on gas wa ter heater s are not requ ired for us e on your water he ater . The p urpos e of an insulat ion blan k et is to re duce th e standby hea t los s encou ntered wit h storage t ank water heate rs.
5 installed in a carpeted alcove or closet, the entire oor shall be covered by the panel. Also, see the drain requirements. THI S HE A T ER SHA LL BE LOCA TE D OR PROTECTED SO IT IS NOT SU BJECT TO PHYSIC AL DAM AGE BY A MOVIN G VEHIC LE.
6 CAUTION: IF BUILDING COLD W A TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V AL VE OR WA TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED. FIGURE 3. CIRCULA TING RETURN LINE CONNECTIONS TEMPERED W A TER LOOP , IF USED, CONNECT TO POINT "A".
7 THERMOMETERS (Not Supplied) The rmom eters sho uld be obt ained an d fie ld insta lled as sho wn in Figure 3. Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply . COMBINA TION W A TER (POT ABLE) HEA TING AND SP ACE HEA TING 1 .
8 FIGURE 4. WIRING DIAGRAM AND SCHEMA TIC HEA TER WIRING All electrical work must be installed in the United States in accordance with the current edition of the National Electrical Code ANSI/NFP A No. 70, in Canada, with the current edition of Canadian Electrical Code CSA C22.
9 T ABLE 4. GAS SUPPL Y LINE SIZES (IN INCHES)* MAXIMUM CAP ACITY OF PIPE IN CUBIC FEET PER HOUR BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material acceptable for the purpose in locating the leaks.
10 5. W ait ve (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to next step.
11 SETTING THE W A TER HEA TER TEMPERA TURE A T 120°F (49°C) (APPROX. " " MARK ON F ACE OF THE TEMPERA TURE ADJUSTING DIAL) WILL REDUCE THE RISK OF SCALDS. Some States or Provinces require settings at specic lower temperatures. Figure 6 shows the approximate water temperatures produced at various thermostat settings.
12 1. Provide complete combustion of gas. 2. Cause rapid ignition and carryover of ame across entire burner. 3. Give reasonably quiet operation during ignition, burning and extinction.
13 BLOWER MAINTENANCE For safety and satisfactory operation it is recommended that the blower be checked once a year by a competent service person. 1. MOTOR - The motor is factory oiled and sealed and requires no further maintenance. 2. WHEEL - Wheel must be clean of soot, ash or any other coating which inhibits either rotation or air ow .
14 T ANK CLEANOUT PROCEDURE The following practices will ensure longer life and enable the unit to operate at its designed efciency: 1. Once a month the heater should be ushed. Open the drain valve and allow two gallons of water to drain from the heater .
15 cold water inlet line and allow water to ow through heater and out drain valve. Don’t forget to plug vent and cap opening in Flo-Jug. 9. When ushing is completed: • Fill heater being certain to expel air from tank through a nearby hot water faucet or , if removed, the relief valve opening.
16 NOT E: Ano de must remai n install ed ( exce pt for inspe ctio n ) to avoid sh or tening ta nk life. See LI MITED WAR R ANT Y . Re place as necessary . SERVICE AND REP AIR The wate r heater req uires no sp ecial c are oth er than th e norma l mainte nance as n oted above.
17 TROUBLESHOOTING For your safety , water heater service should be performed only by a qualied service technician. Read the GENERAL SAFETY INFORMA TION section rst . PROBLEM POSSILBE MALFUNCTION SER VICE T O BE PERFORMED NOT ENOUGH OR NO HOT W A TER 1) Blower will not run.
18 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below . For your safety , water heater service should be performed only by a qualied service technician. Read the GENERAL SAFETY INFORMA TION section rst. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLEM SOLUTION Inadequate or no earth ground 1.
19 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below . For your safety , water heater service should be performed only by a qualied service technician. Read the GENERAL SAFETY INFORMA TION section rst. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLE MS OLUTION Ignition/flame failure.
20 TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below . For your safety , water heater service should be performed only by a qualied service technician. Read the GENERAL SAFETY INFORMA TION section rst. INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL PROBLE MS OLUTION 15 # LED ST AT US B C D E F 1.
21 NOTES.
22 NOTES.
23 Limited W arranty American W ater Heater Company , the warrantor , extends the following LIMITED WARRANTY to the owner of this water heater . 1. THE T ANK If the glass-lined tank in this water heat.
24 P .O. Box 1597, Johnson City , TN 37605 Phone: 800-456-9805 • Fax: 800-999-5210 www .americanwaterheater .com Copyright © 2012 American Water Heater Company .
Een belangrijk punt na aankoop van elk apparaat American Water Heater Commercial Ultra Low NOx Gas water Heater (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen American Water Heater Commercial Ultra Low NOx Gas water Heater heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens American Water Heater Commercial Ultra Low NOx Gas water Heater vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding American Water Heater Commercial Ultra Low NOx Gas water Heater leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over American Water Heater Commercial Ultra Low NOx Gas water Heater krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van American Water Heater Commercial Ultra Low NOx Gas water Heater bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de American Water Heater Commercial Ultra Low NOx Gas water Heater kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met American Water Heater Commercial Ultra Low NOx Gas water Heater . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.