Gebruiksaanwijzing /service van het product LM8M/LMLM*MP van de fabrikant Johnson Controls
Ga naar pagina of 28
368261-UIM-A-0508 EFFICIENCY RATING CERTIFIED ISO 9001 Certified Quality Management System RESIDENTIAL GAS FURNACE WITH PSC MOT OR MODELS: TM8M/TMLM*MP , YM8M/YMLM*MP , CM8M/CMLM*MP , LM8M/LMLM*MP (80% Modulating Multi-position / Low NOx) INSTALLATION MANUAL LIST OF SECTIONS SAFETY .
368261-UIM-A-0508 2 Johnson Controls Unitary Products SPECIFIC SAFETY RULES AND PRECAUTIONS 1. Only Natural gas or Propane (LP) ga s are approved for use with this furnace. 2. Install this furnace only in a location and position as specified in these instructions.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 3 CODES AND ST AND ARDS Follow all national, local codes and standar ds in addition to this installa- tion manual. The installation must co mply with regulations of the serv- ing gas supplier , local building, heat ing, plumbing, and other codes.
368261-UIM-A-0508 4 Johnson Controls Unitary Products FURNA CE LOCA TION AND CLEARANCES The furnace shall be locat ed using the following guid elines: 1. Where a minimum amount of air intake/vent piping and elbows will be required. 2. As centralized with the air distribution as possible.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 5 DUCT FLANGES Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment.
368261-UIM-A-0508 6 Johnson Controls Unitary Products For horizontal left hand applications no conversion is required to an MC coil when used with a downflow/horiz ontal furnace. A mounting plate, supplied with every coil should al ways be installed on the side desig- nated as top side.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 7 BOTT OM RETURN AN D A TT IC INST ALLA TIONS Bottom return applications normally pull return air through a base plat- form or return air plenu m. Be sure the return platform structure or return air plenum is suitable to support the weight of the fur nace.
368261-UIM-A-0508 8 Johnson Controls Unitary Products SECTION III: FIL TE RS FIL TER INST AL LA TION All applications require the use of a field installed filter . All filters and mounting provision must be field supplied. Filters must be installed external to the furnace cabinet.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 9 HORIZONT AL APPLICA TION Horizontal Filters Any branch duct (rectangular or r ound duct) attached to the plenum must attach to the vertical plenum before the filter . The use of straps and / or supports is required to support the weight of the external filte r box.
368261-UIM-A-0508 10 Johnson Controls Unitary Products HIGH AL TITUDE NA TURAL GAS ORIFICE CONVERSION The National Fuel Gas Code requires that gas appliances installed above 2,000 feet elevation have thei r inputs de-rated by 4% per 1,000 feet above sea level.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 11 SUPPL Y VOL T AGE CONNECTIONS 1. Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/national electrical codes. The switch shoul d be close to the unit for conve- nience in servicing.
368261-UIM-A-0508 12 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V oltage System Wiring” document available online at www .
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 13 FIGURE 21: Thermostat Chart - T wo St age Air Conditioner – V ariable Speed or PSC Modulating Furnace C 24 – Volt Comm on Y1 First Stage Co .
368261-UIM-A-0508 14 Johnson Controls Unitary Products FIGURE 22: Thermostat Chart - T wo Stage Air Conditioner with Single S t age Ther mostat – V ariable Speed or PSC Modulating Furnace HM1 Humidi.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 15 FIGURE 23: Thermostat Chart - Single S tage Heat Pump – V ariable S peed or PSC Modulating Furnace C 24 – Volt Common R 24 – Volt Hot Y1 First Stage Co mp ressor O Reversing Valve Energized in Cool L Malfunction Ligh t G Fan *DP32H70124 THERMOSTAT W1 Second St age Aux.
368261-UIM-A-0508 16 Johnson Controls Unitary Products FIGURE 24: Thermostat Chart - Single S tage Heat Pump – V ariable S peed or PSC Modulating Furnace C 24 – Volt Comm on R 24 – Volt Hot Y1 First Stage Comp ressor O Reversing Valve Energized in Cool L Malfunction Ligh t G Fan *DP32H70124 THERMOSTAT W1 Second St a ge Aux.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 17 FIGURE 25: Thermostat Chart - T wo Stage Heat Pump – V ariable S peed or PSC Modulating Furnace O Reversing Valve Energized in Co ol C 24 – .
368261-UIM-A-0508 18 Johnson Controls Unitary Products ACCESSOR Y CONNECTIONS The furnace control will allow power- switchin g control of various acces- sories. ELECTRONIC AIR CLEANER CONNECTION T wo 1/4” (0.64 cm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 19 An unconfined space is not less than 50 cu.ft (1.42 m 3 ) per 1,000 Btu/ hr (0.2928 kW) input rating for all of the appliances inst alled in that area.
368261-UIM-A-0508 20 Johnson Controls Unitary Products 2. One permanent openings, commencing within 12 in (30.5 mm)of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 in (2.54 cm) from the side s and back and 6 in (15.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 21 6. Remove the burner assembly . It sh ould be possible to swing the burner assembly out of the way without disconnecting the r emain- ing wires. 7. With the burner assembly out of the way , simply slide the N Ox screens out of the heat exchanger tubes and discar d the screens.
368261-UIM-A-0508 22 Johnson Controls Unitary Products T ab le 10: Gas Rate (CU FT/HR) at Full Inpu t Seconds For 1 Revolution Size of T est Dial Seco nds For 1 Revolution Size of T est Dial 1 Cu Ft 2.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 23 ADJUSTMENT OF MANI FOLD GAS PRESSURE * The gas line pressure MUST BE • 7” W .C. (1.74 kP A) for Natural Gas • 1 1” W .
368261-UIM-A-0508 24 Johnson Controls Unitary Products ADJUSTMENT OF F AN CONTROL SETTINGS Cooling - The airflow delivered by the furnace during cooling operation can be adjusted to match the cooli ng capacity of the A/C condensing unit. This is done by moving the CO OL jumper on the control board to give the desired airflow .
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 25 PRESSURE CONTROLS Pressure Sensor - This furnace is equipped with a pressur e sensor in the burner compartment near the combustion blower . This sensor mon - itors combustion airflow through furnace and piping systems.
368261-UIM-A-0508 26 Johnson Controls Unitary Products Three Red Flashes - S tuck open pressure switch. This indicates that the pressure switch is open wh en it should be closed.
368261-UIM-A-0508 Johnson Controls Unitary Produ cts 27 SECTION XI: REPL ACEMENT P ARTS LIST DESCRIPTION MOTOR MOTOR, DIRECT DRIVE BLOWER BLOWER, COMBUSTION ELECTRICAL CAP ACITOR, RUN SWITCH, LIMIT CO.
Subject to change without notice. Printed in U.S.A. 368261-UIM-A-0508 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Contro ls Unit a r y Prod uc t s 5005.
Een belangrijk punt na aankoop van elk apparaat Johnson Controls LM8M/LMLM*MP (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Johnson Controls LM8M/LMLM*MP heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Johnson Controls LM8M/LMLM*MP vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Johnson Controls LM8M/LMLM*MP leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Johnson Controls LM8M/LMLM*MP krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Johnson Controls LM8M/LMLM*MP bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Johnson Controls LM8M/LMLM*MP kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Johnson Controls LM8M/LMLM*MP . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.