DVPDNET -SL DeviceNet Network Scanner Operation Manual DVP-0204520-02.
.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 1 W ar ning Please r ead this instruction car efully befor e use and follow th is instruction to operate the device in or der to pr event damages on the device or injuries to staff. Switch off the power befor e wiring.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 2 3.2 Installing DVPDNET -SL and DVP-SV MPU on DIN Ra il .............................................. 7 3.3 Connecting to DeviceNe t Connecti on Port ....................................
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 3 1 Introduction 1. T o ensure correct inst allation and operation of DVP DNET -SL, please read this chapter carefully before usi ng your DVPDNET -SL. 2. This chapter only provides introductory i nformation on DVPDNET -SL.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 4 1.3 I/O Scan List Item Explanation Software screen Scan T able Before DVPDNET -SL start s its operation, you have to configure it s scan list through the configuration sof t ware. The scan list is a list consisting of the information of slave devices with data, e.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 5 Electrical specification V oltage 1 1 ~ 25 VDC supplied by the po wer cable in the network Current 28mA (typical), 125mA impulse cu.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 6 2.3 DeviceNet Connection Port The connector is used on t he connection to Device Net. Wire by using the co nne ctor enclosed with DVPDNET -SL. PIN Signal Color Content 1 V - Black 0 VDC 2 CAN_L Blue Signal- 3 SHIELD - Shielded 4 CAN_H White Signal+ 5 V+ Red 24 VDC 1 2 3 4 5 2.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 7 DVPDNET-SL. z When DVPDNET-SL is operating, changing the setting of the function switch wil l be invalid. z Use slotted screwdriver to adju st the DIP switch carefully in case you scrat ch th e swit ch.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 8 DVPDNET 35mm DIN r ai l DVP28SV RUN STOP 3.3 Connecting to DeviceNet Connection Port The colors on the PINs on the DeviceNet conn ection port match the colors of the conne ction cables.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 9 Mapped D registers DVPDNET -SL index Output mapping Input mapping 4 D7750 ~ D7997 D7500 ~ D7747 5 D8250 ~ D8497 D8000 ~ D8247 6 D8750 ~ D8997 D8500 ~ D8747 7 D9250 ~ D9497 D9000 ~ D9247 8 D9750 ~ D9997 D9500 ~ D9747 4.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 10 PORT2 PORT1 Dev i c eN et VFD-B DVP28SV DVPDNET DVP28SV RUN STOP L N 0V R T U - D N E T D V P - 1 6 S P L N 0V X0 X1 Y0 DVP-PS0 1 DVP-1 6SP RTU-DNET IFD9502 DVP-PS0 1 DVPDNET- SL RS-232 Node 02 Node 01 Node 03 De viceN et net wor k conf igu rat io n too l 2.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 11 (3) Set up the communication pa rameters in the PC and DVP-SV , e.g. the communication port, address, baud rate and communication format.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 12 (5) Click on “OK”, and DeviceNetBuilder will start to scan the e ntire network. (6) If the bar on the dialog box does not progress, it mean s the connection between the PC and DVP-SV is abnormal, or there are other program s also using the CO M port on the PC.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 13 (8) Click on “IO Configure … ” button in “Nod e Conf iguration” dialog box, and you will then see “RTU Configuration” page. (9) Click on “Scan IO”, and the "Warning” dialog box will appear.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 14 (11) Double click on RTU-DNE T icon, and you will then see “RTU Setup” dial og box.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 15 Item Function Default DIDO Output Points (Y) The digital ou tput point s shall be 8’ s multiple. The n umber will be regarded as 8 when it is less than 8 and rega rded as 16 when it is bigger than 8 but less than 1 6.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 16 (16) Confirm the pa ram eters and I/O data in VFD-B a nd cli ck on “OK”. 2. Configuration of DVPDNET -SL (1) Double click on DNET Scanner (node 01), and th e “Scan Module Configur ation.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 17 (3) Confirm all the settings and cli c k on “OK”. Nex t, downlo ad the configuration to DVPDNET -SL. If DVP-SV is in RUN mode while you are downloadin g the configuration, a “W arning” dialog box will appear .
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 18 Slave → DVPDNET -SL Register in DVPDNET -SL Devices in slave D6037H Digital I/O module X0 ~ X7 on DVP-16SP D6037L N/A D6038H S tatus.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 19 Target When X0 = On, VFD-B will st art to run, and Y0 indicator will be O n. When X1 = On, VFD-B will stop, and Y0 indicator will be Of f.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 20 6 Sending Explicit Message from Ladder Diagram DVPDNET -SL supports the sending of explicit messages through WPL programs.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 21 1. S tructure of request message See the table below: Request Message PLC device 15 14 13 12 11 10 98 7 6 5 4 3 2 1 0 D6250 ReqID Comm.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 22 S tatus Explanation 0 No explicit message is sent out. 1 The communication of explicit message is su ccessful. 2 The explicit message is being sent out. 3 Error: No response from the t arget equipment.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 23 Compulsory settings in IFD9502 Parameter Set value Explanation Node address 02 Set the node address of IFD9502 to “02". Baud rate 500kbps Set the communication speed of IFD9502 and bus to “500kbp s”.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 24 (4) Program explanations: In the beginning of the program, clear the response message editing area and requ est message editing area to 0.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 25 Parameter Set value Explanation 02-01 03 The operation commands are operated on the comm unication interface. Operation by keys is valid. 09-00 01 Communication add ress of VFD-B: 01 09-01 03 Baud rate: 38,400 09-04 03 Modbus R TU mode.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 26 editing area to 0. When M1 = On, DVPDNET -SL will send out re qu est message. W rite 0004Hex into Class 99 >> Instance 1 >> Attribue 2 of the target equipm ent (node address: 02 ).
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 27 Corresponding nodes on th e netwo rk PLC device b15 b14 b13 … b1 b0 D6032 Node 15 Node 14 Node 13 … Node 1 Node 0 D6033 Node 31 No.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 28 LED status Indication How to correct Red light blinking Error in com munication Check the digital indicator and elimin ate the error . Red light on Network error; cannot check duplicate ID; bus-off (che k the digital indicator) 1.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 29 Code Indication How to correct F2 Low volt age is detected. Check if the power of DVPDNET -SL and PLC MPU is normal. F3 Entering te st mode Switch IN1 from On to Off and re-power DVPDNE T -SL.
DeviceNet Network Scanner DVPDNET -SL DVP-PLC Operation Manual 30 MEMO.
Een belangrijk punt na aankoop van elk apparaat 2nd Ave. DVP-0204520-02 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen 2nd Ave. DVP-0204520-02 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens 2nd Ave. DVP-0204520-02 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding 2nd Ave. DVP-0204520-02 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over 2nd Ave. DVP-0204520-02 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van 2nd Ave. DVP-0204520-02 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de 2nd Ave. DVP-0204520-02 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met 2nd Ave. DVP-0204520-02 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.