TECHNICAL & SER VICE MANUAL DUCTLESS SPLIT -TYPE AIR CONDITIONERS CONTENTS 1. FEA TURES ·························································2 2. TECHNICAL CHANGES ····································3 3.
2 1 FEA TURES This “2 to 1” Multi system consists of a single outdoor unit with two compressors that permit up to two indoor units to be installed separate rooms, each with its own controller . 1.SP ACE-SA VING LA YOUT T wo indoor units are served by a single outdoor unit whose installation requires only minimum space.
3 2 TECHNICAL CHANGES 3 P ART NAMES AND FUNCTIONS OUTDOOR UNIT MUM18NW MSM18EW ➔ MSM18NW 1. Indoor unit has been changed. 2. Outdoor unit has been changed. 3. Remove controller has been changed. (The timer function was changed to the clock timer function.
4 4 SPECIFICA TIONS Model MSM18NW SINGLE DOUBLE Cooling capacity w 1 BTU/h 8,400 8,400 ✕ 2 850 1,700 9.9 10.0 MS09NW ✕ 2 White 1 15,60,1 15 0.5 0.37 208-265-328 177-226-279 – 5/8 32-1/16 7-3/16 10-13/16 18 Max.
Models Indoor air Outdoor intake air DB temperature ( ˚F ) MS09NW 71 67 63 TC 10.3 9.74 9.16 SHC 5.93 6.91 7.72 TPC 0.76 0.71 0.68 TC 9.61 9.07 8.48 SHC 5.55 6.44 7.16 TPC 0.83 0.79 0.75 TC 9.03 8.4 7.9 SHC 5.21 5.95 6.66 TPC 0.89 0.85 0.81 TC 8.4 7.
6 3.CONDENSING PRESSURE AND SUCTION PRESURE (ONE INDOOR UNIT WITH ONE OUTDOOR UNIT) Data is based on the condition of indoor humidity 50%. Air flow should be set at HI.
7 Model Unit Single Double MSM18NW 8,400 8,400 ✕ 2 0.71 0.71 0.85 1.70 0.815 1.63 6.64 7.16 ✕ 2 260 270 75 75 194 191 1 16 1 18 64 54 60 60 57 57 Cooling MS09NW 1 15 . 60 . 1 0.035 ✕ 2 0.34 ✕ 2 MUM18NW 208/230 . 60 . 1(3-wire) 1.0 172 25 ✕ 2 1lds 14oz ✕ 2 80 67 1,230 279 95 — 900 1,150 Btu/h — kW kW A kW A A psi .
8 4.OPERA TING RANGE ( 1 ) POWER SUPPL Y ( 2 ) OPERA TION 5.ADDITIONAL REFRIGERANT CHARGE (R-22(oz)) Indoor unit 1 15V 60Hz 1 [ 208/230V 60Hz 1 [ (3wires) Min.
9 6 OUTLINES AND DIMENSIONS MODEL : MUM18NW OUTDOOR UNIT REAR VIEW Unit center Refrigerant pipe(Flared) { 3/8 Refrigerant pipe(Flared) { 1/4 7/8 Wiring hole { 3-7/8 NOTE : The symbol { indicates diameter .
10 7 WIRING DIAGRAM OUTDOOR MODEL MUM18NW WIRING DIAGRAM F NR 1 15V 3 4 BLK BRN 2 1 BLU GRY N ❈ ❈ ❈ BLK ORN YL W X2 X1 2 2 6 6 4 4 YL W BLU L2 BLU RED TB3 TO INDOOR UNIT No.
11 8 REFRIGERANT SYSTEM DIAGRAM MS09NW ✕ 2/ MUM18NW Unit : inch Indoor unit Outdoor unit Indoor heat exchanger Indoor coil thermistor RT12 Room temperature thermistor RT1 1 Flared connection Flared .
12 9 TROUBLESHOOTING MUM18NW 9-1 Cautions on troubleshooting 9-1-1 Before troubleshooting, check the followings: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 9-1-2 T ake care the followings during servicing.
13 Compressor and outdoor fan do not operate.(Only indoor fan operates.) Check of outdoor unit Press EMERGENCY ON/OFF button. 3-minute time delay works. T est mode operates for 30 minutes. Check the outdoor fan motor , compressor , relay , contactor , and wiring.
14 10 DISASSEMBL Y INSTRUCTIONS OUTDOOR UNIT MUM18NW 1. Removing of the cabinet (1)Remove the set screws of the valve cover to remove the valve cover as shown in Photo 2. (2)Remove the set screws of the side panel to remove the side panel and cabinet.
15 OPERA TING PROCEDURE PHOTOS Photo 5 Photo 6 3. Removing the outdoor fan motor . (1) Remove the cabinet. (Refer to 1) (2) Remove the propeller . (Refer to 2) (3) Disconnect the connector remove the clamp of out- door fan motor lead wire. (4) Remove the screws fixing the outdoor fan motor .
16 OPERA TING PROCEDURE PHOTOS Photo 7 Photo 8 4. Removing the compressor (1)Disconnect the cord connector . (See Phot 5) (2)Remove the set screws of the relay panel. (3)Remove the set nuts of the terminal cover . (4)Pull up the compressor . (5)Pull out the lead wires from the compressor terminal to remove overcurrent relay .
17 1 1 P ARTS LIST OUTDOOR UNIT P ARTS MUM18NW Refer to MS09EW for indoor unit. No. Parts No. Remarks Parts Name Symbol in Wiring Diagram Q , ty/unit MUM18NW 1 2 3 4 5 6 7 8 9 10 1 1 12 13 14 15 16 17.
18 12 OPTIONAL P ARTS 10ft 16ft 23ft 33ft 3/8 1/4 C 13/16 D 1-1/16 MAC - 440PI MAC - 441PI MAC - 442PI MAC - 443PI MS09NW 0 1 Pipe length Cross-section Part No. Model A-Gas B-Liquid Pipe size O.D Insulation Additional refrigerant charge R-22(Oz) 1. REFRIGERANT PIPES The air conditioner has flared connections its indoor and outdoor sides.
OB202-1.qxp 26/9/97 11:08 AM Page 19.
New publication, effective Sep. 1997. Specifications subject to change without notice. The Slim Line. From Mitsubishi Electric. L I S T E D R C Copyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications are subject to ch ange without notice.
Een belangrijk punt na aankoop van elk apparaat Mitsubishi Electronics MUM18NW (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Mitsubishi Electronics MUM18NW heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Mitsubishi Electronics MUM18NW vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Mitsubishi Electronics MUM18NW leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Mitsubishi Electronics MUM18NW krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Mitsubishi Electronics MUM18NW bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Mitsubishi Electronics MUM18NW kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Mitsubishi Electronics MUM18NW . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.