Gebruiksaanwijzing /service van het product 47-116-17 van de fabrikant Ariston
Ga naar pagina of 59
Installation Instructions T ype C Boilers G.C.N: 41-116-03 47-116-17 LEA VE THESE INSTRUCTIONS WITH THE END-USER Condensing Countr y of destination: GB 275.
2 275 This manual is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted b y the user and our authorised personnel.
The technical inf or mation and instructions provided herein belo w are intended f or the installer so that the unit may be installed correctly and saf ely .
= 181 20 65 65 155 (A-B-D-E) 208 (C) 67 67 100 = 2.3. O VERALL D IMENSIONS F IG . 2.1 24 MFFI 24 RFFI SYSTEM 4 275 The appliance ma y be installed in any room or indoor area, although par ticular attention is dra wn to the requirements of the current I.
F asten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit lev el be used to position the boiler so that it is perf ectly lev el. F or additional information, please consult the instructions contained in the connection kit and the flue kit.
6 275 2.8. W A TER C ONNECTIONS L EGEND : A = Central Heating Flow B = Domestic Hot W ater Outlet C = Gas Inlet D = Domestic Cold W ater Inlet) E = Central Heating Return F = Cylinder Flo w G = Cylind.
7 275 In F IG . 2.11 below , sev eral diff erent types of flue systems are shown. F or additional information regarding the flue accessories, please consult the Flue Pipe Accessories manual.
8 275 F IG . 2.11 2.10. A CCESSOR Y C ONNECTION T o carr y out the connection f or the roomstat or the outdoor sensor , proceed as f ollows: 1. Unscrew the scre ws “A” and rotate the control panel f orwards; 2.
9 275 Ref er to the illustrations in section 2.10.1. 1. Unscrew the scre ws “A” and rotate the control panel f orwards. 2. Inser t the connecting cable of the under floor heating sensor into the cable gland “B” and open the lid of the instrument panel after having unscre wed the f astening screws “C” .
L EGEND : A: JUMPER When needed, the P .C .B . allows the diff erent options to be selected by means of a wire link. The boiler has the f ollowing basic arrangement: 1 OPEN 2 CLOSED (jumper) 3 OPEN 4 OPEN 5 OPEN 6 OPEN 7 CLOSED 8 OPEN (MFFI); CLOSED (SYSTEM) N OT E : under absolutely no circumstances must jumpers 2, 7 and 8 be remov ed.
11 275 2.12. W A TER C IRCUIT D IA GRAMS L EGEND : 1- F a n 2 - Main Heat e xchanger 3 - Ignition/detection electrode 4 - Burner 5 - Gas valv e 6 - Heating return temperature probe 7 - Heating flow te.
12 275 3. COMMISSIONING 3.1. I NITIAL P REP ARA TION MTS (GB) Limited suppor t the initiative . Within the inf or mation pack y ou will find a cop y of the logbook. It is impor tant that this is completed in the presence of your customer , they are sho wn how to us it, and it is signed b y them.
3.3. C ONTROL P ANEL A. Selector Knob f or Summer/Winter/Flue T est Modes B. Domestic Hot W ater T emperature Adjustment Knob C . Central Heating T emperature Adjustment Knob D . On/Off L.E.D . E. On/Off Knob F . “COMFOR T” Function Push-button/heating only (RFFI SYSTEM) G.
14 275 3.5. D ISPLA Y :M ESSA GES S HO WN D URING N ORMAL O PERA TION 3.6. O PERA TING P ARAMETERS 3.6.1. C ONTROL M ODES During operation of the boiler , while it is carrying out its nor mal operatio.
+20 20 -20 1 2 3 4 5 6 7 8 9 60 100 The type of cur v e is entered by means of the controls of the displa y P .C .B located under the lid of the P .C.B. itself. T o access the programming b uttons (+ / -), raise the lid with a screwdriv er as shown in the illustration.
16 275 The general conditions to f ollow upon installation are the f ollowing: W arning (see 3.7.2) * The curves 1,2,3,4,5,6 could be set in the low er temperature; * The curves 5,6,7,8,9 could be set in the upper temperature; CUR VE 1: under floor heating (radiant panels at ultra-lo w temperature).
17 275 3.7.2. S ETTING THE T EMPERA TURE F IELD Remov e the protection of the displa y using a screwdriver as a le v er . Press the reset button f or ov er 5 seconds.
The pump ov errun may be v aried (after the burner has been tur ned off). T o access this function, it is necessar y to press the reset b utton f or ov er 5 seconds and then press it repeatedly until the character “ A A ” appears on the left-hand display .
19 275 The draining of the heating system must be carried out as f ollows: - T urn off the boiler and the bipolar switch; - Loosen the automatic air release valv e (27); - Open the system's discharge valv e (18) and gather the water that comes out in a container ; - Empty out from the lowest points of the system (where provided).
20 275 4. GAS ADJUSTMENTS 4.1. O VERALL V IEW 4.2. P RELIMINARIES T ype of appliance Marking on the label of characteristics Fur ther indications F actory setting for the W obbe W o inde x in kWh/m3 F.
21 275 4.4. C HANGING THE T YPE OF G AS 4.5. O PERA TING T ESTS The boiler ma y be transf or med f or use with LPG (G30-G31); the operation must be perf ormed by an A uthorised Ser vice Centre. The operations to carry out are the following: 1. Replacement of the nozzle (see tab le); 2.
6. MAINTENANCE 6.1. G ENERAL R EMARKS It is recommended that the f ollowing inspections be carried out on the boiler at least once a year: 1. Check the seals in the w ater group and, if necessary , replace the gaskets and restore the seal to perf ect working order .
23 275 6.4. O PERA TIONAL T EST After having carried out the maintenance operations, fill the heating circuit to a pressure of appro x. 1.5 bar and release the air from the system. Also fill the domestic hot water system. - Place the boiler in operation.
7. TECHNICAL INFORMA TION Cer tification 63A T4528 Categor y II2H3B/P Thermal Capacity min/max kW 8/24 Usable Ther mal P ower min/max (30/40 ° C) kW 8.8/26.1 Usable Ther mal P ower min/max (60/80 ° C) kW 7.9/23.3 Usable Ther mal P ower min/max (30/50 ° C) kW -/24.
Servicing Instructions T ype C Boilers G.C.N: 41-116-03 47-116-17 LEA VE THESE INSTRUCTIONS WITH THE END-USER Condensing Countr y of destination: GB.
2 1. SER VICING INSTR UCTIONS 1.1 R EPLACEMENT OF P ARTS 1.2 T O G AIN G ENERAL A CCESS - Lowering the control panel and removing the front panel - Removing the side panels 1.
3 F IG . 1.2 F IG . 1.1 1. SER VICING INSTR UCTIONS The lif e of individual components vary and they will need servicing or replacing as and when f aults de velop .
4 Removing the side panels 1. Remov e the scre ws “C” (F IG . 1.4); 2. Pull each panel aw a y from the boiler , then lift the panel up and aw a y from the boiler . 1.3 A CCESS T O THE C OMBUSTION C HAMBER D F IG . 1.5 D F IG . 1.4 C C C C D D Removing the sealed c hamber front co ver 1.
5 Removing the fan 1. Loosen nut “E” (F IG . 1.7); 2. Pull off the hose “F” and disconnect the electr ical connector “G” (F IG . 1.8); 3. Remov e the nuts “H” (F IG . 1.9); 4. Pull the f an aw a y from the exchanger (F IG . 1.10). F IG .
6 Removing the b urner With the f an remov ed (see pre vious section); 1. Slide the burner from its housing (F IG . 1.11). F IG . 1.13 J I J Removing the electr odes 1. Pull off the ignition cable “I” (F IG . 1.12); 2. Remov e the two allen bolts “J” (F IG .
7 Removing the condensate collector 1. Remov e the nuts “L ” from each side of front of the collector (F IG . 1.17); 2. Remov e the nuts “M” from each side of rear of the collector (F IG . 1.18); 3. Release the condesate trap union “N” (F IG .
8 Removing the condensate trap 1. Loosen the union “O” (F IG . 1.22); 2. Remov e the condensate trap (F IG . 1.23). F IG . 1.22 O Removing the injector See the section on removing the f an bef ore carring out this procedure 1. Disconnect all connections from the f an and remov e (F IG .
9 F IG . 1.26 F IG . 1.27 Q.
10 1.4 A CCESS T O THE G AS V AL VE F IG . 1.28 S R Removing the gas v alve 1. Disconnect the electrical connection “R” from the gas valv e (F IG . 128); 2. Release the top nut “S” (F IG . 1.29); 3. Remov e the scre ws “T” from the bottom of the gas v alve pipe (F IG .
11 Removing the saf ety valve 1. Loosen union “W” (Fig. 1.35); 2. Unscrew and remo v e the valv e (Fig. 1.36). 1.5 A CCESS T O THE W A TER C IRCUIT F IG . 1.36 Removing the D .H.W . (secondary) exchanger 1. Remov e the scre w “U” (F IG . 1.32); 2.
12 Removing the automatic air vent 1. Unscrew v alv e “X” (F IG . 1.37); 2. Remov e (F IG . 1.38). Removing the main cir cuit flow s witch 1. Release the retaining clip “Y” (F IG . 1.40); 2. Remov e the main circuit flow s witch. F IG . 1.37 F IG .
13 Removing the pump 1. Unplug the electrical connection “C1” (F IG . 1.44); 2. Release the nut “D1” (F IG . 1.45); 3. Release the nut “E1” (F IG . 1.46); 4. Remov e the pump (F IG . 1.47). E1 D1 C1 F IG . 1.44 F IG . 1.47 F IG . 1.46 F IG .
14 Removing the e xpansion vessel See the section on removing the condesate trap bef ore carr ying out this procedure 1. Loosen nut “H1” (F IG . 1.51); 2. Loosen nut “I1” and remove bac knut “J1” (F IG . 1.52); 3. Remov e the e xpansion v essel (F IG .
15 Removing the D .H.W . temperature probe (N.T .C.) (MFFI only) 1. Remov e the electrical connector “K1” by pulling off (Fig. 1.54); 2. Unscrew and remo v e the D .H.W . temperature probe “L1” (F IG . 1.55). K1 L1 F IG . 1.54 F IG . 1.55 M1 F IG .
16 Checking the fuses 1. Remov e the inspection cov er on the re v erse of the control panel (F IG . 1.60); 2. Remov e the fuses b y pushing and rotating fuse holders “Q1” (F IG . 1.61). 1.6 A CCESS T O THE C ONTROL S YSTEM Remo ving the time cloc k 1.
17 Removing the P .C.B.s 1. Remov e the inspection cov er on the re v erse of the control panel (F IG . 1.60); 2. Remov e the scre ws “S1” (F IG . 1.65 & F IG . 1.66); 3. Remov e the f acia panel (F IG . 1.67); 5. Disconnect the connection cable ”T1” (F IG .
18 W1 F IG . 1.72 F IG . 1.73 W1 W1 W1.
19 2. F A UL T FINDING TABLE I and II YES YES YES NO NO IS THE POWER L.E.D. AND DISPLAY ON? DOES A STOP CODE APPEAR ON THE DISPLAY? POSITION OF THE SUMMER/ WINTER SELECTOR 1. Check the fuses 2. Check the power supply to the control panel 3. Check/replace the ON/OFF button 4.
20 YES NO MAKE SURE THAT: 1. There is sufficient water in the system 2. The gas is turned on 3. The electrical supply is turned on PUSH THE ON/OFF BUTTON TO ON IS THE POWER L.E.D. AND DISPLAY ON? DOES A STOP CODE APPEAR ON THE DISPLAY? POSITION OF THE SUMMER/ WINTER SELECTOR SUMMER WINTER NO YES ON/OFF button 5.
21 YES YES NO IS THE PUMP RUNNING? 1. Check if there is air in the system 2. Check the main circuit flow switch operation 3. Check the pressure on the water gauge and fill system to 1 bar 1.
22 1. Check the fan cable 2. Replace the fan 3. Replace the main P.C.B. 1. Check/replace ignition electrode 2. Check ignition cable 3. Check/replace the main P.C.B. Replace the main P.C.B. IS THE FAN RUNNING? DOES CODE A33 APPEAR? IGNITION SPARKS ARE GENERATED REGULARLY? YES NO NO YES YES NO 1.
23 T ABLE I T ABLE III D ISPLA Y A01 A02 A03 A07 A19 A20 A21 A22 A33 A99 C A USE T oo many attempts to ignite on star ting up After three attempts at ignition, no increase in ∆ T was detected The he.
24 3. ELECTRICAL DIA GRAMS L EGEND : A: JUMPER When needed, the P .C.B . allows the diff erent options to be selected by means of a wire link. The boiler has the f ollowing basic arrangement: 1 OPEN 2.
25 C1 = F AN 1: “ Hall ” sensor power supply 12V (red) 2: “ Hall ” sensor ground (b lue) 3: Not used 4: Star t of coil (blac k) 5: “ Hall ” sensor input (white) 6: End of coil (brown) C2 =.
26 ecoGENUS 24 MFFI - ecoGENUS 24 RFFI.
27 24 MFFI 21 15 13 301 302 301 53 50 49 48 46 47 54 52 55 57 56 49 2 51 52 2 1 4 5 3 51 57 62 26 27 29 33 40 42 43 44 41 39 38 35 34 36 32 31 30 28 98 99 36 33 100 28 45 37 37 102 11 10 9 7 8 7 81 81.
28 573294 573520 569236 997147 997077 998127 571438 998802 998144 573727 573172 573528 997207 571649 998765 569390 998672 998668 998459 998889 998888 998651 998077 998894 997206 997151 569387 573521 564264 998791 998792 573768 998801 998670 571444 571441 574248 998490 571987 571441 574248 571447 998013 Key no.
29 24 RFFI SYSTEM 23 17 14 301 302 301 54 51 50 49 47 48 55 53 56 58 57 2 52 53 2 1 4 5 3 3 52 58 63 27 28 30 34 41 43 44 45 42 40 39 36 35 37 33 32 31 29 96 97 37 34 98 29 46 38 38 100 25 26 21 24 21.
30 573294 573520 569236 997147 997077 998456 571438 573528 997828 573727 573172 997207 571649 998765 569390 998672 998668 998889 998888 998651 998783 997151 569387 573521 998791 573768 998792 564254 998459 998801 998670 571987 571443 571441 574248 571447 998013 Key no.
Manuf acturer: Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A v enue High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 F ax: (01494) 459775 Inter net: http://www .mtsgb .ltd.uk E-mail: inf o@mtsgb .
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Models ECOGENUS 24 MFFI Edition 1 of 1 December 1999.
301 302 301 53 50 49 48 46 47 54 52 55 57 56 49 2 51 52 2 1 4 5 3 51 57 62 26 27 29 33 40 42 43 44 41 39 38 35 34 36 32 31 30 28 98 99 36 33 100 28 45 37 37 102 11 10 9 7 8 7 81 81 80 17 15 23 25 24 2.
PART. CODE DESCRIPTION REF. NOTE 1 573294 Expansion vessel 2 573310 Expansion vessel insert 3 574302 Casing support bracket (Plastic) 4 573244 3/8" lock nut 5 ------ Frame 11 6 ------ Hydraulic group support 11 7 573520 Gasket 3/4" 8 569236 Temperature probe (C.
PART. CODE DESCRIPTION REF. NOTE 6 6 998788 Elbow (fan) 6 7 ------ Flame mirror 11 6 8 998786 Diaphragm (condensing boiler) 6 9 998654 Pipe (C.H. return) 7 0 998459 Electrode cable (resistive) 7 1 999.
Een belangrijk punt na aankoop van elk apparaat Ariston 47-116-17 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Ariston 47-116-17 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Ariston 47-116-17 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Ariston 47-116-17 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Ariston 47-116-17 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Ariston 47-116-17 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Ariston 47-116-17 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Ariston 47-116-17 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.