FieldPoint ™ is a trademark of National Instruments Corporation. Product a nd company names mentioned herein are trad emarks or trade na mes of their resp ective companies. 321904B-01 © Copyright 1998, 1999 National Instruments Corp. All rights reserved.
FP-RLY-420 2 www.natinst.com module. The maximum number of terminal bases per bank multiplied by 1 watt is the total po wer the network module can supply . For e xample, an FP-1000 or FP-1001 can support nine terminal bases (9*1 W = 9 W). Next, refer to the specif ications section in the operating instructions for the I/O modules.
© National Instruments Corp. 3 FP-RLY-420 Field Wiring The terminal base has connections for each of th e eight relay channels and an extern al supply to po wer f ield de vices. Each relay channel of the FP-RL Y -420 has two terminals: N.O. (Normally Open) and I.
FP-RLY-420 4 www.natinst.com Figures 2a and 2b sho w examples of basic wiring connections. Figure 2. Basic Field Connection (T wo Channels Shown) Relay Output Circuit The outputs of the FP-RL Y -420 consist of Form A electromechanical relays. The po wer -up state is off (open) to ensure safe installation.
© National Instruments Corp. 5 FP-RLY-420 Figure 3 shows the diagram of one channel’ s relay output circuit. Figure 3. Relay Output Circuit The maximum switching capacity of each relay is 3 A up to 250 V A C or 35 VDC. T o switch greater DC v oltages, refer to Figure 4.
FP-RLY-420 6 www.natinst.com In addition, the FP-RL Y -420 contains its ow n internal protection MO V to preve nt e xcessi vely high voltage from being applied across the contacts.
© National Instruments Corp. 7 FP-RLY-420 Diode Circuit CR Circuits Varistor Circuit Diagram Notes Use in DC applications only . Compared to RC type, circuit delays release time (2 to 5 times v alues stated in catalog). For larger v oltages, use diode with rev erse breakdown 10 times circuit voltage and forward load ci rcuit.
FP-RLY-420 8 www.natinst.com In-Rush Current The type of load and its in -rush current characteristics, together with switching frequency , can cause contact welding. F or loads with in-rush current, measure the steady state current and in-rush current to determine the proper relay .
© National Instruments Corp. 9 FP-RLY-420 After the module has been inserted into a terminal base ( and po wer is applied), the green POWER indicator lights and the FP-RL Y -420 informs the network mod ule of its presence.
FP-RLY-420 10 www.natinst.com •D o not share the external supply voltages (V and C on the terminal base) with other de vices (including other FieldPoint de vices) unless those devices are also isolated from human contact.
© National Instruments Corp. 11 FP-RLY-420 Maximum switching frequenc y Mechanical ................... ............. . 20 operations per second Electrical..................................... 1 operation per second at maximum load Relays operate time.
Mechanical Dimensions Figure 6 sho ws the mechanical dimensions of the FP-RL Y -420 installed onto a terminal base. Dimensions are gi ven in inches [millimeters].
Een belangrijk punt na aankoop van elk apparaat National Instruments FP-RLY-420 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen National Instruments FP-RLY-420 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens National Instruments FP-RLY-420 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding National Instruments FP-RLY-420 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over National Instruments FP-RLY-420 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van National Instruments FP-RLY-420 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de National Instruments FP-RLY-420 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met National Instruments FP-RLY-420 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.