FieldPoint™, Nat ional Instruments™, and ni. com™ are trademarks of National Instrument s Corporation. Product and company names mentione d herein are trademarks or trade names of their respective companies. 322633B-01 © Copyright 20 00 National Inst ruments Corp.
FP-QUAD-510 2 www.ni.com When defin ing a FieldPoint system that uses an FP-QU AD-510 module, you must calculate the power consu mption. First refer to the specifications section in the user man ual for your network module. The maximum number of terminal bases per bank multiplied by 1 watt is the total po wer the network module can supply .
© National Instruments Corp. 3 FP-QUAD-510 Figure 1. Install Y our Module Field Wiring The terminal base provides connections for each axis and for an external supply to po wer the FP-QU AD-510 input channels and field de vices. The FP-QU AD-510 accepts two types of encoder signal inputs: single-ended (TTL) or differential line dri ver .
FP-QUAD-510 4 www.ni.com Figure 3. Basic Field Connections to Single-Ended Encoders The FP-QU AD-510 supports differential inputs for Phase A, Phase B, and Index signals. Y ou can easily accommodate encoders with various phase relationships b y sw apping the signals and/or connecting them to the in verting inputs as specific applications require.
© National Instruments Corp. 5 FP-QUAD-510 T erminal assignments and wiring diagrams are also listed under the slide-in card on the front of the FP-QU AD-510 module. Status Indicators Figure 5 show s the module label and status indicators. Remov e the slide-in card to see wiring diagrams for the input signals.
FP-QUAD-510 6 www.ni.com Position Counter Operation Each position counter has a 32-bit binary counter th at represents the current position of the shaft connected to the axis. Channels 0 through 3 contain the lo west 16 bits of these counters f or axes 0 through 3 respecti ve ly .
© National Instruments Corp. 7 FP-QUAD-510 Reset on Index Capability Y ou can configure each position counter to reset each time the index condition is met. An index-initiated reset resets both the upper and lo wer 16-bit reg ister s associated with that axis.
FP-QUAD-510 8 www.ni.com The vel oci ty range is the ma ximum v elocity that can be measured for a gi ven timebase. The velocity re gister uses a 15-bit counter , which giv es a maximum number of counts of 2 15 , or 32,768.
© National Instruments Corp. 9 FP-QUAD-510 Note If the axis is stopped with the index condition true, then reading the status bit causes the bit to reset to 0. Howe ver , since the index condition is still true, the bit is immediately latched back to 1.
FP-QUAD-510 10 www.ni.com • As with any hazardous voltage wiring, mak e sure that all wiring and connection s meet applicable electrical codes and common sense practices. Mount terminal bases in an area, position, or cabinet that pre vents accidental or unauthorized access to wiring that carries hazar dous voltages.
© National Instruments Corp. 11 FP-QUAD-510 Specifications The following specif ications are typical for a range of –40 to +70 °C, unless otherwise noted. Encoder Input Number of channels ............ ............. . 4 Input type Single-ended ....
CE Mark Compliance This product meets applicable EU directi ve(s), as follo ws: Safety isolation ................................ EN 61010 (double insulation for 250 Vrms working isolation, installation category I I) EMC directi ve Immunity ..........
Een belangrijk punt na aankoop van elk apparaat National Instruments Quadrature Input Module FP-QUAD-510 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen National Instruments Quadrature Input Module FP-QUAD-510 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens National Instruments Quadrature Input Module FP-QUAD-510 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding National Instruments Quadrature Input Module FP-QUAD-510 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over National Instruments Quadrature Input Module FP-QUAD-510 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van National Instruments Quadrature Input Module FP-QUAD-510 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de National Instruments Quadrature Input Module FP-QUAD-510 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met National Instruments Quadrature Input Module FP-QUAD-510 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.