PROGRAMMABLE PROCESS MONITORS USER ’ S MANUAL DP3600, DP3700 AND DP3800 SERIE S OMEGA ENGINEERING, INC., ONE OMEGA DRIVE, STAMFORD, CT 06907. MANUAL: M881/0399.
1 SPECIFICATIONS ............................................................................................................................................................................................... 3 DESCRIPTION ............................
2 SCALING .............................................................................................................................................................................................................. 12 OFFSET ........................
3 SPECIFICATIONS (typical @ 25 C and rated supply voltage unless otherwise specified). STANDARD INPUT: * 4 - 20 MA, 10 - 50 MA, 0 - 5 VDC, 0 - 10 VDC EXTERNAL HOLD: * An external low level signal applied to the HOLD pin on the rear connector will initiate hold function.
4 DESCRIPTION The DP3600 series of instrumen ts are micro - processor based intelligent monitors that are capable of performing several tasks in addition to displaying the process variable.
5 PROGRAM LIMITS 1. Process Limit1 2. Process Limit2 3. Setup limt 3 f or Rate/Process 4. Process Limit 3 5. Setup Limit4 for Process/Deviation 6. Process Limit 4 7. Timer 1 Limit 8. Timer 2 Limit 9. Deadband for limits 9. Limits Normally open/close (1 Thru 4) 10.
6 Offset: Next configurable function is offset and is indicated by the message ‘OFFSET’ followed by current offset value. To change the v alue of flashing digit press ^v key. To move the flashing digit, push <NXT> key. After programming the desired value of offset, push the "SETUP" key to get to the next function.
7 Selection of Limit 4 as Process or Deviation Limit: This step comes after programming Limit 3 and is indicated by the message ‘LT3 Pr’ (if Limit 3 is setup as Process limit ) or ‘LT3 dEN’ (if Limit 3 is setup as deviation limit). Alternate selection can be made by pushing ^v key.
8 Audio Alarm On/Off: This unit supports an audio alarm which comes on when ever a limit value is exceeded. This alarm can be turned On or Off, as desired. The selection is made by pushing ^v key. If the alarm is ON, the display will read ‘ALR ON’ (Alarm On).
9 Rate Time - Base: This step is for programming time - base for calculation of Rate. Units of time - base are seco nds. Again, the active digit will be flashing. To change the value, push ^v key. To activate another digit for change, use <NXT> key.
10 SET UP FLOW CHART: SETUP SCALING (SCALING) HIGH SCALE (HI SCLE) LOW SCALE (LO SCLE) OFFSET (OFFSET) TARE (TARE) PROGRAM PROCESS LIMIT 1 (PrG Lt1 -- 01.234) PROGRAM PROCESS LIMIT 2 (PrG Lt2 -- 01.234) LIMIT 3 RATE OR PROCESS (Lt3 rtE) or (Lt3 Pr) PROGRAM LIMIT 3 VALUE (PrG Lt3 -- 02.
11 MAX. AND MIN. READIN GS (PEAKS) Displaying: To display the peak values of Process variable push Peak key once and let go. The display will first indicate ‘ HIGH Pt’ briefly and then the value of the highest Process variable value monitored by the system.
12 PROCESS CHANGE Displaying: The system will constantly monitor the total amount of change in process variable since start or last reset. This change is displayable in engineering units by pushing the ‘PR CNG’ k ey. This function is useful in tracking the change that has taken place in the process e.
13 TARE Tare function is used for taking out a preset amount of process variable from the total reading e.g. if we are measuring weight of a certain p roduct being put in a container but do not want the weight of the container to show on the display, then enter the weight of the container as tare value.
14 Timer Limits: Displaying: To display timer limits, first push the TIME key. While still in this mode go on to push LIMITS key. The display will briefly show TR1 LT (for timer 1 Limit) and then the previously programmed value. Pushing the LIMITS key one more time will display TR2 LT followed by pre - programmed timer 2 value.
15 Open Collector Option Whenever a limit is reached an open collector output provides a 5 Vdc signal at 50ma. on the output connector, e.g... Limit 1 provides its 5 volt output signal between pins 1 and 2.
16 PIN NO DESCRIPTION 1 LIMIT 1 COMMON/OPEN COLLECTOR POSITIVE 2 LIMIT 1 NORMALLY OPEN/OPEN COLLECTOR NEGA TIVE 3 LIMIT 2 COMMON/OPEN COLLECTOR POSITIVE 4 LIMIT 2 NORMALLY OPEN/OPEN COLLECTOR NEGATIVE.
17 TROUBLE SHOOTING If the meter locks on a particular display, unplug and plug in again the meter to unlock the display. A total reset defaults all scaling values to zero.
18 A 1 2 3 4 3 B 3.62" (91.9mm) 1.70" 43.2mm NOT DRAWN TO SCALE Back of the Meter Bracket Screw Driver Push Meter this way with the Screwdriver MOUNTING 1. Cut a hole in panel to the specifications shown in the figure 4 : Figure 4. Panel Cutout Dimensions 2.
Een belangrijk punt na aankoop van elk apparaat Omega Engineering DP3600 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Omega Engineering DP3600 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Omega Engineering DP3600 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Omega Engineering DP3600 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Omega Engineering DP3600 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Omega Engineering DP3600 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Omega Engineering DP3600 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Omega Engineering DP3600 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.