1. General Information and Features 2 2. Applicable Standards 3 3. Installation and Removal 4 4. Input and Output Connections 8 5. Specifications 9 5.1 PS T ype Labeling 5.2 Size & W eight 5.3 Mounting 5.4 T emperature Ranges 5.5 Input Range 5.6 Input Current Surge Protection 5.
The compact DRN power supplies are designed to supply well-regulated 21.5 volt DC power to sensors, signal conditioners, data acquisition systems and high level logic equipment.
2.1 Input Voltage Tolerances Exceeds IEC 38 range 2.2 Input / Output Isolation 4KV rms 60Hz 1 minute test 630V conductor spacing, IEC 348 Exceeds VDE551 / IEC 742 separation spacing Exceeds VDE106 protective separation Exceeds VDE 160 clearance distances Exceeds VDE160 creepage distances 2.
The DRN power supplies are heavy enough to cause damage and or injury if dropped during installation. Assure firm rail mounting before releasing grip on the unit. If a rail assembly is to be transported, then disconnection, dismounting and separate packing of the power supply is recommended.
T o change voltage jumpers: 1. Remove cover from case by carefully prying up two side tabs using a screwdriver . Remove two screws from bottom of case. Slide unit out of case. 2. Locate the main board assembly and position it in front of you the same way as shown in Figure 3.
Figure 3.1 Ñ Main Board Power Jumpers MAIN BOARD T1 115VAC WIRING SHOWN WITH W1 W3 TRANSFORMER MOUNTING PLATE W2 115VAC JUMPER WIRING W1 W3 W2 230VAC JUMPER WIRING W2 W3 W1 I NST ALLA TION AND R EMOV.
Figure 3.2 Ñ 35mm "Top Hat" Installation: Hook in the module with the mounting rail guide on the top edge of the mounting rail and lower it to lock it into position. Removal: Release the spring catch with a screwdriver while raising the module to disengage it.
Figure 4.1 Ñ Front Panel Connection Labels shown without regulator cover AC Line AC Neutral Ground RETURN NO CONNECTION +21.5V IN AC N PWR +V N/C OUT DC I NPUT AND O UTPUT C ONNECTIONS 4 8 DRN-PS Ñ .
5.1 PS Type Labeling DRNÐPSÐ750, where 750 equals mA rating. DRNÐPSÐ750 5.2 Size & Weight Height: 2.76" (70mm) Width: 2.95" (75mm) Depth: 5.95" (151mm) Weight: 2.0 lbs. (0.9 kg) 5.3 Mounting 35mm "top hat" DIN EN 50022 5.
5.5 Input Range 115 or 230V, 49Ð61Hz DRNÐPSÐ750 ± 10% 5.6 Input Current Surge Protection 6kA/275V Varistor 5.7 Output Voltage 21.5V ± 2% - IR, where I = output current amperes and R = 0.
5.10 Temperature Derating None below 50 degrees C DRNÐPSÐ750, 15mA per degree C above 50¡C 5.11 Power-on Indicator Front Panel red LED lamp 5.12 Short-circuit and overload protection DRNÐPSÐ750 foldback current limiting with automatic high temperature shutdown no fuses required 5.
Figure 6.1 Ñ Derating Graph Figure 7.1 Ñ Block Diagram 49-61Hz 115/230vac INPUT: (+V) Ground AC Line AC Neutral V A R I S T O R L C F I L T E R B R I D G E ( ) 21.5V R E G U L A T O R Return 75mA 50 DRN-PS-750 ¡ C Ambient 0 1000 800 600 400 200 60 45 35 25 15 5 -5 I max.
Figure 8.1 Ñ Dimensions SPACED AS SHOWN. POWER SUPPLY WITH [151.1] 5.95 2.76 2.95 3.15 TWO SCREWS FASTEN RAIL UNDER MAX [70.0] [75.0] [80.0] D IMENSIONS D RA WING 8 13 DRN-PS Ñ DIN Rail Power Suppli.
S AFETY C ONSIDERA TIONS 14 DNR-PS Ñ DIN Rail Power Supplies Unpacking & Inspection Unpack the instrument and inspect for obvious shipping damage. Do not attempt to operate the unit if damage is found. This instrument is a panel mount device protected in accordance with Class I of EN 61010 (115/230 AC power connections).
WARRANTY / DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.
Where Do I Find Everything I Need for Process Measurement and Control? OM EGAÉOf Course! TEMPERATURE M U Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies M U Wire: Therm.
Een belangrijk punt na aankoop van elk apparaat Omega Engineering DRN-PS-750 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Omega Engineering DRN-PS-750 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Omega Engineering DRN-PS-750 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Omega Engineering DRN-PS-750 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Omega Engineering DRN-PS-750 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Omega Engineering DRN-PS-750 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Omega Engineering DRN-PS-750 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Omega Engineering DRN-PS-750 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.