Gebruiksaanwijzing /service van het product FW-SP-250 van de fabrikant Outback Power Systems
Ga naar pagina of 22
Sur ge P r ot ec tor FW -SP-A CA FW -SP-250 FW -SP-R U ser ’ s Guide Includes M ounting and Installation.
About OutBack P ower S ystems OutBack P ower Systems is a leader in advanced ener gy conversion t echnology . Our products include true sine wave in verter/chargers, maximum power point char ge controllers, syst em com- munication components, as well as br eaker panels, breakers, accessories, and assembled syst ems.
2 W arranty I ntroduction Dear OutBack Customer , Thank you for y our purchase of OutBack products. We make every e or t to assur e our power con- version products will give y ou long and reliable ser vice for your r enewable energy system.
OUTBACK FLEX ware Surge P rotector INST ALLA TION GUIDELINES AND SAFET Y INSTRUC TIONS This product is intended to be installed as part of a permanently grounded electrical system . • The FLEXware Sur ge P rotector is designed f or indoor installation or installation inside a weatherproof enclosure .
INTRODUC TION The OutBack FLEXware Sur ge Pr otec tor connects to the f ollowing FX Ser ies Inverter/Charger por ts: • DC+ • DC- • AC HO T IN • AC NEUTRAL IN • AC HO T OUT • AC NEUTRAL OUT • GROUND The FLEXware Sur ge Pr otec tor is desig ned to protect the FX’ s sensitive components from excessively high v oltages (e.
The FLEX ware Surge P rotector Speci cations LEDs • AC TIVE lights are y ellow (power is present). • ERROR lights are red (pr otection in that circuit is compromised , replacing the surge pr otec tor is recommended). • F or the ERR OR light to show , its circuit must be pow ered; its ACTIVE light will also glow.
FW-SP -ACA The FW-SP -ACA consists of an FW-A CA with an included surge prot ector and is installed onto an FX Series Inver ter/Char ger . Figur e 4: FLEXware Sur ge Pr otec tor -ACA LEDs Underside sc.
(1) Remove the DC C or T urbo (secured by four Phillips corner screws) (2) Remove the DC battery caps (under the DCC or T urbo) (3) Remove the AC Wiring Compartment plastic cover (secured with two Phi.
(7) Remove the appropriate knockouts for the individual power application. Note that knockouts should be scored rst with a utility knife and then removed . The dual, concentric knock out on the back o ers openings for the FW500, FW1000, PS2 and PS4 AC enclosures .
9 (11) Inser t a bushing into the AC enclosur e (it is not critical that this bushing line up precisely with the FW-SP -ACA); if exible cable is used instead of an enclosure , appropriate strain relief is r equired.
FW-SP -250 The FW-SP -250 is a two-piece combined FLEXware 250 top cover and FLEX ware Surge P rotector . I t replaces an existing FLEXwar e 250 cover , attaching at the AC end of the FLEXware 250. Pr ocedure The FLEXware 250 A C should already be installed (see FW250 AC instructions) and all AC and DC power shut o .
(8) Route the FW-SP -250 wires through to the A C Wiring Compartment and to the batter y lugs. (9) Secure the surge pr otec tor’ s wiring in the appropriate locations and replace the various plastic covers as per the wiring instructions on page 16. 11 (5) Install the top section of the cover contain- ing the surge prot ector rst.
Figur e 11: FW-ACA (2) Remove the FW-A CA plastic cover (secured with two Phillips screws) (3) Remove the FW- ACA Bracket (secured with one Phillips screw); if a damaged FLEXware Sur ge Pr otec tor is.
1/ 3/07 The locating pin on the FW-ACA bracket ts in this slot (4) P ass the FW-SP -R wires through the FW - ACA Bracket opening, lining up the locating pin with the slot on the surge prot ector .
(5) With the FW-SP-R attached t o the FW-ACA Bracket, hold the ends of the FW-SP -R wires and slide it and the bracket back inside the FW-ACA to its original location. NO TE: The FW-SP -R slides into a double slot at the bottom of the FW-ACA. The LEDs should be level with the top of the FW-A CA housing.
(6) When the new surge protector board has been secured to the FW-SP -250 cover , reinstall the FW-SP -250 as shown on pages 10-11. (3) Remove the FW-SP -250 (secured by six Phillips screws). (2) Remove the AC Wiring Compartment cover (secured by two Phillips screws).
Wiring and C onnec ting the FLEX ware Surge Pr otec tor With the FW-SP -250 or FW-SP-ACA secur ed, connect all AC and DC wiring as well as any HUB, MA TE, A UX, and BA T TERY TEMP cables.
• Install the various covers in this order with the DCC or Turbo last: (1) DC battery terminals (2) FW-ACA (if used) (3) AC Wiring Compar tment Figur e 16: After wiring, install all covers .
18 FLEX ware ™ Surge P rotector Limited W arranty OutBack P ower Systems , Inc. (“OutBack ”) provides a limit ed warranty (“ Warranty ”) against defects in materials and workmanship for its FLEXware Sur ge Pr otec tor P roducts (“Product”) if installed for use with OutBack FX Series Inverter/Chargers in xed location applications.
19 1. P roof- of-purchase in the f or m of a copy of the original P roduct purchase invoice or r eceipt con rming the Pr oduct model number and serial number ; 2. OutBack issued warranty cer ti cate f or the FX Series I n verter/Charger used with the Pr oduc t; 3.
Surge P rotector Limited W arranty Registra tion 20 Revision 2007-06-20 Surge P rotector Limited W arrant y Registration Complete this form to request a Limited W arranty , and return it to: Outback P ower Systems Inc.
900-0089-01-00 REV A European Sales O c e Barcelona, España (+34) 600-843-845 19009 62nd Avenue NE Arlington, W A USA (+1) 360-435-6030 www.outbackpower .
Een belangrijk punt na aankoop van elk apparaat Outback Power Systems FW-SP-250 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Outback Power Systems FW-SP-250 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Outback Power Systems FW-SP-250 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Outback Power Systems FW-SP-250 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Outback Power Systems FW-SP-250 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Outback Power Systems FW-SP-250 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Outback Power Systems FW-SP-250 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Outback Power Systems FW-SP-250 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.