Gebruiksaanwijzing /service van het product RPS830 van de fabrikant Perle Systems
Ga naar pagina of 72
5500193-10 RPS Series Remote Power Switches Models Covered: RPS820 RPS830 RPS1620 RPS1630 User ’s Guide.
.
i Warnings and Cautions: INST ALL A TION INSTRUCTIONS SECURE RACKING If Secure Racked units are installed in a closed or multi-unit rack assembly , they may require further evaluation by Certification Agencies. The following items must be considered.
ii RPS Series: Remote Power Switches - User's Guide FCC Part 15 R egulation This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
iii T able of Contents 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv RPS Series: Remote Power Switches - User's Guide 7. Saving and Restoring Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 7.1. Sending Parameters to a File . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 1. Introduction Electronic equipment sometimes "locks-up" requiring a service call just to flip the power switch to perform a simple reboot.
1-2 RPS Series: Remote Power Switches - User's Guide Four Differ ent RPS Models This User ’ s Guide discusses four different RPS models. Throughout this User ’ s Guide, all four units are referred to as the "RPS". Aside from the hardware configuration, all other features function identically in both units except where noted.
2-1 2. Unit Description 2.1. RPS820 and RPS830 F ront Panel The front panels of both RPS820 and RPS830 models include two LED indicators which function as follows: • Power: Lights when power is applied to the unit. Note that this indicator does not show the On/Off status of the switched outlets.
2-2 RPS Series: Remote Power Switches - User's Guide ➂ Bus "A" Switched Plugs and Plug Indicators: AC Outlets that can be switched On, Off or rebooted in response to user commands. • RPS820: Four 208-240 V AC, IEC-320-C13 Outlets with indicator lights.
2-3 Unit Description 2.3. RPS1620 and RPS1630 Hardware As shown in Figure 2.2, RPS1620 and RPS1630 units includes power outlets, LEDs and a manual control button.
2-4 RPS Series: Remote Power Switches - User's Guide As shown in Figure 2.2, RPS1620 and RPS1630 units include the following components: Manual Switch Button: A Manual Control Button for the unit’ s switched plugs.
2-5 Unit Description Power Cir cuit "A" Input Comp onents: An AC inlet and circuit breaker , which supply power to plugs one through 8: Model RPS1620: • Power Inlet: T wo (2) 208 to 240 V AC, IEC-320-C14 AC inlets. • Cir cuit Breaker: 10 Amps.
2-6 RPS Series: Remote Power Switches - User's Guide.
3-1 3. Quick Start Guide This Quick Start Guide describes a simplified installation procedure for the RPS820, RPS830, RPS1620 and RPS1630, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation.
3-2 RPS Series: Remote Power Switches - User's Guide 3.1.2. Connect your PC to the RPS The RPS can either be controlled by a local PC Serial Port, controlled via external modem, or controlled via TCP/IP network. In order to switch plugs or select parameters, commands are issued to the RPS via the Network Port or Console/RS232 Port.
3-3 Quick Start Guide T o communicate with the RPS unit, proceed as follows: 1. Access Command Mode: This procedure differs slightly for the W eb Browser Interface and T ext Interface: a) W eb Browser Interface: Start your JavaScript enabled W eb Browser .
3-4 RPS Series: Remote Power Switches - User's Guide Figur e 3.1: Plug Status Scr een - W eb Br owser Interface (Model RPS830 Shown) Remote Power Switch v1.
3-5 Quick Start Guide 2. T est Switching Functions: Y ou may wish to perform the following tests in order to make certain that the RPS is responding to commands. a) Reboot Outlet: If you are communicating with the unit via the W eb Browser Interface, select the button in the "Boot" column for Plug 1, and then click on "Apply .
3-6 RPS Series: Remote Power Switches - User's Guide.
4-1 4. Installation This section provides further details regarding the connections that are made in the process of installing the RPS. 4.1. Power Supply Connection Before you connect the RPS to your power supply , it is recommended to install the Cable Keepers, which will secure the power supply cables to the RPS unit.
4-2 RPS Series: Remote Power Switches - User's Guide 4.2. Connection to Switched Outlets Connect the power cord from each device that you wish to control, to a Switched AC Outlet on the RPS unit. Note that when power is applied to the RPS in the default state, the Switched Outlets will all initially be switched "ON".
4-3 Installation 4.4. Connecting the Network Cable The Network Port is an RJ45 Ethernet jack, for connection to a TCP/IP network. Connect your 10Base-T cable to the Network Port. Note that the RPS includes a default IP address (192.168.168.168) and a default subnet mask (255.
4-4 RPS Series: Remote Power Switches - User's Guide.
5-1 5. Configuration 5.1. System Mode and User Mode In order to restrict access to sensitive command functions, the RPS features two operating modes; System Mode and User Mode. • System Mode: Allows access to all configuration menus, switching functions and status screens.
5-2 RPS Series: Remote Power Switches - User's Guide 5.2. Communicating with the RPS In order to configure the unit or invoke command functions, you must first connect to the RPS and access the command mode. As discussed in Section 3, the RPS offers two separate command interfaces: the W eb Browser Interface, and the T ext Interface.
5-3 Confi guration 5.2.1. Accessing the Web Browser Interface In order to issue commands via the W eb Browser Interface, the RPS must be connected to a TCP/IP network, and your PC must be equipped with a JavaScript enabled web browser (such as Internet Explorer™ or Netscape™ Navigator .
5-4 RPS Series: Remote Power Switches - User's Guide 5.2.2. Accessing the T ext Interface The T ext Interface can be accessed via Network, modem or local PC.
5-5 Confi guration T o access command mode via the T ext Interface, proceed as follows: 1. The RPS is transparent to parity and will accept 7 or 8 bit characters, but will always answer back at 8 bits, no parity . Make certain your communication program is set for the appropriate baud rate, bits, parity and Comm Port.
5-6 RPS Series: Remote Power Switches - User's Guide 5.3. Configuration Menus As described in the sections that follow , configuration parameters for the RPS can be selected via the W eb Browser Interface or T ext Interface.
5-7 Confi guration Figur e 5.3: General Parameters Menu - W eb Br owser Interface GENERAL PARAMETERS: 1. System Password: (undefined) 2. User Name: (undefined) 3. Site ID: (undefined) 4. Command Echo: On 5. Inactivity Timeout: 2 Mins 6. Command Confirmation: On 7.
5-8 RPS Series: Remote Power Switches - User's Guide The General Parameters Menu allows the following parameters to be defined. • System Password: The RPS will display a password prompt when you attempt to access command mode.
5-9 Confi guration • Inactivity Timeout: Determines how long the RPS will wait for additional commands during periods of inactivity . When the T imeout Period elapses, the user will be disconnected from the RPS command mode.
5-10 RPS Series: Remote Power Switches - User's Guide 5.3.2. The Serial Parameters Menu The Serial Parameters Menus are used to configure the RPS's serial console port, and allow you to select parameters such as the baud rate, parity and modem initialization string.
5-11 Confi guration As shown in Figure 5.5 and Figure 5.6, the Serial Parameters Menus allow you to define the following parameters: Note: When the baud rate, data bits, parity or stop bits settings are changed via the console port, newly selected parameters will not be applied until the user exits and then re-enters command mode.
5-12 RPS Series: Remote Power Switches - User's Guide 5.3.3. The Plug Parameters Menus The Plug Parameters Menus are used to define Plug Names, Plug Passwords, boot/sequence delay times and Power Up Default values for each of the RPS’ s Switched AC Outlets.
5-13 Confi guration Note that when defining plug parameters via the W eb Browser Interface, the desired plug is selected using the dropdown menu at the top of the page. When defining plug parameters via the T ext Interface, the plug is selected using the /P n command (where n is the number or name of the desired plug.
5-14 RPS Series: Remote Power Switches - User's Guide 5.3.3.1. Plug P asswords and Co-Location Features The Plug Passwords, which are defined via the Plug Parameters Menu(s) allow you to determine which plugs an individual user will be permitted to control.
5-15 Confi guration 5.3.3.2. The Boot / Sequence Delay Period. The Boot / Sequence Delay value will be applied differently for Reboot operations as opposed to simple On/Off operations as described below: 1. Reboot Cycles: a) Single Plug: The Boot/Seq.
5-16 RPS Series: Remote Power Switches - User's Guide 5.3.4. Network Parameters Menus The Network Parameters Menus are used to select the IP Address and other network parameters. • W eb Browser Interface: Click the "Setup" button to access the Setup Menus, and then click the "Network Parameters" button.
5-17 Confi guration Figur e 5.9: Network Parameters - W eb Br owser Interface NETWORK PARAMETERS: 1. IP Address: 207.212.30.80 2. Subnet Mask: 255.255.255.0 3. Gateway Address: 207.212.30.1 4. Send MSS: 536 5. IP Security MAC Address: 00-09-9b-00-90-e0 Enter Selection, Press <ESC> to Exit .
5-18 RPS Series: Remote Power Switches - User's Guide IP SECURITY: 1. Security Mask #1: (undefined) 2. Mask #1 Action: Permit 3. Security Mask #2: (undefined) 4. Mask #2 Action: Permit 5. Security Mask #3: (undefined) 6. Mask #3 Action: Permit 7.
5-19 Confi guration Example 1: Deny access to all hosts except 192.1.1.5: Security Mask #1: 255.255.255.255 Mask #1 Action: Deny Security Mask #2: 192.1.1.5 Mask #2 Action: Permit Since 255 is a wild card, Mask #1 blocks all IP Addresses. Mask #2 then specifically grants access to 192.
5-20 RPS Series: Remote Power Switches - User's Guide Figur e 5.12: T elnet Parameters Menu - W eb Browser Interface TELNET PARAMETERS: 1. Service: On 2. Telnet Port #: 23 3. Multiple Telnet: Off Enter Selection, Press <ESC> to Exit ... Figur e 5.
5-21 Confi guration The T elnet Parameters Menus allow the following parameters to be defined. Please note that all parameters listed here are available via both the W eb Browser Interface and T ext Interface. • Service: Enables/Disables T elnet communication with the RPS unit.
5-22 RPS Series: Remote Power Switches - User's Guide Figur e 5.14: W eb Br owser Parameters Menu - W eb Browser Interface WEB SERVER: 1. Service: On 2. Server Port #: 80 Enter Selection, Press <ESC> to Exit ... Figur e 5.15: W eb Br owser Parameters Menu - T ext Interface 5.
5-23 Confi guration The W eb Server Parameters Menu allows the following parameters to be defined. Please note that all parameters listed here are available via both the W eb Browser Interface and T ext Interface. • Service: Enables/Disables the RPS’ s W eb Server .
5-24 RPS Series: Remote Power Switches - User's Guide.
6-1 6. Operation As discussed in Section 5, "Configuration", the RPS offers two separate command interfaces; the W eb Browser Interface and the T ext Interface.
6-2 RPS Series: Remote Power Switches - User's Guide 4. Switching Plugs Off: Click the "Of f" button next to the desired plug(s), and then click "Apply ." T o switch all plugs Off, click the "Of f" button in the "All Plugs" row , and then click "Apply .
6-3 Operation 6.2. Operation via the T ext Interface When using the T ext Interface, all switching functions are performed by invoking simple, ASCII commands. ASCII commands are also used to display status screens and to log out of command mode. The T ext Interface also includes a Help Menu, which summarizes all available RPS commands.
6-4 RPS Series: Remote Power Switches - User's Guide 6.2.2. Switching and Reboot Commands - T ext Interface These commands can be used to switch plugs On/Off, reboot plugs or set plugs to their user-defined Power Up Default values. Plugs may be specified by name or number .
6-5 Operation T o switch plugs On/Off, initiate a reboot cycle, or set plugs to their Power Up Default values, proceed as follows: 1. Switch Plug(s) On: T ype /ON n and press [Enter] . Where " n " is the number or name of the desired plug. For example: /ON 1 or /ON ROUTER 2.
6-6 RPS Series: Remote Power Switches - User's Guide 6.2.3. Applying Commands to Several Plugs - T ext Interface As described below , switching and reboot commands can be applied to only one Switched AC Outlet, or to an assortment of outlets.
6-7 Operation 6.3. Logging Out of Command Mode When you have finished communicating with the RPS, it is important to always disconnect using either the "Log Out" button (W eb Browser Interface) or /X command (T ext Interface), rather than simply closing your browser window or communications program.
6-8 RPS Series: Remote Power Switches - User's Guide T o enable the Automated Mode, access the General Parameters menu (see Section 5.3.1) and then set the "Automated Mode" option to the "On" state. When the Automated Mode is enabled, RPS functions will change as follows: 1.
7-1 7. Saving and R estoring Configuration Parameters After the RPS has been properly configured, parameters can be downloaded and saved as an ASCII text file on your local or remote PC.
7-2 RPS Series: Remote Power Switches - User's Guide 7.2. Restoring Saved P arameters This section describes the procedure for using ProComm to send saved parameters to the RPS. Note: Parameters that have been saved to an ASCII file can only be restored via the T ext Interface.
8-1 8. Upgrading the RPS Firmware When new , improved versions of the RPS firmware become available, the "Upgrade Firmware" function can be used to update the unit. Updates can be installed via the Console Port or Network Port. Notes: • The upgrade procedure can only be performed via the T ext Interface.
8-2 RPS Series: Remote Power Switches - User's Guide 4. Set your communication program for ASCII Mode, then use the program’ s "Send File" function to transfer the upgrade file to the RPS. Select ASCII format, then specify the filename and directory location where the firmware upgrade file resides.
Apx-1 A . Interface Descriptions A.1. Console Port Interface Figur e A.1: Console Port Interface.
Apx-2 RPS Series: Remote Power Switches - User's Guide B. Specifications Power Input / Output: Model RPS820 (208 to 240 V AC) AC Input: T wo Separate Circuits; 10 Amps Maximum per Circuit • V o.
Apx-3 Appendices Physical / Environmental: Size: Models RPS820 and RPS830 (Horizontal Mount): • Width: 17.5” (44.5 cm) Standard Rack • Depth: 7.0” (17.8 cm) • Height: 1.75” (4.5 cm) 1 Rack U Models RPS1620 and RPS1630 (V ertical Mount): • Width: 1.
Apx-4 RPS Series: Remote Power Switches - User's Guide C. Customer Service C.1. Making a T echnical Support Query This section contains the following information about making a query; • Who to contact on page Apx-4 • Information needed when making a query on page Apx-6 • Making a support query via the Perle web page on page Apx-7 C.
Apx-5 Appendices C.3. Perle Support Centres Worldwide Notes: • Perle of fers free technical support to Perle Authorised Distributors and Registered Perle Resellers. • T o access technical support please visit the Perle website at www . perle.com/support.
Apx-6 RPS Series: Remote Power Switches - User's Guide C.4. Information Needed When Making a Query When you make a technical support enquiry please have the following information ready; Hint: Print out this page and fill in the table provided with the basic information you need.
Apx-7 Appendices C.5. Making a Support Query via the Perle Web P age If you have an internet connection, please send details of your problem to T echnical Support using the email links provided on the Perle web site (http://www .perle.com) in the 'Support' area.
Apx-8 RPS Series: Remote Power Switches - User's Guide T rademark and Copyright Information This document must not be reproduced in any way whatsoever , either printed or electronically , without.
Index -1 Inde x A Activity Indicator RPS1620 and RPS1630 2-4 Automated Mode 5-9, 6-7 B Back Panel RPS820 and RPS830 2-1 Baud Rate Console Port 5-1 1 Boot/Sequence Delay 5-15 Boot/Sequence Delay T ime .
RPS Series: Remote Power Switches - User's Guide Index -2 M MAC Address 5-16 Main Power Switch RPS1620 and RPS1630 2-4 RPS820 and RPS830 2-2 Manual Operation 6-8 Manual Plug Control RPS1620 and R.
Index Index -3 Switched Outlets RPS1620 and RPS1630 2-4 RPS820 and RPS830 2-2 Switching Plugs 6-1 to 6-8, 6-5 System Mode 5-1, 5-14 System Password 5-8 System Ready Indicator RPS820 and RPS830 2-1 T T.
Index -4 RPS Series: Remote Power Switches - User's Guide.
Een belangrijk punt na aankoop van elk apparaat Perle Systems RPS830 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Perle Systems RPS830 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Perle Systems RPS830 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Perle Systems RPS830 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Perle Systems RPS830 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Perle Systems RPS830 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Perle Systems RPS830 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Perle Systems RPS830 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.