Gebruiksaanwijzing /service van het product QV-PIER van de fabrikant Quadra-Fire
Ga naar pagina of 41
1 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Models: QV -Pier QV -ST Series: HV -IPI Owner ’ s Manual Installation and Operation DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instructions included.
2 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 These units MUST use one of the vent systems described in the Installing the Fireplace section of the Installers Guide . NO OTHER vent systems or component s MA Y BE USED .
3 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 T able of Content s Safety and W arning Information .................................................. 2 Service Parts List ..............................................
4 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Part number list on following page. 6 Log Assembly (NG , LP) Exploded Part s Diagram Service Parts List QV -Pier-HV -IP.
5 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 SERVICE PARTS LIST IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.
6 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 (NG , LP) Exploded Parts Diagram Service Parts QV -ST -HV -IPI Beginning Manufacturing Date: 6-03 Ending Manufacturing Date: ______ Part number list on following page.
7 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 SERVICE PARTS LIST IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.
8 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 (NG , LP) Exploded Parts Diagram Service Parts Beginning Manufacturing Date: 6-03 Ending Manufacturing Date: ______ QV .
9 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Appliance Certification The Quadra-Fire fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the applicable laboratories.
10 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 2 Getting St arted Introducing the Quadra-Fire Gas Fireplaces Quadra-Fire direct vent gas fireplaces are designed to op- erate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.
11 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 1. Diagram of the QV -PIER-HV -IPI 5-1/ 4 (133m m) 1/2 (13m m) 12 (306 mm) Ø 8 (205mm ) 42-5/8 (10 82mm) Ø 8 .
12 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 3. Diagram of the QV -ST -HV -IPI 5-14 (133mm) 12 (306mm) 1/2 (13mm) (4) 46-5/8 (1 183mm) 42 (1067mm) 32-5/16 (.
13 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 3 Inst alling the Fireplace Step 1. Locating the Fireplace The diagram below shows space and clearance require- ments for locating a fireplace within a room.
14 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Minimum Clearances from the Fireplace to Combustible Materials Inches mm Glass Sides or Ends .......... 3 6 .................... 9 1 4 Floor . .. .......................
15 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Framing should be constructed of 2 X 4 lumber or heavier . Model A B C D E QV -PIER-HV -IPI 42-1/8 42-1/2 23 35-3/4 48 QV -ST -HV -IPI 47-5/8 42-1/2 23 35-3/4 48 Figure 5.
16 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 NOTE: PIPES OVERLAP 1-1/4 INCHES A T EACH JOINT . Figure 6. DVP-Series Direct V ent Component Specifications (5-inch inner pipe / 8-inch outer pipe) D V P 9 0 S T 12- 9/1 6 11 - 1 / 4 7-1 /4 1-1/4 T YP 1/2 TYP 8-9 /16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6 12 DVP12 2 MIN.
17 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 7. V ent System Components and T ermination Kit s Step 3. Inst alling the V ent System A. V ent System Approvals These models are approved to use DVP series direct vent pipe components and terminations (see Figures 6 and 7).
18 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 8 NOTE: On vertical venting configurations you may want to install the flue re- strictor (385-128). See flue restrictor installation in- structions. Flue Restrictor Instructions 1.
19 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 NA TURAL GAS VENTING WITH ONE 90° ELBOW V (FT .) H (FT .) 90 0 Elbow on top 2.5’ MAX. (64mm) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX.
20 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 15. V enting with T wo 90° Elbows H 1 H V V V 1 H NA TURAL GAS VENTING WITH TWO 90° ELBOWS V (FT .) H + H 1 (FT .) 90 0 Elbow on top 2.5’ MAX. (64mm) 1' MIN.
21 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 16. V enting with T wo 90° Elbows Figure 17. V enting with T wo 90° Elbows H 1 V H V H H 1 NA TURAL GAS VENTING WITH TWO 90° ELBOWS V (FT .) H + H 1 (FT .) 1' MIN.
22 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 18. V enting with three 90° elbows H H 1 H 2 V H V H 1 V 1 NA TURAL GAS VENTING WITH THREE 90° ELBOWS V + V 1 (FT .) H + H 1 (FT .) 1' MIN. (305mm) 3' MAX.
23 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 19. V enting with three 90° elbows V H H 1 V 1 V H H 1 V 1 NA TURAL GAS VENTING WITH THREE 90° ELBOWS V + V 1 (FT .) H + H 1 (FT .) 90 0 Elbow on top 2.5’ MAX.
24 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 1. Att ach the First V ent Component to the Starting Collars T o attach the first vent component to the st arting collars of the fireplace: • Slide the first vent section onto the unit and push in until they snap lock in position.
25 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 4. Install Firestops For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes. NOTE: Model DVP-TRAP does not need an exterior firestop on an exterior combustible wall.
26 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 25 Hole & New Framing Members CEILING NEW FRAMING MEM BERS EXIST ING CEILING JOIST S CHIMNEY HOLE 10" ( 254 mm) 10" (254 mm) NOTE: There must be NO INSULA TION or other combustibles inside the framed firestop opening.
27 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 V = VENT TERMINAL X = AIR SUPPL Y INLET = AREA WHERE TERMINAL IS NOT PERMITTED Figure 29. V ent T ermination Minimum Clearances A = 12 " ....................... clearances above grade, veran- da, porch, deck or balcony B = 12 " .
28 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 For V ertical T erminations - T o locate the vent and install the vent sections: • Locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint.
29 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Step 4. Positioning, Leveling, and Securing the Fireplace • Place the fireplace into position. • Level the fireplace from side to side and from front to back. • Shim the fireplace with non-combustible material, such as sheet metal, as necessary .
30 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 • Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.
31 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Step 8. Wiring the Fireplace NOTE: Electrical wiring must be installed by a licensed electrician. CAUTION: DISCONNECT REMOTE CONTROLS IF AB- SENT FOR EXTENDED TIME PERIODS.
32 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Wall Switch Position the wall switch in the desired position on a wall. Run a maximum of 25 feet (7.8 m) or less length of 18 A.W .G . minimum wire and connect it to the fireplace ON/OFF switch pigtails.
33 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 QV-S T - HV-I PI TO P E DG E SI DE E D GE QV- PI ER-HV -IPI TO P E DG E SI DE E DG E 0” GAP 0” GAP Step 9.
34 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Inst alling the T rim Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but MUST NEVER overlap onto the front face.
35 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Figure 45. Figure 46. S tart by applying the teco-sil (granulated glass) to the base pan (see Figure 46). Pile a thin layer and follow the pattern on the base pan (see Figure 47).
36 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Turn on the electric ember lights and paint the glass to a darkness as desired (see Figure 50). Figure 50. Make sure to paint the glass from both sides (see Figure 5 1 ).
37 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Ember Light Replacement Bulb In the lower gas valve compartment you will find three ac- cess panels for the three light bulbs (see Figure 54). Figure 54. Using a 5/16” nut driver remove the two bolts (see Figure 55 ).
38 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 4 Maint aining and Servicing Y our Fireplace Fireplace Maintenance Although the frequency of your fireplace servicing .
39 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 T roubleshooting 5 With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service.
40 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Intellifire Ignition System - (continued) Sym pt om Possibl e C auses C orr ecti ve Act i on s c. M odu l e is n ot grou n ded. V er i fy t h at m odu le is secu r ely gr ou n ded t o met al c h assis of applian ce.
41 Quadra-Fire • QV -PIER, QV -ST Series: HV -IPI • 2005-901 Rev . G • 2/06 Lifet ime Warrant y Î LIMITED LIFETIME W ARRANTY The Hearth & Home T echnologies limited Lifetime Warranty guaran.
Een belangrijk punt na aankoop van elk apparaat Quadra-Fire QV-PIER (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Quadra-Fire QV-PIER heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Quadra-Fire QV-PIER vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Quadra-Fire QV-PIER leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Quadra-Fire QV-PIER krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Quadra-Fire QV-PIER bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Quadra-Fire QV-PIER kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Quadra-Fire QV-PIER . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.