This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference. Catalog No: 1000.57A Effective: 02-28-07 Replaces: 02-24-06 P/N 241275 Rev .
2.
GENERAL SAFETY T o meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F . However , water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water , the rec- ommended initial setting for the temperature control is 125°F .
4 COLD WA TER ST AR T Before arriving at the job site to begin the installation, it's important to first inspect the system and determine what materials you will need. Some parts are includ- ed with the controller while others you will need to provide.
5 Connecting P ow er to the Controller Supply power from the 120 V AC power input from the heater to the controller power inputs T erminal Block (TB1). This is accomplished by connecting wiring from the control box to the heater TB1 board 120 V AC power input connections.
6 Cold Star t Sequence of Operation 1) 120V AC to heater sends 120V AC to Cold Start control on terminal block 1. 2) 120/24V AC transformer and 120V AC-12VDC con- verter are powered.
7 NO TE: Elodrive actuator is Nema 4 rated. TR OUBLESHOO TING Check your power source using a V olt-Ohm meter; check the following voltages at TB1 terminal block: TB1-1 to TB1-2 = 108 V AC Minimum, 132 V AC Maximum TB1-1 to TB1-3 = 108 V AC Minimum, 132 V AC Maximum TB1-2 to TB1-3 = Must be less than .
8 Cold Wa ter Star t T r oubleshooting Guide.
9 W iring Dia gr am.
10 COLD WA TER R UN Pur pose The Cold W ater Run system utilizes a variable-speed pump to inject the proper amount of water from the main system loop into the boiler to maintain the opti- mum inlet temperature.
11 Injection & Heater Pump Comparison — Hi Delta Heater Pump Injection Pump Heater Model Flow T emp. Rise Press. Drop Flow T emp. Rise Injection Pump Heater Pump 302 32 16 2 13 40 191 1- 1 ⁄ 4 hp 11 2 402 34 20 2 17 40 191 1- 1 ⁄ 4 hp 11 2 502 42 20 2.
12 Fig. 13: Remove the pump body Fig. 14: Be sure not to damage the seal when removing or replacing the pump body Injection Pump Co v er Installation Before Star ting 1) T urn off power to the unit at the circuit breaker . 2) T urn off gas supply . 3) Shut off the water supply to the heater and, if nec- essary , drain water from the system.
13 3. Insert and tighten all eight (8) wrench bolts, secur- ing the pump body in place. 4. Y ou will now be able to install the pump cover . See Fig. 18 and 19.
14 Typical Boiler Piping (Hi Delta sho wn).
15 ST AR T -UP PROCEDURE • Run full system flow for two minutes. • Initiate PID pump control to achieve target inlet temperature by slowing injector pump. • Boiler ΔT will not increase during bypass operation. • If target temperature is not achieved after seven minutes from “call for heat”, the system will shut down.
16 W iring Dia gr am.
17 Cold Wa ter Run T roubleshooting Guide Ste p 9 Ste p 8 Ste p 10 Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Is th ere a C all F or Heat at t he heat er? Is th e 220 VAC inver ter in t he cold .
18 ILL USTRA TED P ARTS LISTS Cold Wa ter Star t.
19 1-M 4-M 2-M 3-M CALL OUT DESCRIPTION HI DEL T A MVB F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 8 1 7 1 1 0 F 8 1 7 1 1 0 R E M R O F S N A R T C - 2 3-C POWER SUPPL Y.
20 Cold Wa ter Run.
21 CALL OUT B V M A T L E D I H N O I T P I R C S E D F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 0 2 7 1 1 0 F 0 2 7 1 1 0 C A V 4 2 T D P D - Y A L E R C - 2 F 9 3 0 9 .
ww w .raypak.c om Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036 Litho in U.
Een belangrijk punt na aankoop van elk apparaat Raypak 241275 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Raypak 241275 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Raypak 241275 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Raypak 241275 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Raypak 241275 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Raypak 241275 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Raypak 241275 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Raypak 241275 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.