INST ALLA TION & OPERA TING INSTR UCTIONS Catalog No. 3000.51F Effective: 04-08-09 Replaces: 03-25-08 P/N 240726 Rev . 7 This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future reference.
2 Rev . 7 reflects the following: Changes to: Paragraph 3 of the GENERAL SPECIFICA TIONS section on page 6; Fig. 13 on page 14; paragraph one of the Electrical Wiring section on page 16; te Wiring Dia.
WARNINGS 4 Pay Attention to These T erms 4 GENERAL SAFETY 5 T ime/T emperature Relationships in Scalds 5 RECEIVING EQUIPMENT 6 GENERAL SPECIFICA TIONS 6 INST ALLA TION 8 Code Requirements 8 Mounting B.
4 D ANGER: Indicates the presence of immediate hazards which will cause severe personal injury , death or substantial property damage if ignored. WARNING: Indicates the presence of hazards or unsafe practices which could cause severe personal injury , death or substantial property damage if ignored.
5 GENERAL SAFETY T o meet commercial hot water requirements, the tank- stat is adjustable up to 190°F . However , water temperatures over 125°F can cause severe burns instantly or death from scalds. This is the preferred starting point for setting the control for supplying gen- eral purpose hot water .
6 RECEIVING EQUIPMENT On receipt of your equipment it is suggested that you visually check for external damage to the carton. If the carton is damaged, it is suggested that a note be made on the Bill of Lading when signing for equipment. Remove the heater from the carton and if it is dam- aged report the damage to the carrier immediately .
7 OUT IN G GAS C OUTDOOR BASE A 8 J K A 2 26-1/2 21-1/4 ELEC CONN H UP FRONT CONTROLS 40 ST ACKLESS OUTDOOR TOP 13-1/4 8-1/2 11 6-3/4 26-1/2 2-1/2 OPTIONAL COMBUSTIBLE FLOOR SHIELD 38 Fig. 2: Dimensions and System Component Layout T ANK HEATER UPPER LO WER Components should be placed as close as possible.
8 INST ALLA TION Code R equir ements Installation must be in accordance with local codes, or , in the absence of local codes, with the latest editions of the National Fuel Gas Code, ANSI Z223.1,/NFP A 54, and the National Electrical Code, ANSI/NFP A 70.
9 1. The heater must be provided with adequate sup- ply of air for proper combustion and ventilation in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.
10 2. Attach mounting angles to heater jacket with 1/2" sheet metal screws, (4 places). 3. Lower outdoor top to heater and secure with 1" sheet metal screws. Indoor Models The drafthood is shipped separately and must be installed on the heater .
11 Models 0330, 0331, 0400 & 0401 V ent T er minal/Indoor Stac k Installation 1. Remove the louvered jacket top by removing four (4) #10 flat head screws. 2. If originally installed, remove "Pagoda" top from the louvered jacket top. 3. Place the inner stack adapter panel over the flue collector inside the heater .
12 The weight of the vent stack or chimney must not rest on heater draft hood. Support must be provided in compliance with applicable codes. The heater top and draft hood must be readily removable for maintenance and inspection. V ent pipe should be adequately sup- ported to maintain proper clearances from combustible construction.
13 ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. (d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust tankstat so appliance will operate continuously . (e) T est for spillage at the draft hood relief opening after 5 minutes of main burner operation.
14 Gas Pressur e Specifications Gas Pressur e Regulator The gas valve is provided with pressure taps to meas- ure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres- sure. T ype of Gas Inches WC Regulator Setting Min.
15 If this water heater is installed in a closed water supply system, such as one having a back-flow preventer in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situ- ation.
16 Electrical W iring The electrical power supply requirement for these heaters is 120 volts, 60 Hz. Field wiring connections and electrical grounding must comply with the local codes, or in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFP A 70.
17 W iring Dia g r ams Fig. 15: Standing Pilot Model 0260 (FIELD INST ALLED).
18 Fig. 16: Intermittent Ignition Device (IID) Model 0260.
19 Fig. 17: Intermittent Ignition Device (IID) Models 0330 & 0400.
20 Fig. 18: Intermittent Ignition Device (IID) Model 0261 Low NOx.
21 Fig. 19: Intermittent Ignition Device (IID) Models 0331 & 0401 Low NOx.
22 SER VICING PR OCEDURES Sequence of Oper ation Inter mittent Ignition De vice (IID) Heaters equipped with the IID system will automatical- ly light the pilot burner first and then the main burner , each time there is a call for heat from the tankstat.
23 F or Standing Pilot Model with R ober tshaw Gas V alv e, On/Of f Operation 1. STOP! Read the safety information above. 2. Set the tankstat on the lowest setting. 3. T urn OFF all electric power to the heater . 4. Remove heater door panel. 5. Push in gas control knob slightly and turn clock- wise to "OFF".
24 * If red reset button does not pop up when released, STOP and immediately call your service technician or gas supplier. * If the pilot does not stay lit after several tries, turn the gas control knob to "OFF" and call your Service technician or gas supplier.
25 For Honeywell Gas V alve: T urn gas control knob counter-clockwise from “OFF” until it stops. Push in gas control knob and continue rotating counter-clockwise to “ON” position. Make sure knob rest against stop. For Honeywell Gas V alve: T urn gas control knob counter-clockwise to “ON”.
26 Inspection Procedur es Bur ner s Clean main burners and air louvers of dust, lint and debris. Keep heater area clear and free from com- bustibles and flammable liquids. Do not obstruct the flow of combustion and ventilating air . Make visual check of burner and pilot flame.
27 Operation On call for heat, the ignition system, consisting of an electronic spark module, gas pilot system is energized. Providing pilot is proven blower will start running, the main gas valve will open and the heater will operate. When the operating control is satisfied the heater will shut down.
28 10. Carefully slide out the burner tray assembly . 1 1. Reverse above procedure to reinstall. Gas V alve R emo val 1. Shut off main electrical power switch to heater . 2. Shut off gas supply to the heater . 3. Remove front door . 4. Disconnect gas line from gas valve.
29 The heater may be cleaned from the side opposite the water connections, without breaking pipe connections. It is preferable, however , to remove both headers for better visibility through the tubes and to be sure the residue does not get into the system.
30 These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed.
31 1) Adjust inlet gas pressure as shown on rating plate. 2) Clean pilot orifice. 3) Replace thermocouple. 1 ) Adjust manifold pressure as shown on rating plate. 2) Clean burners free of debris or insects. 3) Clean gas line or increase gas line piping.
32 NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure. Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Pull ignition lead and check spark at module. Spark Okay? YES • Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
33 Electrical (Standing Pilot) START HEATER R E N R U B T O L I P F I S T H G I L R E N R U B T O L I P F I BUT MAIN BURNERS DO S E O D T O N NOT LIGHT CHECK FOR 24 V CH ECK THERMOCOUPLE AT GAS VALVE F I .
34 ADJUSTMENTS & REPLA CEMENT OF COMPONENTS Gas V alve R emo val 1. Shut off gas supply to the heater . Remove gas pip- ing to gas valve inlet. 2. Disconnect wires, pilot tubing and bleed line, if required. 3. Turn vertical gas pipe from manifold slightly and unscrew gas valve.
35 Circulator R eplacement 1. Shut off electrical power to the heater . 2. Shut off water supply and open drain valve to remove water in the piping at the pump level. 3. Disconnect wiring and conduit connections to the pump. 4. Remove the nuts and bolts at the inlet and outlet flanges.
36 LIMITED PARTS WARRANTY ECONOPAK WATER HEATERS MODELS WH - 0260 TO 0 401 SCOPE: Raypak, Inc. ("Raypak") warrants to the original owner that all parts of this water heater which are actuall.
37.
38.
39.
ww w .ra y pak.com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A..
Een belangrijk punt na aankoop van elk apparaat Raypak 2600401 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Raypak 2600401 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Raypak 2600401 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Raypak 2600401 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Raypak 2600401 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Raypak 2600401 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Raypak 2600401 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Raypak 2600401 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.