SERVICE Manual CONTENTS AIR CONDITIONER 1. Installation 2. Disassembly and Reassembly 3. T roubleshooting 4. Exploded Views and Parts List 5. Refrigerating Cycle Block Diagrams 6.
1 1. Installation 1-1 Refrigerant Refill Procedure INDOOR A-UNIT INDOOR B-UNIT • Piping length and the height Additional refrigerant char ge (R22,g) • When length of the pipe is over 5u by the uni.
2 1-2 “Pump down” Procedure Relocation of the air conditioner 1. Carry out the pump down procedur e (refer to the details of ‘pump down’). 2. Remove the power cord. 3. Disconnect the assembly cable from the indoor and outdoor units. 4. Remove the flare nut connecting the indoor unit and the pipe.
3 2. Disassembly and Reassembly 2-1 Indoor Unit Stop operation of the air conditioner and remove the power cable befor e repairing the unit. No Parts Procedure Remark Front Grille 1 1) Stop the air conditioner operation and block the main power . 2) Separate tape of front panel upper .
4 No Parts Procedure Remark Electrical Parts (Main PCB) Ass’y T ray Drain. Heat Exchanger Fan Motor and Cross Fan 2 3 4 5 1) Do “1”above. 2) T ake all the connector of PCB upper side out. (Inclusion Power cord) 3) Separate the outdoor unit connection wire from the terminal block.
5 2-2 Outdoor Unit No Parts Procedure Remark Cabinet Fan Motor & Propeller Fan 1) T urn off the unit and remove the power cable. 2) Remove the top cover . 3) Remove the control box cover . 4) Unplug the ass'y cable. 5) Remove the cabi-side. 6) Remove the cabi-front.
6 1) The input voltage should be rating voltage ± 10% range. The airconditioner may not operate pr operly if the voltage is out of this range. 2) Is the link cable linking the indoor unit and the outdoor unit linked pr operly? The indoor unit and the outdoor unit shall be linked by 5 cables.
7 Display Standard T imer Nature Power (GREEN) X (GREEN) X X (GREEN) (GREEN) X X X X X X X X X X X X X Restore from power failure (input initial power) Indoor unit Room sensor Error (open or short) In.
8 3-2 Checking and T esting Operations (Outdoor Unit) T o complete the installation, perform the following checks and tests to ensur e that the air conditioner is operating correctly .
9 4. Check the test operation status by pressing the PCB switch 4. S/W -A and S/W -B of outdoor unit. 4. • Check the operation status by pushing the switch one at time. 4. • Perform the test operation only for the unit selected last. 4. • Check the pipe pressur e and the other operation status during the test operation.
10 DISPLA Y EXPLANA TION Outdoor sensor error (Short/Open) Outdoor A cond pipe sensor error (Short/Open) Outdoor B cond pipe sensor error (Short/Open) Outdoor C cond pipe sensor error (Short/Open) A u.
11 3-3 Fault Diagnosis by Symptom 3-3-1 No Power (completely dead)-Initial diagnosis 1) Checklist : (1) Is input voltage normal? (2) Is AC power linked correctly? (3) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.
12 3-3-2 When the power voltage is not available 1) Inspection items (1) Is the power voltage is normal? (The rating voltage ± 10% range) (2) Is the power cord is corr ectly connected and is the cont.
13 3-3-3 No Power (Outdoor unit) 1) Inspection items (1) Á Is the power source normal (The rating V oltage ± 10% range)? (2) Is the outdoor power connected normally? ((1) of terminal : L, (2) of ter.
14 3-3-4 When the fan of indoor unit does not operate 1) Inspection items (1) Is the power voltage normal? (2) Is the connector of indoor fan with the good contact? (CN73) (3) Is the soldering status .
15 3-3-5 When the outdoor unit fan does not operate 1) Inspection items (1) The outdoor unit fan motor operates only when the operating conditions are satisfied and is selected by the R Y74(LOW) and PY75(HI) to rotate.
16 3-3-6 When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis) 1) Checklist : (1) Is input voltage normal? (2) Is the UP/DOWN louver motor properly connected with the connector (CN61)? 2) T roubleshooting pr ocedure Remove power cord and plug in again in approx.
17 3-3-7 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis) 1) T r oubleshooting procedur e Remove power cord and plug in again approx. 5 Seconds Is operation lamp blinking? Check as in the procedure “NO Power parts”. Refer to page 11.
18 3-3-8 When the 4 way valve (A,B) is not operating 1) Inspection items (1) Are the 4 way valve A and B under the operating conditions? (When the COMP A (4 way valve A ) and COMP B (4 way valve B) ar.
19 3-3-9 When the compressor does not operate 1) Inspection items (1) Is the COMP A under the operating conditions? (cooling operating of A, B(C) r oom) (2) Is the power voltage normal? (the rating vo.
20 3-4 Set up the Model option • It is necessary to set up option code after replacing the main-PCB as a service parts. Make sure that you can set up the option of code the r emote controller after you replace the main PBA otherwise, the unit won’t be working pr operly and all LED lamps on display will be flickering.
21 ! If the first number is , it is correct otherwise pr ess until appear . @ When pressing the button ~ appear on the display , select one of them. # When pressing the button ~ appear on the display , select one of them. $ When pressing the button ~ appear on the display , select one of them.
22 <T able of the option code> MODEL AD26B1C13 AD18B1C09 OPTION CODE 015773-100373 015223-10020C DB98_05645A(1)_1 5/30/02 7:05 PM Page 22.
23 MEMO DB98_05645A(1)_1 5/30/02 7:05 PM Page 23.
24 4. Exploded V iews and Parts List 4-1 Indoor Unit 17 16 14 22 9 7 21 3 4 5 6 19 20 8 12 25 13-4 23 13-3 13-2 13 13-1 11 10 2 1 15 18-1 18-5 18-4 18 18-6 18-6-1 18-2 18-3 24 DB98-05645A(1)-2 5/30/02.
25 Q’TY ■ Parts List CODE NO No. Description REMARK AD18B1C09 AD26B1C13 1 2 3 4 5 6 7 8 9 10 11 12 13 13-1 13-2 13-3 13-3-1 13-3-2 13-4 14 15 16 17 18 18-1 18-2 18-3 18-4 18-5 18-6 18-6-1 19 20 21.
26 4-2 Outdoor Unit 4-2-1 UD26B1C2 12 15 8 17 3 4 5 7 6 9(9-1~9-2) 14(14-1~14-4) 2 1 10 13(13-1~13-6) 16(16-1~16-7) 11 DB98-05645A(1)-2 5/30/02 7:06 PM Page 26.
27 Q’TY ■ Parts List CODE NO No. Description Specification REMARK UD26B1C2 1 2 3 4 5 6 7 8 9 9-1 9-2 10 11 12 13 13-1 13-2 13-3 13-4 13-5 13-6 14 14-1 14-2 14-3 14-3-1 14-4 14-4-1 15 16 16-1 16-2 .
28 4-2-2 UD18B1C2 15 16(16-1~16-7) 13(13-1~13-6) 14(14-1~14-4) 9 3 1 10 4 6 5 7 8 2 11 17 12 DB98-05645A(1)-2 5/30/02 7:06 PM Page 28.
29 Q’TY ■ Parts List CODE NO No. Description Specification REMARK UD18B1C2 1 1-1 2 3 4 5 6 7 8 9 10 11 12 13 13-1 13-2 13-3 13-4 13-5 13-6 14 14-1 14-2 14-3 14-3-1 14-4 14-4-1 15 16 16-1 16-2 16-3.
30 4-3 ASS’Y CONTROL IN (DB93-01223A) ■ Parts List No 1 2 3 4 5 6 7 8 9 10 11 Description HOLDER CONTROL ASS’Y MAIN PCB TERMINAL BLOCK ASSY ASSY DISPLA Y PCB CONNECTOR WIRE PCB U/D HOLDER CLAMP .
31 5. Refrigerating Cycle Block Diagram Refrigerating cycle temperature and pressure STD Pressure Piping T emp.(°F) T emp. Condition (°F) Operating Condition (psi) T1 T2 Indoor Outdoor 3-W A Y V/V DB WB DB WB Standard 57-71 50-54 50-54 80 67 95 75 Cooling Max over load - 61-64 61-64 80 67 115 75 Low temp.
32 6. Wiring Diagrams 6-1 Indoor Unit DB98-05645A(1)-2 5/30/02 7:06 PM Page 32.
33 6-2 Outdoor Unit DB98-05645A(1)-2 5/30/02 7:06 PM Page 33.
7. Schematic Diagrams 7-1 Indoor Unit ■ AS07A5(6)MA / AS09A5(6)MA 34 35.
37 36 7-2 Outdoor Unit ■ AS07A5(6)MA / AS09A5(6)MA.
ELECTRONICS Printed in Korea. DB98_05645A(1)-co 5/30/02 7:50 PM Page 2.
Een belangrijk punt na aankoop van elk apparaat Samsung AD26B1C13 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Samsung AD26B1C13 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Samsung AD26B1C13 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Samsung AD26B1C13 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Samsung AD26B1C13 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Samsung AD26B1C13 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Samsung AD26B1C13 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Samsung AD26B1C13 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.