Gebruiksaanwijzing /service van het product CHDZR09053 van de fabrikant Sanyo
Ga naar pagina of 106
a Outdoor Units 85464369098000 ©SANYO 2008 – W -3W A Y ECO-i System Air Conditioner – R410A Models Indoor Units Class 9 12 18 24 36 48 X 4-W ay Air Discharge Semi-Concealed T ype XHX1252 XHX1852 .
2 IMPOR T ANT! Please Read Bef ore Star ting This air conditioning system meets strict safety and oper- ating standards. As the installer or ser vice person, it is an impor tant par t of your job to install or service the system so it operates saf ely and efficiently .
3 2. The standards f or minimum room v olume are as follows . (1) No par tition (shaded por tion) (2) When there is an effectiv e opening with the adjacent room f or ventilation of leaking refrigerant gas (open- ing without a door , or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
4 New tool? 1-2. Pre vent impurities including water , dust and o xide from entering the tubing. Impur ities can cause R410A refriger- ant deterioration and compressor def ects. Due to the features of the refrigerant and refrigerating machine oil, the pre vention of w ater and other impur ities becomes more impor tant than ev er .
5 V alve Liquid 3-2. Use R410A exclusiv e cylinder only . Single-outlet valve (with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown. New refrigerant R410A cannot be used f or earlier models 1. Compressor specifications are different.
6 CONTENTS P age P age IMPORT ANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant New refrigerant R410A cannot be used for earlier models 1.
7 P age 6. HOW TO PROCESS TUBING . . . . . . . . . . . . 76 6-1. Connecting the Refrigerant T ubing 6-2. Connecting T ubing Between Indoor and Outdoor Units 6-3. Insulating the Refrigerant T ubing 6-4. T aping the T ubes 6-5. Finishing the Installation 7.
8 T able 1-1 Outdoor Unit 1-2. Accessories Supplied See T ab les 1-1 – 1-8. 1-1. T ools Required for Installation (not supplied) 1. Flathead screwdriver 2. Phillips head screwdriver 3. Knife or wire stripper 4. T ape measure 5. Car penter’ s lev el 6.
9 T able 1-2 (4-W ay Air Dischar ge Semi-Concealed) (X-T ype) T able 1-3 (1-W ay Air Dischar ge Semi-Concealed) T able 1-4 (Concealed Duct) ● Use M10 or 3/8" f or suspending bolts.
10 T able 1-5 (Concealed Duct High-Static Pressure) T able 1-6 (Ceiling-Mounted) Part Name Figure Q’ty Remarks 8 For suspending indoor unit from ceiling W asher 8 For suspending indoor unit from cei.
11 H3 LM LA LF LB LC L4 LG LH LD L2 H2 L1 H1 LE L3 C B 4 1 2 3 5 6 7 40 1. Main tubing length LM = LA + LB … b 262 ft. 2. Main distribution tubes LC – LH are selected according to the capacity after the distribution joint. 3. Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
12 *1: If future extension is planned, select the tubing diameter based on the total horsepo wer after e xtension. Howe ver e xtension is not possible if the resulting tubing size is two r anks higher. *2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.
13 1-7. Straight Equivalent Length of Joints Design the tubing system by ref erring to the following tab le for the straight equiv alent length of joints. T able 1-14 Straight Equivalent Length of Joints T able 1-15 Refrigerant tubing (Existing tubing can be used.
14 Common solenoid valve kit ● Multiple indoor units under group control can utilize a solenoid v alve kit in common. ● Categories of connected indoor unit capacities are deter mined by the solenoid v alve kit. T able 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit) DC CHDZ09053 CHDZ14053 CHDZR09053 CHDZR14053 (oz) 416 416 1-9.
15 W ARNING Always check the gas density limit for the room in which the unit is installed. 1-1 1. Check of Limit Density When installing an air conditioner in a room, it is necessar y to ensure that e ven if the refrigerant gas accidentally leaks out, its density does not e xceed the limit le vel f or that room.
16 1-13. Optional Distribution Joint Kits See the installation instructions packaged with the distribution joint kit f or the installation procedure. T able 1-19 1. APR-CHRZP900BAB F or outdoor unit (Capacity after distribution joint is 307.100 BTU/h or less.
17 2. APR-RZP224BAB Use: For indoor unit (Capacity after distrib ution joint is 76.400 BTU/h or less.) 3. APR-RZP680BAB Use: For indoor unit (Capacity after distrib ution joint is greater than 76.400 BTU/h and no more than 232.000 BTU/h.) 4. APR-RZP1350BAB Use: For indoor unit (Capacity after distrib ution joint is greater than 232.
18 Part Number Cover of relay kit 14 Relay kit 13 Cover of control box 12 Earth (M5 with washer) 11 Terminal for communication line 10 Terminal for power line 9 Base of control box 8 Service panel 7 D.
19 Part Number Cover of relay kit 14 Relay kit 13 Cover of control box 12 Earth (M5 with washer) 11 Terminal for communication line 10 Terminal for power line 9 Base of control box 8 Service panel 7 D.
20 Suspension bolt (3/8" or M10) (field supplied) Nut (field supplied) (3/8" or M10) W asher M4 screws (12 pcs.) Suspension hook Notes on Installation • Be sure to secure the v alve body b y using its str ucture with the suspension bolt, etc.
21 1-15. Example of T ubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in T ables 1-10, 11, 12, 15 and 16-2 use the liquid tubing siz e and length, and calculate the amount of additional refrigerant charge using the formula below .
22 Checking of limit density Density limit is determined on the basis of the size of a room using an indoor unit of minimum capacity . F or instance, when an indoor unit is used in a room (floor area 161 ft. 2 × ceil- ing height 8.8 ft. = room volume 1417 ft.
23 2. SELECTING THE INST ALLA TION SITE 2-1. Indoor Unit A V OID: ● areas where leakage of flammable gas ma y be expected. ● places where large amounts of oil mist exist. ● direct sunlight. ● locations near heat sources which may aff ect the perf or mance of the unit.
24 Fig. 2-5 Fig. 2-6 Fig. 2-7 2-2. Outdoor Unit A V OID: ● heat sources, e xhaust fans, etc. ● damp , humid or unev en locations ● indoors (no-ventilation location) DO: ● choose a place as cool as possible . ● choose a place that is well v entilated.
25 2-3. Precautions When Installing in Heavy Snow Areas a) The platf or m should be higher than the maximum snow depth. (Fig. 2-8) b) The 2 anchoring f eet of the outdoor unit should be used f or the platform, and the platf or m should be installed beneath the air-intake side of the outdoor unit.
26 33-3/16 2-11/64 15/16 97-29/32 65-53/64 (32-5/64) 35-15/64 (Maximum brac ket dimensions) 35-3/64 (Ceiling panel dimensions) 33-3/16 35-15/64 (Maximum brac ket dimensions) 35-3/64 (Ceiling panel dim.
27 97-29/32 65-53/64 36-7/64 45-5/16 (32-5/64) Air direction: F ront direction Air direction: Right direction Ceiling panel T op (Bef ore installation of snowf all protection duct) Ceiling panel F ront view Right side view F ront view Right side vie w Ceiling panel F ront view Right side view unit: in.
28 X 3. HOW TO INST ALL THE INDOOR UNIT ■ 4-W ay Air Dischar ge Semi-Concealed T ype (X T ype) 3-1. Preparation for Suspending This unit uses a drain pump .
29 X Fig. 3-5 (2) The length of suspension bolts m ust be appropriate f or a distance between the bottom of the bolt and the bottom of the unit of more than 19/32 in. as shown in Fig. 3-5. (3) Thread the 3 hexagonal n uts and 2 washers (field supply) onto each of the 4 suspension bolts as shown in Fig.
30 X Fig. 3-9 11-3/16 in. or less (as shor t as possible) 33-15/32 in. or less 0 – 45° * Length of supplied drain hose = 9-27/32 in. Fig. 3-10 Upward gradient prohibited Fig. 3-11 Fig. 3-12 Suppor t pieces W ater (Approx. 0.3 gal) Drain pan outlet Drainage check Plastic container for w ater intake Over 3-15/16 in.
31 X Air-intake grille Ceiling panel Air-intake grille hinge 1 1 3-6. How to Install the Ceiling P anel 3-6-1. Before Installing the Ceiling P anel Checking the unit position (1) Check that the ceiling hole is within this range: 33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.
32 X 3-6-2. Installing the Ceiling Panel After completing the wiring process, install the supplied wiring cov er before installing the panel. It is not possible to install the wiring cov er after install- ing the panel. The power m ust be tur ned ON in order to change the flap angle.
33 X 3-6-3. Wiring the Ceiling P anel (1) Open the cov er of the electr ical component box. (2) Connect the 7P wiring connector (red) from the ceiling panel to the connector in the unit electrical component bo x. (Fig. 3-24) ● If the connectors are not connected, the Auto flap will not operate.
34 X 3-6-5. Checking After Installation ● Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling surf ace. Gaps may cause w ater leakage and condensation. ● Check that the wiring is securely connected.
35 XM ■ 4-Wa y Air Discharge Semi-Concealed T ype (XM T ype) 3-8. Preparation for Suspending This unit uses a drain pump . Use a car penter’ s lev el to check that the unit is le vel.
36 XM 3-11. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O .D . 1-1/32") for the drain and use the supplied hose band to pre vent water leaks . (Fig. 3-33) The PVC pipe must be purchased separately . The transparent drain part on the unit allows you to check dr ainage.
37 XM 3-12. Checking the Drainage After wiring and drain piping are completed, use the follo wing pro- cedure to check that the w ater will drain smoothly . F or this, pre- pare a bu ck et and wiping cloth to catch and wipe up spilled water . (1) Connect power to the po wer ter minal board (R, S terminals) inside the electr ical component box.
38 XM ● If the scre ws are not sufficiently tight- ened, trouble such as that sho wn in the figure below ma y occur. Be sure to tighten the screws securely . ● If a gap remains between the ceil- ing surface and the ceiling panel ev en after the screws are tightened, adjust the height of the unit again.
39 XM 3-13-5. Checking After Installation ● Check that there are no gaps between the unit and the ceiling panel, or betw een the ceiling panel and the ceiling surf ace. Gaps ma y cause water leakage and condensation. ● Check that the wiring is securely connected.
40 A ■ 1-W ay Air Dischar ge Semi-Concealed T ype (A T ype) 3-14. Suspending the Indoor Unit (1) Follo w the diagrams to mak e the holes in the ceiling. (Figs. 3-52 and 3-53) (2) Depending on the ceiling type: ● Inser t suspension bolts as shown in Fig.
41 A Fig. 3-57 Fig. 3-56 3-15. Placing the Unit Inside the Ceiling (1) Use the supplied M5 or 3/16" screws (4) to attach the full-size installation diag ram to the indoor unit suspension lugs, in order to obtain the ceiling opening dimensions f or suspending the unit.
42 A Fig. 3-60 Fig. 3-61 2-1/8 Suspension bolts T ubing side 19/32 19/32 2-1/8 Suspension bolts 25/32 25/32 25/32 Ceiling material ● The indoor unit includes a drain pump.
43 A Fig. 3-64 Air bleed v alve Fig. 3-66 Fig. 3-65 0 – 45° 11-13/16 in. or less 33-15/32 in. or less * Length of supplied drain hose = 9-27/32 in. Uphill slope Fig. 3-67 Suppor t brack et CA UTION 3-17. Checking the Drainage After wiring and drain piping are completed, use the f ollowing procedure to chec k that the water will drain smoothly .
44 A Refrigerant tubing joint (gas tube) Refrigerant tubing joint (liquid tube) Drain pipe connection (Be sure to connect the supplied flexib le hose.) Inter-unit Control Wiring P ower supply outlet Fig. 3-69 ● Route the power wiring into the indoor unit thr ough the power inlet on the side of the unit.
45 A Hook Screw Hinge Intake grille Slide Press on the tabs with a flathead (minus) screwdriver while pulling out the intak e grille. Screw Removing the intake grille Slide the intake g rille hooks (2 locations) in the direction of the arrow to open the intak e gr ille.
46 A (5) Align the installation holes on the panel with the bolt holes on the unit. (6) Inser t the supplied washer head bolts into the 4 panel installation holes, and tighten until the panel is securely f astened against the unit. (Fig. 3-77) (7) V er ify that the panel is securely f astened against the unit.
47 A 3-19-3. Wiring the ceiling panel (1) Loosen the 2 screws on the electrical component bo x lid, and remov e the lid. (Fig. 3-80) (2) F asten the wir ing connector (7P , red) which comes out from the ceiling panel using the lead wire clamps (2 locations) on the unit.
48 U Fig. 3-84 Fig. 3-85 Indoor unit Inspection access 17-23/32 17-23/32 Air outlet duct flange Min. 9-27/32 Min. 15-3/4 Min. 25-19/32 22-27/32 A (Suspension bolt pitch) Electrical component box Refrigerant tubing Min. 9-27/32 ■ Concealed Duct T ype (U T ype) 3-20.
49 U Fig. 3-86 3-21. Suspending the Indoor Unit Depending on the ceiling type: • Inser t suspension bolts as shown in Fig. 3-86 or • Use e xisting ceiling suppor ts or constr uct a suitable support as shown in Fig. 3-87. Hole-in-anchor Hole-in-plug Concrete Inser t Suspension bolt (M10 or 3/8") (field supply) Fig.
50 U Fig. 3-91 Fig. 3-92 Drain hose (supplied) (not supplied) (not supplied) P acking (supplied) VP-25 Align the hose band with end of the hose, and tighten so that it does not contact the bead. Drainage check section on drain port (transparent) Hard PVC sock et VP-25 Hard PVC pipe PVC adhesive Bead Vinyl clamps Drain insulator (supplied) 3-22.
51 U Fig. 3-97 Inter-unit control wiring P ower supply outlet (4) When the check of drainage is complete , open the check pin (CHK) and remount the insulator and drain cap onto the drain inspection port. CA UTION Be careful since the fan will star t when you short the pin on the indoor control board.
52 D ■ Concealed Duct High-Static Pressure T ype (D T ype) 3-25. Required Minimum Space for Installation and Service ● This air conditioner is usually installed abov e the ceiling so that the indoor unit and ducts are not visible . Only the air intake and air outlet ports are visible from below .
53 D Fig. 3-102 Hole-in-anchor Hole-in-plug Concrete Insert Suspension bolt (M10 or 3/8") (field supply) 3-26. Suspending the Indoor Unit Depending on the ceiling type: ● Inser t suspension bolts as shown in Fig. 3-102 or ● Use e xisting ceiling suppor ts or construct a suitable suppor t as shown in Fig.
54 D Fig. 3-105 Fig. 3-106 Fig. 3-107 Min. 1-31/32 in. Inspection plug Min. 3-15/16 in. Good Min. 1/100 Downward g radient Not good 3-27. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O .D . 1-1/4") f or the drain and use the supplied drain soc ket to pre v ent water leaks.
55 T ■ Ceiling-Mounted T ype (T T ype) 3-30. Required Minimum Space for Installation and Service (1) Dimensions of suspension bolt pitch and unit T able 3-6 Dimension T ype 12, 18 AB C 33-21/32 35-5.
56 T W ARNING It is important that you use extreme care in supporting the indoor unit from the ceil- ing. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the ceiling unit, test the strength of each attached suspension bolt.
57 T (5) Before suspending the indoor unit, remo ve the 2 or 3 scre ws on the latch of the air-intake g rilles, open the grilles, and remov e them by pushing the claws of the hinges as sho wn in Fig. 3-117. Then remov e both side panels sliding them along the unit tow ard the front after removing the 2 attachment scre ws.
58 T CA UTION ● Attach so that the hose band fastener is on the side of the drain port. (Fig. 3-130) ● Attach the hose bands so that each is appro ximately 13/64 – 63/64 in. from the end of the supplied drain hose. Good Min. 1/100 Downward g radient Not good Fig.
59 T 5-33/64 63/64 63/64 13/64 13/64 T wist tie (4 ties) Unit drain port Drain hose insulation (supplied) Hard PVC pipe (equivalent to VP-20) (Field supply) P osition to fasten hose bands Drain hose (supplied) Hose band (2 bands, supplied) Unit drain pan Fig.
60 K ■ W all-Mounted T ype (K T ype) 3-35. Removing the Rear P anel from the Unit (1) Remov e the set screws used to f asten the rear panel to the indoor unit during transpor tation. (2) Press up on the frame at the 2 locations shown b y the arrows in the figure at right, and remove the rear panel.
61 K (2) Check with a tape measure or carpenter’ s lev el. This is impor tant so that the unit is correctly installed. (Fig. 3-140) (3) Make sure the panel is flush against the w all. Any space between the wall and unit will cause noise and vibr ation.
62 K Insulating tape Refrigerant tubing Rear panel tab Plastic cov er Indoor and outdoor unit connection wiring (3) T o mount the indoor unit on the rear panel. 1. When installing the indoor unit, position the indoor unit onto the installation tabs on the upper par t of the rear panel.
63 K 3-42. When Using Wireless Remote Controller Instead of Wired Remote Controller When the wireless remote controller is to be used, slide the s witch on the indoor unit control PCB. • If this setting is not made, an alarm will occur . (The operation lamp on the display b links.
64 (P ositions where anchor bolts are fastened) 31-7/64 (Installation hole pitch) 37-13/32 (Maximum dimensions) 35-3/64 (Ceiling panel dimensions) 36-7/32 (Installation hole pitch) 35-3/64 (Ceiling panel dimensions) Installation anchor hole (4 – 19/32 s 25/32 oval holes) 4.
65 Fig. 4-7 4-3. Remove the Brackets Used for T ransport ● After installing the unit, remov e the 2 transpor t brac kets from the front and rear (4 brac kets total).
66 4-5. Prepare the T ubing ● Material: Use C1220 phosphorous deo xidized copper as described in JIS H3300, “Copper and Copper Allo y Seamless Pipes and T ubes. ” (F or tubes that are ø1" (ø25.4 mm) or larger , use 1/2H material or H mater ial.
67 ● Precautions for br azing Be sure to replace the air inside the tube with nitrogen to pre vent o xide film from forming during the brazing process. Be sure to use a damp cloth or other means to cool the valv e unit dur ing brazing. CA UTION 1. Be sure to use nitrogen.
68 Control wiring (A) Inter-unit (between outdoor and indoor units) control wiring (B) Remote control wiring (C) Control wiring f or group contr ol (D) Inter-outdoor unit contr ol wiring A WG #18 (0.75 mm 2 ) Use shielded wiring* Use shielded wiring Use shielded wiring Use shielded wiring Max.
69 * Disconnect switch ( Field Supply) * * * * * * U2 U1 L2 L1 R2 R1 2 1 U2 U1 4 3 3 4 5 2 1 WHT Remote controller BLK 2 1 2 1 WHT Remote controller Group control: BLK 2 1 2 1 WHT Remote controller B C Indoor unit (No . n) Indoor unit (No . 1) Indoor unit (No .
70 ● For XM T ype U2 U1 3 1 2 1 2 2 1 U2 U1 4 3 3 4 5 2 1 2 1 U2 U1 3 1 2 1 2 U2 U1 3 1 2 1 2 U2 U1 3 1 2 1 2 2 1 2 1 2 1 B C A L1 L2 L3 N L N L N L N L N 2 1 2 1 4 3 3 4 5 L1 L2 L3 N A D B B A A * .
71 Outdoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit more than 3.3 ft. more than 3.3 ft. Branch point 16 or fe wer Indoor unit Indoor unit Indoor unit Indoor unit less than 3.
72 Fig. 5-4 Stranded wire Ring pressure terminal Strip 3/8 in. Fig. 5-5 Wire Special washer Screw Ring pressure terminal T erminal plate Screw and Special washer Ring pressure terminal Wire W ARNING Loose wiring may cause the terminal to overheat or result in unit malfunction.
73 Earth screw Conduit Power wiring (field supplied) Optional remote control wire (field supplied) Earth screw Conduit Power wiring (field supplied) Clamping clip Optional remote control wire (field s.
74 Optional remote control wire (field supplied) Earth screw Conduit Power wiring (field supplied) Clamping clip Earth screw Conduit Clamping clip Power wiring (field supplied) Optional remote control.
75 Earth screw Clamping strap Conduit Power wiring (field supplied) Clasp Optional remote control wire (field supplied) 3-way connection wiring with harness (supplied) Entirely cover the remote wiring and the 3-way wiring harness with the clasp. Remote control wiring 5-5.
76 6. HO W TO PR OCESS TUBING The liquid tubing side is connected by a flare n ut, and the gas tubing side is connected by br azing. 6-1. Connecting the Refrigerant T ubing Use of the Flaring Method M.
77 Caution Before Connecting T ubes Tightly (1) Apply a sealing cap or water-proof tape to pre vent dust or water from entering the tubes bef ore they are used. (2) Be sure to apply refr igerant lubricant to the match- ing surf aces of the flare and union bef ore connecting them together .
78 Unit side insulator Insulation tape (white) (supplied) Sealer (supplied) Flare insulator (supplied) T ube insulator (not supplied) Heat resistant 248°F or abov e Vinyl clamps (supplied) Flare nut Fig.
79 Fig. 6-10 Fig. 6-11 6-4. T aping the T ubes (1) At this time, the refrigerant tubes (and electrical wir- ing if local codes per mit) should be taped together with ar moring tape in 1 bundle . T o prev ent the con- densation from ov erflowing the drain pan, k eep the drain hose separate from the refrigerant tubing.
80 Fig. 7-1a Fig. 7-2 Fig. 7-1b Fig. 7-3 7. AIR PURGING Air and moisture in the refrigerant system may ha ve undesirab le eff ects as indicated below .
81 Fig. 7-4 (3) Do a leak test of all joints of the tubing (both indoor and outdoor) and all ser vice v alves . Bubbles indicate a leak. Wipe off the soap with a clean cloth after a leak test. (4) After the system is found to be free of leaks , reliev e the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder .
82 Fig. 7-5 Fig. 7-6 NO TE The required time in the abov e table is calculated based on the assumption that the ideal (or target) vacuum condition is less than –14.7 psig (–755 mm Hg, 5 T orr). (2) When the desired vacuum is reached, close the “Lo” knob of the manif old valv e and tur n off the vacuum pump .
83 8. TEST RUN 8-1. Preparing for T est Run ● Before attempting to start the air conditioner , chec k the follo wing. (1) The control wiring is correctly connected and all electrical connections are tight. (2) The transpor tation pads f or the indoor fan ha ve been remov ed.
84 YES Make necessary corrections. Check the alarm contents. Check the alarm contents. T ur n OFF the indoor and outdoor unit power . NO YES NO *1 *2 *3 *3 *2 CASE 1 CASE 2 CASE 3B CASE 3A YES YES NO YES NO NO NO YES YES NO Recheck the items to check bef ore the test r un.
85 2 3 2 1 ON 1 ON ON 3 12 3 2 1 ON 3 2 1 ON 3 1 1 1 1 1 1 1 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 2 1 ON 2 1 ON ON 1 2 2 1 ON ON 1 2 3 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF 3 2 1 ON ON 12 3 2 1 ON 3 ON OFF ON OFF ON OFF L Examples of the No.
86 S003 CN100 CN101 CN003 S002 S004 S005 S006 S007 Fig. 8-4 8-3. Main Outdoor Unit PCB Setting W-3WAY_ECO-i_US.indd 86 W-3WAY_ECO-i_US.indd 86 2008/02/07 10:56:12 2008/02/07 10:56:12.
87 8-4. Auto Address Setting Basic wiring diagram: Example (1) ON 1 2 3 1 ON 3 2 ON 1 2 2 ON 1 3 3 2 1 ON ON ON OFF ON OFF ON OFF ON OFF OFF (S006) (S007) (S005) (S004) (S003) (S002) 1 1-1 1-2 1-3 1-10 • If link wiring is not used (The inter-unit contr ol wires are not connected to multiple refrigerant systems.
88 1-1 1-2 2-1 2-2 2-9 1-3 1-13 2 9 2 1 ON 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 2 ON 1 3 1 3 1 ON 3 2 ON 1 2 2 ON 1 3 3 2 1 ON ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Auto.
89 Case 1 Automatic Ad dress Setting (no compressor operation) ● Indoor and outdoor unit power can be turned ON f or each system separately . Indoor unit addresses can be set without operating the compressors . Automatic Address Setting from Outdoor Unit 1.
90 Case 2 Automatic Ad dress Setting in Heating Mode ● Indoor and outdoor unit power cannot be turned ON f or each system separately . In the f ollowing, automatic setting of indoor unit addresses is not possib le if the compressors are not operating.
91 Case 3 Automatic Ad dress Setting in Cooling Mode ● Indoor and outdoor unit power cannot be turned ON f or each system separately . In the f ollowing, automatic setting of indoor unit addresses is not possib le if the compressors are not operating.
92 is blinking LED 1 LED 2 ( : ON : Blinking : OFF) Display meaning After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor units in that system is possible .
93 Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them f or future ref erence.
94 8-7. Meaning of Alarm Messages T able of Self-Diagnostics Functions and Description of Alarm Displays Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB . They are also displa yed on the wired remote controller .
95 P ossible cause of malfunction Thermistor fault Protective device f or compressor is activated Indoor thermistor is either open or damaged. Outdoor thermistor is either open or damaged. Oil sensor fault. Indoor coil temp . sensor (E1) Indoor coil temp .
96 Alarm messages display ed on system controller Indoor or main outdoor unit is not operating correctly . Mis-wiring of control wiring between indoor unit, main outdoor unit and system controller . Indoor or main outdoor unit is not operating correctly .
97 X XM <How to remo ve the filter> 1. Use a screwdriv er to remov e the bolt screw on each side f or the two latches. (Be sure to reattach the two bolt scre ws after cleaning.) 2. Press on the two latches of the air intak e grille with your thumbs in the direction of the arrow to open the grille.
98 X XM 4. Remov e the air filter attached to the air intake grille. Care: After a prolonged idle period Care: Before a prolonged idle period Check the indoor and outdoor unit air intak es and outlets for bloc kage; if there is a bloc k- age, remo ve it.
99 A Air filter finger-hold Air filter Air intake grill Latch Air filter finger-hold Hook Screw Slide Screw *T ake hold of the finger-hold on the air filter , pull it toward y ou.
100 A Care: After a prolonged idle period Care: Before a prolonged idle period Check the indoor and outdoor unit air intak es and outlets for bloc kage; if there is a bloc kage, remov e it. • Operate the f an for half a da y to dr y out the inside. • Disconnect the power supply and also turn off the circuit breaker .
101 U D 9-3. Concealed Duct (High-Static Pressure) T ype (U, D T ypes) ■ NAME OF P ARTS ■ CARE AND CLEANING CONC EALED D UCT U ty p e (s ta n d a r d st at ic p r es s u re ) W a t e r d r a i n F.
102 U D ■ TROUBLESHOOTING If your air conditioner does not w ork proper ly , first check the f ollowing points bef ore requesting ser vice. If it still does no t work properly , contact your dealer or a service center. Air conditioner does not r un at all 1.
103 T Air intake grill finger-hold Air filter Air intake grill Air filter finger-hold Latch Air filter finger-hold * Take hold of the finger-hold on the air filter, pull it toward you.
104 T Care: After a prolonged idle period Care: Before a prolonged idle period Check the indoor and outdoor unit air intak es and outlets for bloc kage; if there is a bloc kage, remov e it. • Operate the f an for half a da y to dr y out the inside. • Disconnect the power supply and also turn off the circuit breaker .
105 K <How to remo ve the filter> 1. Mov e the flap on the air outlet gr ille to its low est position with the remote control unit. 2. The filter is disengaged by pushing the tab up gently . Hold the air filter by the tab at the bottom, and pull downw ard.
106 K Care: After a prolonged idle period Care: Before a prolonged idle period Check the indoor and outdoor unit air intak es and outlets for bloc kage; if there is a bloc kage, remov e it. • Operate the f an for half a da y to dr y out the inside. • Disconnect the power supply and also turn off the circuit breaker .
Een belangrijk punt na aankoop van elk apparaat Sanyo CHDZR09053 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Sanyo CHDZR09053 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Sanyo CHDZR09053 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Sanyo CHDZR09053 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Sanyo CHDZR09053 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Sanyo CHDZR09053 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Sanyo CHDZR09053 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Sanyo CHDZR09053 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.