Insta lla tion Manua l Cooling Solutions EcoBreeze™ System A CECFR20101SE, A CECFR20200SE, A CECFR20201SE, A CECFR40101SE, A CECFR40200SE, A CECFR40201SE 990-3976D-001 Publication Da te: J une 2014 .
Schneider Electric IT Corporation Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan.
Contents EcoBreeze System Installation i General Information ................................................................... 1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Inspecting the Equipment .
EcoBreeze System Installation ii Mechanical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Position the EcoBreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Unwrap the equipment .
1 EcoBreeze System Installation Gener a l Inf or ma tion Safety Read and adhere to the following important safety considerations when working with this cooling unit. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH T urn off all power supplying this equipment before working on the equipment.
EcoBreeze System Installation 2 Inspecting the Equipment Inspect for missing components. All shipped loose components are identified by part number and description on the bill of lading. Ensure each item is present before accepting delivery of the unit.
3 EcoBreeze System Installation Model Identif ica tion Model identification label loca tion F rames Modules Other components SKU Description ACECFR20101SEn* 6 m (20 ft) ISO Frame 400/3/50 ACECFR20200S.
EcoBreeze System Installation 4 Access Door and P anel Opera tion Module access doors and panels have latches with a locking mechanism. Secondary door latches are provided on doors on compartments that have positive air pressure to prevent the doors from opening quickly if a door is opened while the unit is in operation.
5 EcoBreeze System Installation Component Identif ica tion * V ersion shown is the 12 m (40 ft) model. Item Description Quantity 20 ft Quantity 40 ft EcoBreeze Frame and Module assembly* 1 1 R.
EcoBreeze System Installation 6 EcoBreeze F rame and Modules Item Description ISO corner fittings Return air inlets Module anchor brackets Module T ension rods and mounts Screw.
7 EcoBreeze System Installation Module — front Remote displa y interface na3665a SUPPLY BLOWER ACCESS COIL ACCESS COIL ACCESS Item Description Condenser coil Sprayer head and mist eliminator.
EcoBreeze System Installation 8 Site Prepar a tion Incoming power supply requirements N OTE : This equipment requires three-phase electrical service. Electrical service must conform to national and local electrical codes. The equipment must be grounded.
9 EcoBreeze System Installation Environment N OTE : Locating the EcoBreeze system near areas of increased airborne debris may result in more frequent service intervals.
EcoBreeze System Installation 10 Refrig era tion Each EcoBreeze Module contains its own closed refrigeration circuit. No field connections are required.
11 EcoBreeze System Installation Ser vice access Install a service platform (not supplied) to facilitate maintenance activities. Regular maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to remove, maneuver , and install Modules and components.
EcoBreeze System Installation 12 W eights and Dimensions F rame Frame (fully populated with Modules) Weight (dry) ACECFR20101SE4, ACECFR20200SE4, ACECFR20201SE4 7 863 kg (17,300 lb) ACECFR40101SE8, AC.
13 EcoBreeze System Installation Installa tion Lifting and Rig ging EcoBreeze Frame. The EcoBreeze Frame is not equipped with forklift pockets. Lift and rig only from the four upper ISO corner blocks on each EcoBreeze Frame using a crane. Recommended horizontal sling angles are greater than 45 degrees.
EcoBreeze System Installation 14 Mec hanical Connections Install the EcoBreeze Frame per the EcoBreeze Frame Install Kit instructions. P osition the EcoBreeze N OTE : The power and plumbing connections for the EcoBreeze Frame are located on the end where the unpacking sheet is placed on the protective wrap.
15 EcoBreeze System Installation Unwrap the equipment NOTICE DAMAGE TO EQUIPMENT • Do not remove the plastic wrap until the EcoBreeze Frame is placed on its permanent supports and you are prepared to install the return air ductwork. If the plastic is removed, ensure that the return air plenums on top of the Frame are protected.
EcoBreeze System Installation 16 Remo v e the tension rods T ension rods are installed diagonally across each Module bay to provide support during shipping. 1. Release tension on the rods by loosening the nuts on the ends of the tension rods. 2. Using an M12 wrench, remove the eight bolts securing the tension rod brackets.
17 EcoBreeze System Installation Lower Module drop-do wn box 1. Open the lower-right door on each Module. 2. For shipping, the drop-down box is secured upside down inside the Module. Remove the screws securing the drop-down box (a). NOTE: The screws will be re-used to install the drop-down box.
EcoBreeze System Installation 18 6. Locate the insulation strips packed in the ship-loose kit. 7. Remove the backing from the insulation and apply the insulation around the air transition ducts. 8. Open the damper on the supply air transition. W a ter supply connection N OTE : There are two water supply inlets on the EcoBreeze Frame.
19 EcoBreeze System Installation Connect the water supply to the two 3/4-inch water supply fittings on the EcoBreeze Frame. If necessary , make the connections using the appropriate fittings from the pipe adapter kit. See “Component Identification” on page 5.
EcoBreeze System Installation 20 N OTE : Separate the drain line from the EcoBreeze Frame and the external drain line by a 50 mm (2 in.) air gap in order to prevent back up of contaminated water into the cooling system. N OTE : Pitch the external drain piping at a minimum of 25 mm (1 in.
21 EcoBreeze System Installation Electrical Connections The electrical connections required are the following: • Power to Frame • Control (remote display interface) • Communication - Building Ma.
EcoBreeze System Installation 22 P ower supply to EcoBreeze F rame 1. Use a punch tool to create an access hole as needed for power supply wires entering the main power enclosure. 2. Attach the conduit connector to the access hole on the main power enclosure.
23 EcoBreeze System Installation Remote displa y interface See EcoBreeze remote display installation instructions for additional information. The remote display interface enclosure contains the LCD display that is used to control the EcoBreeze from a remote location.
EcoBreeze System Installation 24 3. Wire the expansion bus to the 124, 125, and 126 contacts on the terminal block in the remote display interface enclosure.
25 EcoBreeze System Installation Building Management System The Modbus interface allows the EcoBreeze System to communicate with a building management system (BMS).
.
.
W orldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www .apc.com/support/contact . 6/2014 990-3976D-001 © Schneider Electric is owned by Schneider Electric Industries S.A.
Een belangrijk punt na aankoop van elk apparaat Schneider Electric ACECFR40201SE (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Schneider Electric ACECFR40201SE heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Schneider Electric ACECFR40201SE vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Schneider Electric ACECFR40201SE leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Schneider Electric ACECFR40201SE krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Schneider Electric ACECFR40201SE bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Schneider Electric ACECFR40201SE kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Schneider Electric ACECFR40201SE . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.