Printed in U.S.A. 1/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Application DuraDrive ™ Direct Coup led Actuator s are desig ned to be used in both damper and valve control applications. The follow general instructions are for damper applications, refer to the Applicable Liter ature table for valve literature.
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Applicable Literature F-Number Description Audience Purpose F-26750 MX40-6XXX-2XX, MX4X-7XXX-2XXSeries Actuator/Linkage Assembli e.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 3 SPECIFICA TIONS Actuator Inputs Control Signal: On-off, spring return. SPST control co ntacts or T riacs (500 mA rated). Power Input: See T able-1. All 24 V ac circuits are Class 2.
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Table-1 Model Ch art. Part Numbers Actuator Powe r Input Auxiliary Switch Approximate Timing in Seconds @ 70° (21°C) a a T i mi ng was measured with no load applied to the actuator .
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 5 ACCESSORIES For use with MA4X-7XXX: AM-671 Universal Mounting Br acket, AM-693 is r equired AM-672 Universal Mounting Br acket, AM.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 TYPICAL APPLICA TIONS (wiring diagrams) Figure-1 through Fi gure-3 illustrate typical wiring diagra ms for spring return floatin g actuators.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 7 INST ALLA TION Inspection Inspect the package for damage. If damaged, notif y the appropriate carrier immediate ly . If undamaged, open the package and inspect the device for obvious damage.
8 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Precautions General War n i ng : • Electrical shock hazard! Disconnect the power supply (line power) before installation to prevent electric shock and equipment damage.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 9 Mounting Caution: T o remain in NEMA 2/IP54 compliance, the MA4X-715X an d MA4X-707X series actuators should be mounted with con duit end d own.
10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 B - Left - Short Shaft B - Right - Short Shaft 1. Assemble mounting clamp. 2. Assemble retaining clip. 3. Place actuator over shaft. 4. Hand tighten clamp nuts. R "L" Marker 1 2 U niversa l m ountin g clamp .
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 11 C - Left and Right 1/2 1/2 Center the Universal Brac ket in the Slot 6 x 2 5. Center bracket in slot. 6. Drill two holes. 7. Start one screw. 8. Swing bracket down. x 1 7 8 #8 S heet Meta l S cre w 1 1 1 .
12 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 MA4X-707X and MA4X-715X Series Installat io n Caution: Do not drill additional h oles in the actu ator bod y . Six p re-drilled holes are lo cated on each side, unde r the label, to a ccept #10-24 thread-formi ng screws for mounting accessories.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 13 B Shaft Rotates Clockwise T o Open Shaft Rotates Counterclockwise T o Open A - Left A - Right This step determines shaft rotation. Linkage may change damper direction. For MA41-707X and MA41-715X only (manual override).
14 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 C - Left C - Right - Long Shaft 1. Assemble mounting clamp. 2. Assemble retaining clip. 3. Place actuator over shaft. 4. Hand tighten clamp nuts. R 20 10 0 -5 30 40 L 20 10 0 -5 30 40 Correct clamp mounting position if actuator is locked with 5° preload.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 15 E- Left E- Right C 12 R L Centerline 15 10 R R 0° 14 5° 9 11 9. Loosen clamp nuts. 10. Check that the shaft is in full zero position. For MA41-707X and MA41-715X only: 1 1. T ighten clamp nuts to 8 - 10 ft-lb (1 1 - 14 Nm).
16 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 F- Left F- Right x 2 16 x 2 16 R L For MA40-707X and MA40-715X only: 16. Tighten bracket screws.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 17 Jackshaft Insta llation (MA40-704X Series) The MA40-704X actuator is desi gned for use with jackshafts up to 3/4" (19 mm) in diameter . In most applications, the MA40-704X actuato r may be mounted in the same manner as a standard damper shaft application.
18 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Wiring Requirement s Control and Power Leads See T able-3 for power wiring data.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 19 Auxiliary Switches The MA40-704X-501 series actuators include one built-in SPDT auxi liary switch which ca n be used for interfacing or signaling (e.g., for fan start-up). The switch is adjustable between 0° and 95° of rotation (0 to 1 scale).
20 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 Rotation Limitation for MA4X-7 15X and MA4X-707X Serie s The AM-689 rotation limiter is used in conjuncti o n with the tab on the universal cla mp or the AM-686 position ind icator which comes with th e AM-689.
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 21 CHECKOUT After the entire system has been installed and the actuator has been powered up, the following check can be made fo r proper system op eration. Ch eck for correct operation of the damper while actuator is being stroked.
22 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8 DIMENSIONAL DA T A Figure-7 and Fig ure-8 dimensions are in inches (mm). 2-25/64 (61) 4 (103) 10-1/2 (267) 3-1/2 (89) 2-7/64 (53) Dimensions shown are in inches (mm). 6 Holes for #10-24 Screws 7-1/2 (191) Note: These are not through holes .
F-26642-8 © Copyright 2010 Schneider Electric All Rights Reserved. 23 s 3 Holes for #10-24 Screws 6-13/64 (157) 3-21/32 (93) 4 (103) 2 (50) 47/64 (19) 4-57/64 (125) 6-51/64 (172) 3-5/32 (80) 13/32 (10) 3-1/2 (62) 1/4 (6.4) 49/64 (19) 1 (25) 2-13/32 (61) Dimensions shown are in inches (mm).
Copyright 2010, Schnei der Ele ctric All brand names, trademarks and regist ered trademarks are the property of their re spective owners. Information cont ained within this document is subject to chang e without notice. F-26642-8 www .schneider-electric.
Een belangrijk punt na aankoop van elk apparaat Schneider Electric MA4X-707X (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Schneider Electric MA4X-707X heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Schneider Electric MA4X-707X vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Schneider Electric MA4X-707X leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Schneider Electric MA4X-707X krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Schneider Electric MA4X-707X bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Schneider Electric MA4X-707X kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Schneider Electric MA4X-707X . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.