MODEL 3100-XX FLAME DETECTOR.
Sierra Monitor Corporation 1991 T arob Court, Milpitas, CA 95035 (408) 262-661 1, T oll Free: 800-727-4377 Fax: 408-262-9042 MODEL 3100-XX Flame Detector APPLICABILITY & EFFECTIVITY This manual pr.
Instruction Manual T able of Contents TABLE OF CONTENTS SECTION PAGE 1 . PRODUCT DESCRIPTION 1 2 . OPERA TION 2 2.1 General 2 2.2 Field-of-V iew 3 2.3 Range 3 2.4 Environment 3 2.5 Configuration 3 2.6 LED operation 4 2.7 Relay operation 5 3 . INST ALLA TION 7 3.
Model 3100 Series Flame Detector (1 1/04) Page: 1 Instruction Manual FIGURE 1-1: Model 3100 Series Flame Detector 1. PRODUCT DESCRIPTION 1.1 Introduction All versions of the Model 3100 Flame Detector Se- ries utilize Ultraviolet, Infrared and V isible spectrum to provide continuous and reliable flame detection.
Instruction Manual Page: 2 Model 3100 Series Flame Detector (1 1/04) 2 . OPERA TION 2. 1 General When the Model 3100 Flame Detector is powered up, the microprocessor checks the configuration switch settings and configures the detector . The mi- croprocessor then runs a full series of self tests.
Model 3100 Series Flame Detector (1 1/04) Page: 3 Instruction Manual 2.2 Field-of-V iew (See Figur e 2-1) Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de- tectors ability to cover the threat area.
Instruction Manual Page: 4 Model 3100 Series Flame Detector (1 1/04) LED 1 LED 2 Mounting Screw (2 locations) Configuration Switches 2.5.2 V erify Control The Enhanced Model 3100-02, -03, -04, - 05 and -06 have the V erified Fire function.
Model 3100 Series Flame Detector (1 1/04) Page: 5 Instruction Manual (“on” or “off”) of a switch (SW1-SW8). The first flash pattern indicates the position of the first switch (SW1), with each consecu- tive flash indicating the position of the next switch in order .
Instruction Manual Page: 6 Model 3100 Series Flame Detector (1 1/04) ing” - remain energized until power is re- moved, ”Fire Following” - de-energize a short time after the fire is no longer detected. The “J2” connector provides connections for both normally open contacts and normally closed contacts on the Fire Relay .
Model 3100 Series Flame Detector (1 1/04) Page: 7 Instruction Manual 3. 0 INST ALLA TION 3.1 General Precautions All wiring and installation must be done in accor- dance with the NFP A 70 and 72 standards and must comply with any codes specific to the application or location.
Instruction Manual Page: 8 Model 3100 Series Flame Detector (1 1/04) 3.3.5 Auxiliary Relay The Auxiliary Relay connector is located be- tween the Power and Fire Relay connectors. The connection points are labeled “Aux In” and “Aux Out”. The Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 9 Instruction Manual 5 . 0 TROUBLESHOOTING The flame detector has several built-in self test mechanisms which verify function and calibration. The following procedure covers most faults and problems which may occur during installation or during the course of normal operation.
Instruction Manual Page: 10 Model 3100 Series Flame Detector (1 1/04) 1. If the relay closes (0 ohms on the meter) and the LEDs come “on” the detector is operating normally .
Model 3100 Series Flame Detector (1 1/04) Page: 11 Instruction Manual 6 .0 SPECIFICA TIONS SIERRA MONITOR CORPORA TION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment.
Instruction Manual Page: 12 Model 3100 Series Flame Detector (1 1/04) Figure A-2: Model 3100 Series Dimensions Figure A-1: Model 3100 Series Exploded V iew APPENDIX A.
Model 3100 Series Flame Detector (1 1/04) Page: 13 Instruction Manual Figure A-3: Model 3100 Series Common W iring Connections.
Instruction Manual Page: 14 Model 3100 Series Flame Detector (1 1/04) Figure A-4: Model 3100 Series (Enhanced) W iring Connections Factory jumpers are used to set NC or NO connections.
Model 3100 Series Flame Detector (1 1/04) Page: 15 Instruction Manual APPENDIX B T ABLES B.1 Dip Switch Settings B.1.1 Sensitivity Sensitivity SW1 SW2 Level 20 Foot O N O N 4 40 Foot OF F O N 3 60 Foot O N OF F 2 80 Foot OF F OF F 1 B.
Instruction Manual Page: 16 Model 3100 Series Flame Detector (1 1/04) B.2 Connectors B.2.1 Fire Relay Connector (J2) Fire Relay Description Pin 1 (Left Most) & Pin 2 Normally Open Side of Relay Pin 3 & Pin 4 (Middle) Common or Center Side of Relay Pin 5 & Pin 6 (Right Most) Normally Closed Side of Relay B.
Model 3100 Series Flame Detector (1 1/04) Page: 17 Instruction Manual B.3 V erify/Aux. Relay Configurations Model # V erify Relay Aux. Relay 3100-02 Open Contacts Closed Contacts 3100-03 Closed Contac ts Open Contacts 3100-04 Open Contacts Open Contacts 3100-05 Closed Contact Closed Contacts B.
Instruction Manual Page: 18 Model 3100 Series Flame Detector (1 1/04) B.7 Detector Response to Fuels T able Fuel Distance Fire Size Response T ime Heptane 80 Feet 1 Square Foot Less than 3 sec. Silane 5 0 Feet 18 inch jet Less than 3 sec. Hydrogen 15 Feet 18 inch jet Less than 5 sec.
Model 3100 Series Flame Detector (1 1/04) Page: 19 Instruction Manual APPENDIX C -- WIRING CONNECTIONS.
Instruction Manual Page: 20 Model 3100 Series Flame Detector (1 1/04) Index A Alarm Mode 2, 4 V erified 2 Auxiliary Relay 1, 2, 5, 6, 7 C Cleaning 8 Conduit 7, 11 Configuration Relay Control 4 Sensitivity 3 Switches 3, 4 V erify Control 4 Configuration Switches 5 Connection 7 Connector Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 21 Instruction Manual T T esting 8 U Ultraviolet 3 V V erified Fire 2, 4, 5, 6 V erify Control 4 Relay 2, 4, 5, 6, 7, 15 V erify Control 6, 15 V ersions.
Een belangrijk punt na aankoop van elk apparaat Sierra Monitor Corporation 3100-01 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Sierra Monitor Corporation 3100-01 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Sierra Monitor Corporation 3100-01 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Sierra Monitor Corporation 3100-01 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Sierra Monitor Corporation 3100-01 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Sierra Monitor Corporation 3100-01 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Sierra Monitor Corporation 3100-01 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Sierra Monitor Corporation 3100-01 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.