Sierra Monitor Corp. 1991 Tarob Ct. Milpitas, CA 95035 USA 408-262-6611, Toll Free 800-727-4377, FAX: 408-262-9042 Visit our Web Site: www.sierramonitor.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 1 Sentry Controller MODBUS Memory Map Detail 1 All Registers are MODB US 16 bit registers 2 There are five different ways of using M ODBUS registers ( see italic reference number in left colu mn for each address ) 2.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 2 Read Only Parameters Modbus Address Parameter Units FIX EGU Discrete 40001:0 High alarm bi ts - sensor 1 40001:1 High alarm bi ts - sensor 2 40001:2.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 3 Modbus Address Parameter Units FIX EGU 40007:0 High alarm relay lat ched – sensor 1 40007:1 High alarm relay lat ched – sensor 2 40007:2 High al.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 4 Modbus Address Parameter Units FIX EGU 40020:0 Sensor 1: Status 2 Sensor Disconnected (Trouble Bits) 40020:2 Sensor 1: Voltage Re gulator Failure 40.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 5 Modbus Address Parameter Units FIX EGU 40040:0 Sensor 3: Sensor Disconnected (Trouble Bits) 40040:2 Sensor 3: Voltage Regul ator Failure 40040:3 Sen.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 6 Modbus Address Parameter Units FIX EGU 40060:0 Sensor 5: Sensor Disconnected (Trouble Bits) 40060:2 Sensor 5: Voltage Regul ator Failure 40060:3 Sen.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 7 Modbus Address Parameter Units FIX EGU 40080:0 Sensor 7: Sensor Disconnected (Trouble Bits) 40080:2 Sensor 7: Voltage Regul ator Failure 40080:3 Sen.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 8 Analog Process Variables Modbus Address Parameter Units FIX EGU 40111 Sensor 1 concentration % / PPM 0 - 6553.5 40112 Sensor 2 concentration % / PPM 0 - 6553.5 40113 Sensor 3 concentration % / PPM 0 - 6553.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 9 Modbus Address Parameter Units FIX EGU 40156 Sensor 6 Power (H 2 S and COMB only ) 40157 Sensor 7 Power (H 2 S and COMB only ) 40158 Sensor 8 Power .
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 10 Modbus Address Parameter Units FIX EGU 40224 Sensor 1 Input Value - Multiplex 0 0 - 6553.5 40225 Sensor 1 Input Value - Multiplex 1 0 - 6553.5 40226 Sensor 1 Input Value - Multiplex 2 0 - 6553.5 40227 Sensor 1 Input Value - Multiplex 3 0 - 6553.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 11 Modbus Address Parameter Units FIX EGU 40266 Sensor 3 High Alarm Ti me Mont h 40267 Sensor 3 High Alarm Ti me Day 40268 Sensor 3 High Alarm Ti me H.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 12 Modbus Address Parameter Units FIX EGU 40311 Sensor 4 High Conc. Tim e Month 40312 Sensor 4 High Conc. Tim e Day 40313 Sensor 4 High Conc. Tim e Hr 40314 Sensor 4 High Conc. Tim e Min 40315 Sensor 4 Low Conc.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 13 Modbus Address Parameter Units FIX EGU 40356 Sensor 5 Input Value - Multiplex 0 0 - 6553.5 40357 Sensor 5 Input Value - Multiplex 1 0 - 6553.5 40358 Sensor 5 Input Value - Multiplex 2 0 - 6553.5 40359 Sensor 5 Input Value - Multiplex 3 0 - 6553.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 14 Modbus Address Parameter Units FIX EGU 40398 Sensor 7 High Alarm Ti me Mont h 40399 Sensor 7 High Alarm Ti me Day 40400 Sensor 7 High Alarm Ti me H.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 15 Modbus Address Parameter Units FIX EGU 40443 Sensor 8 High Conc. Tim e Month 40444 Sensor 8 High Conc. Tim e Day 40445 Sensor 8 High Conc. Tim e Hr 40446 Sensor 8 High Conc. Tim e Min 40447 Sensor 8Low Conc.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 16 Read/Write Parameters High Alarm Limits Modbus Address Parameter Units FIX EGU 40501 Sensor 1 % / PPM 0 - 65535 40502 Sensor 2 % / PPM 0 - 65535 40.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 17 40550 Sensor 4 Calib. Coeff. 1 k1 ccn ccn ccn 40551 2 k2 vmin vmax vmi n 40552 3 k3 vmax - vmax 40553 4 n1 gasfac - - 40554 5 n2 - - - 40555 6 n3 - - - 40556 7 bp12 - - - 40557 8 bp23 - - - 40558 9 ccn - - - 40560 Sensor 5 Calib.
Sentry MODBUS I/O Memory Map March 4, 2005 Page : 18 Control Bits Modbus Address Parameter Units FIX EGU 40601 System Reset 40602 Alarm Reset 40603 History Reset 40610 System Tim e Month 40611 System .
Een belangrijk punt na aankoop van elk apparaat Sierra Monitor Corporation Gas Detector (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Sierra Monitor Corporation Gas Detector heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Sierra Monitor Corporation Gas Detector vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Sierra Monitor Corporation Gas Detector leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Sierra Monitor Corporation Gas Detector krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Sierra Monitor Corporation Gas Detector bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Sierra Monitor Corporation Gas Detector kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Sierra Monitor Corporation Gas Detector . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.