Gebruiksaanwijzing /service van het product 07-1126 van de fabrikant SPX Cooling Technologies
Ga naar pagina of 20
/ Mar le y Ultra Low -Noise Fan / User Manual 07 -1 126.
.
3 Cont ents General Information ...................................................................... 4 Installation .................................................................................... 5 Operation ....................................
4 Gener al Infor mation Description The Marley Ultra Low-Noise series of fans represent the top in the new generation of super low noise fans—the FRP blades have been developed to meet the most stringent noise limitations. The fans permit variable pitch adjustment at standstill and feature a simplified design.
5 Installation Rotation and Flow Direction The rotation direction is correct when the airflow moves from the convex back (suction surface) of the blade, to the concave side (pressur e surface). Figure 1 shows the conventional clockwise di- rection of rotation and normal direction of airflow as viewed from the dischar ge face of the rotor .
6 Installation 1 0 B 1 0 A 1 5 9 3 7 2 6 10 4 8 Figure 2.
7 Installation T or que hub assembly bolts 11 according to the following table: Fan Diameter inches Flange T ype Bolt T ype Bolt T or que N·m ft·lb 84" to 96" T ype 115 M16 cl. 8.8 230 169 M16 cl. A4-70 126 93 M16 cl. A4-80 168 124 108" to 168" T ype 190 M20 cl.
8 Installation The drive shaft end must remain recessed at least 1 ⁄ 32 " in the hub bore to prevent dangerous rotor vertical translation once retaining bolt 16 has been tightened to the shaft end. Never power the drive shaft with bushing bolts not torqued or bushing improperly positioned.
9 Installation Rotate the blade on its axis until the requir ed pitch angle is ob - tained. Check there is no gap between each blade shaft shoulder and cor - responding pillow block. T or que pillow block bolts 15 according to the following tables, complying with bolt orientation and tightening order as shown in Figure 4.
10 Installation Fan Diameter inches Bolt 15 Bolt T or que N·m ft·lb 84" to 96" M18 282.5 208 108" to 120" M20 400.3 294 132" to 144" M24 679.8 500 The screw class information is shown in the fan documenta- tion part list.
11 Oper ation Prior to Start-Up 1––Make sur e all the pillow blocks are fixed to the hub boss—if any movement of the blocks is detected, do not operate the fan and check the torque of bolts 15 .
12 Oper ation 3––After the r otor has been running for one hour , check the tor que of the hub screws 15 . 4––Repeat the check of screws 15 after 24 hours fr om start-up.
13 Maint enance Maintenance and Operation 1––Inspect the overall fan condition periodically . Inspection intervals depend on fan operating conditions and may vary from a minimum of 2 weeks to a maximum of 6 months. The following components should be specifically inspected when inspecting the overall fan conditions: - Screw tor que.
14 Maint enance Possible Causes of Vibration The actual causes of vibration may change considerably . Some of the most common are as follows. 1–– Unbalance of one or more blades: the vibration cau.
15 Maint enance 9––W or n output shaft bearing: this condition generates vibration on the tip path plane at a frequency equal to the r otor RPM. 10––The fan and/of the structure bolts are not tightened: in this case all the bolts have to be tightened.
16 P ar ts List Item Figure 6 Description Standard Material Standard Protection 1 Blade FRP –– 2 Coupling Flange Steel Epoxy Paint 3 Hub Disk Steel Epoxy Paint 4 Lower Pillow Block Aluminum ––.
17 P ar ts List 16 10B 10A 14 13 12 3 7 4 6 5 12 15 11 8 2 1 17 16 10 9 8 Figure 6.
18 T r oubleshooting T rouble Cause Remedy Low air flow Low power absorption System congestion. Clean the entire system. Obstacles to the air flow . Check the real obstacles area and the inlet shape towards the original design.
.
M0 7 -1126 7 4 01 WES T 129 STR E ET | OVER LAN D P AR K, KANSAS 66213 U N ITE D ST A TES | 913 664 7 400 | spxcooling@spx.com | spxcooling.com In the interest of technological progress, all products are subject to design and/or material c hange without notice.
Een belangrijk punt na aankoop van elk apparaat SPX Cooling Technologies 07-1126 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen SPX Cooling Technologies 07-1126 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens SPX Cooling Technologies 07-1126 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding SPX Cooling Technologies 07-1126 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over SPX Cooling Technologies 07-1126 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van SPX Cooling Technologies 07-1126 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de SPX Cooling Technologies 07-1126 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met SPX Cooling Technologies 07-1126 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.