Gebruiksaanwijzing /service van het product SBD71120NE van de fabrikant State Industries
Ga naar pagina of 36
1 MODELS SBD71120NE THRU SBD85500NE COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER • INSTALLATION • OPERATION • MAINTENANCE • LIMITED WARRANTY PLACE THESE INSTRUCTIONS ADJACENT T O HEA TER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. Printed in U.
2 ROUGH-IN-DIMENSIONS See Models Below FIGURE 1 ST ANDARD SANDBLASTER - T ABLE 1A INPUT APPROX. GA S H VENT CONNECTIONS Approximate RA TE T ANK INLET DIA INLET OUTLET Ship. Weight MODEL BTU/Hr. CA P . A B C D E F G I J TO P FRONT BACK TOP FRONT BACK STD.
3 T ABLE 1C - HEA TER PERFORMANCE DA T A SBD MODELS INPUT APPROX. RECOVERY RA TING CAP ACITIES (GPH AND LPH) R A TE G A L E FF . 30° F 40° F 50° F 60° F 70° F 80° F 90° F 100° F 1 10° F 120° F 130° F 140° F MODEL BTUH C A P .
4 T ABLE OF CONTENTS ROUGH-IN-DIMENSIONS ................................................ 2- 3 T ABLE OF CONTENTS ..................................................... 4 FOREWORD ..................................................................... 4 GENERAL SAFETY INFORMA TION .
5 IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERA TE HEA TER UNTIL ALL CORRECTIVE STEPS HA VE BEEN MADE BY A QUALIFIED SERVICEMAN. 1. EXTERNAL FIRE.
6 IMPROPER AND INEFFICIENT OPERA TION OF THE APPLIANCE RESUL TING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESUL T IN SERIOUS PERSONAL INJURY OR DEA TH. Y ou should contact your gas supplier for any specific changes which may be required in your area.
7 Continued pilot outage preceded by higher than usual water temperature is evidence of high limit switch operation. Contact your dealer or servicer to determine the reason for operation. ELECTRONIC IGNITION CONTROL Each heater is equipped with a Honeywell ignition module.
8 W ARNING THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS W A TER HEA TERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERA TED OR REP AIRED.
9 HARD W A TER Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. See MAINTENANCE section for details of tank cleanout procedure.
10 VENTING WARNING THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION. Heater must be protected from freezing downdrafts.
11 MODEL 120 Input: 120,00Btuh T otal V ent Height (Feet) Draft Hood: 5” 6 8 10 15 20 30 50 100 Input Btuh Rise V ent Connector Diameter (inches) 120,000 1 F t .
12 MODELS 250, 251 Input: 250,000, 251,000 T otal V ent Height (Feet) Draft Hood: 6” 6 8 10 15 20 30 50 100 Input Btuh Rise V ent Connector Diameter (in inches) 250/251,000 1 Ft .
13 ASME ratings cover pressure relief capacities. A.G.A. ratings cover release rate with temperature actuation. In addition to the appliance relief valve, each remote storage tank which may be used in.
14 DISCONNECT THE HEA TER AND ITS MANUAL GAS SHUTO FF V AL VE FROM THE GAS SUPPL Y PIPING SYSTEM DURING ANY SUPPL Y PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 Kp a). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEA TER FOR TEST PRESSURES OF 1/2 PSIG (3.
15 INST ALLA TION DIAGRAMS-TOP INLET/OUTLET USAGE GENERAL The type, size and location of the relief valves must be in accordance with local codes. The locations of the relief valves shown in the installation diagrams are typical. The heater has a factory installed high temperature limit switch and temperature and pressure relief valve.
16 VERTICAL ST ORAGE T ANK AND FORCED CIRCULA TION DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 27. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSARY TO OBT AIN ADEQUATE BOOSTER OUTPUT , AD D AN ANTI-SCALD VA L VE FOR HOT WA TER SUPPLIED TO FIXTURES.
17 DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W A TER TEMPERA TURE CONTROL W ARNING ON PAGE 27. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBTA IN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI- SCALD V AL VE FOR HOT WA TER SUPPLIED TO FIXTURES.
18 INST ALLA TION DIAGRAMS-SIDE INLET/OUTLET USAGE DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES. SEE W ATER TEMPERA TURE CONTROL WARNING ON P AGE 27. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSARY TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI- SCALD V AL VE FOR HOT WA TER SUPPLIED TO FIXTURES.
19 ONE OR TWO TEMPERA TURE - ONE HEA TER, HIGH TEMPERA TURE STORAGE WITH OR WITHOUT RECIRCULA TION HEA TER WITH OR WITHOUT MIXING V A L VE HEA TER WITH MIXING V A L VE AND RECIRCULA TED SANITIZING LOOP NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) W A TER CIRCULATION.
20 TWO TEMPERA TURE - TWO PRE-HEA TERS WITH MIXING V A L VE OR BOOSTER HEA TER WITH OR WITHOUT BUILDING RECIRCULA TION TWO PRE-HEATERS WITH MIXING VALVE TWO PRE-HEA TERS WITH BOOSTER HEA TER DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES.
21 MEDIUM TEMPERA TURE - ONE HEA TER WITH AUXILIAR Y STORAGE T ANK FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION VERTICAL ST ORAGE T ANK HORIZONTAL STORAGE TANK DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES.
22 MANIFOLD KITS TWO UNIT MANIFOLD KIT (P ART NO. 78692) THREE UNIT MANIFOLD KIT (P ART NO. 78593) FOUR UNIT MANIFOLD KIT (P ART NO. 78694) DIMENSIONS “A” INCHES (CM) MODEL LOW PROFILE VERTICAL HOOD “A” SBD MODELS SBD MODELS 1 2 0 69.75” (177cm) 69.
23 MECHANICAL VENTING SINGLE UNIT INST ALLA TION When mechanical venting of these heaters is desired, the following kits are available. SBD 120 through the SBD 200/A S tate p art number 193933 SBD 250.
24 OPERA TION IMPORT ANT A qualified person must perform the initial firing of the heater . At this time the user should not hesitate to ask the individual any questions which they may have in regard to the operation and maintenance of the unit. An Operational Checklist is included at the rear of this manual.
25 1 . ROT A TE THERMOST A T DIAL -BY HAND- COUNTERCLOCKWISE T O LOWEST SETTING . SEE STEP 5 ABOVE. 2 . TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE IF SERVICE IS TO BE PERFORMED. 3 . REMOVE CONTROL ACCESS P ANEL. 4 . TURN KNOB OF GAS CONTROL V AL VE CLOCKWISE TO “OFF” POSITION.
26 1 . RO T A TE THERMOSTA T DIAL -BY HAND- COUNTERCLOCKWISE TO LOWEST SETT ING . SEE STEP 5 ABOVE. 2 . TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE IF SERVICE IS TO BE PERFORMED. 3 . REMOVE CONTROL ACCESS P ANEL. 4 . TURN KNOB OF GAS CONTROL V AL VE CLOCKWISE TO “OFF” POSITION.
27 V alves for reducing point-of-use temperature by mixing cold and hot water are available. Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority . The water temperature is controlled by a thermostat, Fig.
28 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.
29 TYPICAL PILOT AND MAIN BURNER FLAMES FIGURE 16 If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or blocks the air openings to the burner or heater . NOTE: Cleaning of main burners.
30 VENTING SYSTEM Examine the venting system every six months for obstructions and/or deterioration of the vent piping. Remove all soot or other obstructions from chimney which will retard free draft. REMOTE STORAGE T ANK TEMPERA TURE CONTROL The water temperature in the storage tank (if used) is controlled by the storage tank temperature control.
31 UN•LIME ® and the booklet may be obtained through your State dealer or distributor . FIGURE 18 DELIMING SOL VENTS S tate recommends the use of UN•LIME for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products.
32 1. With the 5 gallon Up-N-Down container in the vertical position, unscrew the plastic vent cap in the handle and pierce the plastic membrane over the vent boss under the cap to allow the container to vent. Note: If your container does not have the vent cap and vent boss, drill a 3/16" hole in the handle.
33 PIN END VIEW 24 V .A.C. NORMAL SEQUENCE OF OPERA TION B . DAMPER HAS OPENED, NO COMBUSTION VOL T AGE ACROSS: 4 & 1; 4 & 2; 4 & 3: 1. Check for power at ignition module terminals. If 24V AC power is present damper is working properly . 2.
34 OPERA TIONAL CHECKLIST This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERA TION” should be used as an on-the-job troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction.
35.
36 500 Lindahl Parkway , Ashland City , TN 37015 Phone: 800-821-2017 Fax: 800-644-9306 www.stateind.com.
Een belangrijk punt na aankoop van elk apparaat State Industries SBD71120NE (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen State Industries SBD71120NE heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens State Industries SBD71120NE vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding State Industries SBD71120NE leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over State Industries SBD71120NE krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van State Industries SBD71120NE bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de State Industries SBD71120NE kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met State Industries SBD71120NE . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.