Gebruiksaanwijzing /service van het product SSE-5 van de fabrikant State Industries
Ga naar pagina of 24
1 • Inst allation • Operation • Maintenance • Checklist • Limited Warranty CAUTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE INST ALLING AND USING THIS APPLIANCE. KEEP THIS MANUAL WITH THE HEA TER FOR FUTURE REFERENCE.
2 RECOVER Y CAP ACITY DIMENSIONS RECOVERY RA TE IN GALLONS PER HOUR * T emperature Rise F° (C°) T ank Cap acity Maximum All Dimensions in Inches (mm) Approx. Ship in Gals.(Ltrs) KW Input A B C D Wt.Lbs.(Kgs) 5 1 9 3 2 0 1 / 2 521mm 1 6 1 / 4 413 mm 21 1/2 546 mm 5 1/4 133 mm 82 37.
3 T ABLE OF CONTENTS P AGE ROUGH-IN-DIMENSIONS ...................................... 2 RECOVERY CAP ACITY ....................................... 2 F O R E W O R D ......................................................... 3 T ABLE OF CONTENTS .......
4 GETTING TO KNOW YOUR W A TER HEA TER Below is an illustration of the water heater with its features called out. The text of this manual will refer to the items shown.
5 GENERAL SAFETY INFORMA TION INSULA TION BLANKETS Insulation blankets available to the general public for external use on electric water heaters are not approved for use on your S tate water heater . The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters.
6 RELIEF DEVICES An unplugged 3/4” NPT relief valve opening is provided for installing temperature and pressure relief valve. CAUTION: TO REDUCE THE RISK OF EXCESSIVE PRESSURES AND TEMPERA TURE IN T.
7 PIPING DIAGRAM ONE OR TWO TEMPERA TURE - ONE HEA TER ONE OR TWO TEMPERA TURE - TWO HEA TER DANGER : TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES.
8 ONE OR TWO TEMPERA TURE - THREE HEA TERS ONE OR TWO TEMPERA TURE - FOUR HEA TERS CAUTION: IF BUILDING COLD W A TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V AL VE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED.
9 MEDIUM TEMPERA TURE - ONE HEA TER VERTICAL ST ORAGE T ANK MEDIUM TEMPERA TURE - ONE HEA TER HORIZONT AL STORAGE T ANK *PIPE RELIEF V AL VE TO OPEN DRAIN. †T ANK TEMPERA TURE CONTROL SET A T DESIRED TEMPERA TURE - MAX. 170°F (76.6 mm). HEA TER THERMOST A T SET A T LEAST 5° HIGHER.
10 MEDIUM TEMPERA TURE - TWO HEA TERS HORIZONT AL STORAGE T ANK MEDIUM TEMPERA TURE - TWO HEA TERS VERTICAL STORAGE T ANK RETURN LINE FROM FIXTURE CIRCULA TING LOOP (IF USED) SHOULD CONNECT TO ANY OPENING NEAR BOTTOM OF T ANK. * PIPE RELIEF V AL VE TO OPEN DRAIN.
11 MEDIUM TEMPERA TURE - THREE HEA TERS HORIZONT AL ST ORAGE T ANK MEDIUM TEMPERA TURE - THREE HEA TERS VERTICAL ST ORAGE T ANK * PIPE RELIEF V AL VE TO OPEN DRAIN † T ANK TEMPERA TURE CONTROL SET A T DESIRED TEMPERA TURE (MAX. 170°F (76.6°C). HEA TER THERMOST A T SET A T LEAST 5° HIGHER.
12 MEDIUM TEMPERA TURE - FOUR HEA TERS HORIZONT AL STORAGE T ANK MEDIUM TEMPERA TURE - FOUR HEA TERS VERTICAL ST ORAGE T ANK CAUTION: IF BUILDING COLD WA TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V AL VE OR WA TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED.
13 60°C 75°C 85°C 90°C 60°C 75°C 85°C 90°C (140°F) (167°F) ( 185°F) (194°F) (140°F) (167°F) (185°F) (194°F) TYPES TYPES TYPES TYPES TYPES TYPES TYPES TYPES RUW, T FEPW V , MI T A, TBS .
14 AMPERAGE T ABLE/OVERCURRENT PROTECTION This table provides the total connected heating element load in amperes for branch circuit conductor and over current protection sizing. Single-phase heaters are two wire circuits. Three-phase heaters are three wire circuits.
15 SMALL COMMERCIAL WIRE DIAGRAM 208-240V / 3PH SMALL COMMERCIAL WIRE DIAGRAM 208-240V / 3-1PH.
16 3-1 PHASE CONVERSIONS In the case where the unit is phase convertible and it has only one contactor , jumper wires (provided) must be added according to the phase of the supply voltage. See the diagram below . For single-phase connection, jumpers A-C and B-D must be added.
17 SMALL COMMERCIAL WIRE DIAGRAM 300-600V / 3PH NOTES.
18 DANGER THIS W A TER HEA TER IS EQUIPPED WITH AN ADJUST ABLE THERMOST A T TO CONTROL WA TER TEMPERA TURE. HOT W A TER TEMPERA TURES REQUIRED FOR AU T OMA TIC DISHW ASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESUL TING IN SERIOUS PERSONAL INJUR Y AND/ OR DEA TH.
19 MAINTENANCE Always close the front access door after making a temperature adjustment. T urn on electricity . DRAINING The water heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater .
20 6. Remove the elements from the openings. • Use a twisting, pulling action to remove elements scaled beyond size of the tank openings. • Brush loose scale from elements. 7. Lime scale removal. • Place limed ends of heating elements into UN•LIME delimer and allow scale to dissolve.
21 When such a condition is encountered, local codes or inspection agency should be consulted to determine which system is acceptable in your area. These may consist of: • Installation of a second relief valve set to lower than the primary safety relief valve.
22 LEAKAGE CHECKPOINTS INSTRUCTIONS : USE THIS ILLUSTRA TION AS A GUIDE WHEN CHECKING FOR SOURCES OF WA TER LEAKAGE. YOU OR YOUR DEALER MA Y BE ABLE T O CORRECT WHA T APPEARS T O BE A PROBLEM. Water on side of the tank may be condensation due to the panel or insulation not being in place.
23 MODEL SSE LIMITED W ARRANTY S tate W ater Heaters, the warrantor , extends the following LIMITED W ARRANTY to the owner of this water heater: 1. THE TANK If the glass-lined tank in this water heate.
24 500 Lindahl Parkway , Ashland City , TN 37015 Phone: 800-821-2017 Fax: 800-644-9306 ww w.st ateind.com.
Een belangrijk punt na aankoop van elk apparaat State Industries SSE-5 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen State Industries SSE-5 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens State Industries SSE-5 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding State Industries SSE-5 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over State Industries SSE-5 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van State Industries SSE-5 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de State Industries SSE-5 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met State Industries SSE-5 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.