STUDER INNOTEC XP- COMPACT User and installer Manual Combi Inverter, Battery charger and Transfersystem XP-COMPACT XPC 1112 XP-COMPACT XPC 1624 XP-COMPACT XPC 1648 Remote control RCC-01 Temperature sensor CT-35 Solar charge controller XPCxxxx-S AC cable cover CFC-01 IP-23 top cover C-IP23 User manual XP-COMPACT V2.
STUDER INNOTEC XP- COMPACT Summary 1 General Information .................................................................................................................3 1.1 O PERATING INSTRUCTIONS ...................................................
STUDER INNOTEC XP- COMPACT 4.8.3 Delaye d mode of th e Transfer System ............................................................................................ ............. 15 4.9 T HE S OLAR CHARGE CONTROLLER ( OPTION ) .........................
STUDER INNOTEC XP- COMPACT 1 General Information 1.1 Operating instructions This manual is a part of the delivery package of every XP-COMPACT inverter-charger.
STUDER INNOTEC XP- COMPACT 1.5 Precautions This manual must be readily available for the user at all times. The user must be familiar with the precautions and safety aspects. During operation of XP-COMPACT, high voltages are generated at the connections and inside of the appliance which could be deadly fatal.
STUDER INNOTEC XP- COMPACT 2 Introduction The XP-COMPACT is a sine wave inverter with integrated battery charger and solar charge con- troller with many additional functions, it has been developed to be used as stand-alone (no grid feeding) AC provider, or as continuous / break-free current supply provider (UPS).
STUDER INNOTEC XP- COMPACT technical specification (chap.6). The battery ch arger is meant for the lead-acid and lead-gel batter- ies. Thanks to the floating charge system the ba ttery can remain continuously connected.
STUDER INNOTEC XP- COMPACT 2.3.3 Connection in parallel and in serie 12V 12V 12V 12V 24V 3 Mounting and installing 3.1 Installation place The location of the XP-COMPACT must be chosen by the following.
STUDER INNOTEC XP- COMPACT Connecting must be done by qualified staff. Material such as cab le, connectors and distribution boxes, fuses etc. used in the installation must comply with the respective valid low-voltage installa- tion rules and regulations.
STUDER INNOTEC XP- COMPACT 3.6 Cabling/wiring Connecting of the XP-COMPACT is a very important step in the installation. You must take care that all connecting work is carried out in a clean and correct manner and that under no circum- stance a cable is connected to a wrong terminal.
STUDER INNOTEC XP- COMPACT 3.6.6 Connection to Auxiliary Contact On these three terminals is a potential free change-over contact. The maximal permitted current and voltage for this is 16A/250Vac. The LED 5 “Contac t active” shows the position of them: alight means active and off means non-active .
STUDER INNOTEC XP- COMPACT 4.2 Display and control parameters on remote control panel (optional) 16 0 OFF AC OUT Over Temp. Overload AC IN SOLAR CHARGE Contact manual Contact act ive Program COMPA CT .
STUDER INNOTEC XP- COMPACT 13 OFF XP-COMPACT is turned off. Turn- ing it back on is only possible manually. XP-COMPACT is for the time be- ing turned off.
STUDER INNOTEC XP- COMPACT User manual XP-COMPACT V2.0 E 13 perature synchronizes the relay with the alarm signal. In this way, for example, an emergency back up system can be started without any break in the energy supply. 4.6.4 Battery Condition Deep discharging of the lead-acid batteries leads to high losses in capacity and early aging.
STUDER INNOTEC XP- COMPACT 4.7.2 Equalization charging Before you program the XP-COMPACT for Equalizat ion-charge you must check with your supplier that the batteries are suitable for this process. Equalization is recommended for the lead-acid batteries in order to mix well the electrolyte fluid and to clean the lead plates.
STUDER INNOTEC XP- COMPACT the transfer contact is active, then you have at the output AC OUT the same voltag e as that at the input. This voltage can not be modified by the XP-COMPACT! 4.8.1 Set the transfer voltage threshold The voltage threshold of the transfer is factory settled at 200Vac.
STUDER INNOTEC XP- COMPACT 4.10 The Multifunctional Contact In the XP-COMPACT there is a built-in power rel ay. The potential-free change-over contact (NO – NC) of this power relay is connected to the screw terminal AUX CONTACT. Maximum Contact load: 230V ac /12Vdc/24Vdc/16Amp 60Vdc/3 Amp.
STUDER INNOTEC XP- COMPACT 5.3 Battery Condition Built-in microprocessor calculates the actual state of charge of the battery and displays it on LED 15 – 18. The LED 14 is lit when the system is carrying out a charge cycle with equalization. The voltage levels and charge characteristics can be changed through Programming.
STUDER INNOTEC XP- COMPACT 6.1 Standard setting The XP-COMPACT is delivered with the following default setting: 6.1.1 Battery voltage Low voltage 11.6V / 23.2V / 46.4V Float Charge 13.5V / 27.0V / 54.0V End of Charge Voltage 14.4V / 28.8V / 57.6V Equalization 15.
STUDER INNOTEC XP- COMPACT table 6.3.1. If desired, repeat the operation with any other parameter (voltage or time) to be changed. If during 10 seconds no buttons are pressed, the selected values are automatically stored and the XP-COMPACT switches back in to the normal operating status.
STUDER INNOTEC XP- COMPACT 6.4.3.3 Second priority cut-off The Auxiliary Contact can use to cut-off second priori ty load with the criteria of the battery status or overtemp. One of the 4 LED 15 to 18 or 10 will be chosen as the cut off criteria. The second prior- ity loads will be supply only if the ba ttery as a sufficient residual capacity 6.
STUDER INNOTEC XP- COMPACT User manual XP-COMPACT V2.0 E 21 9 Technical Data Model XPC1112 XPC1624 XPC1648 Inverter Nominal battery voltage 12 V 24 V 48 V Input voltage range 9.5 – 17 V 19 – 34 V 38 – 68 V Nominal power 1100 W 1600 W 1600 W Maximum power load 30 min.
Een belangrijk punt na aankoop van elk apparaat Studer XPC 1112 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Studer XPC 1112 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Studer XPC 1112 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Studer XPC 1112 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Studer XPC 1112 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Studer XPC 1112 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Studer XPC 1112 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Studer XPC 1112 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.